Bulletin 150 SMC Dialog Plus™ Controller

2
Installation
Getting Started - Bulletin 150 SMC Dialog Plus™ Controller
The open-style design of the SMC Dialog Plus controller requires that
it be installed in an enclosure. The internal temperature of the
enclosure must be kept within 0°C to 5 °C (32 °F to 12 °F).
The controller is convection cooled. It is important to mount th
controller in a position that allows air to flow vertically through the
power structure. Allow for a minimum of six inches (15 cm) of fre
space around all sides of the controller.
Wiring
Power Wiring
Refer to the product nameplate for power lug termination information
including:
•
Lug wire capacity
•
Tightening torque requirements
•
Lug kit catalog numbers (97-1000A
Control Wiring
Refer to the product nameplate for control terminal wire capacity and
tightening torque requirements. Each control terminal will accept
maximum of two wires.
The SMC Dialog Plus controller accepts control power input of eithe
100-240 V AC, (+ 10/-15%) single-phase, 50/60Hz or 24V AC/DC.
Refer to the product nameplate prior to applying control power.
Connect control power to the controller at terminals 11 and 12. The
control power requirement for the control module is 40 VA. For
controllers rated 97-1000A, control power is also required for the
heatsink fans as defined in Table C. Depending on the specifi
application, additional control circuit transformer VA capacity may
be required.
Table A
Heatsink Fan Power Requirements
SMC Rating
Heatsink Fan V
97-360A
45
500A
145
650-1000A
320
Getting Starting - Bulletin 150 SMC Dialog Plus™ Controller
3
Control Terminals
Figure 1
SMC Dialog Plus Controller Control Terminals
13
12
11
21
22
15
14
23
24
25
18
17
16
26
27
20
19
28
29
30
Table B
Control Terminal Designation
Terminal
Number
➊
Description
11
Control Power Input
12
Control Power Common
13
Controller Enable Input➊
14
Logic Ground
15
Dual Ramp/Option Input ➊
16
Start Input➊
17
Stop Input➊
18
Auxiliary Relay Common
19
N.O. Auxiliary Contact #1
20
N.C. Auxiliary Contact #2
21
Not Used
22
Not Used
23
Not Used
24
Not Used
25
Converter Module Fanning Strip Connection ➊
26
Converter Module Fanning Strip Connection ➊
27
Converter Module Fanning Strip Connection ➊
28
Converter Module Fanning Strip Connection ➊
29
Auxiliary Contact #3
30
Auxiliary Contact #3
Do not connect any additional loads to these terminals. These “parasitic” loads may
cause problems with operation, which may result in false starting and stopping.
4
Getting Started - Bulletin 150 SMC Dialog Plus™ Controller
Figure 2
Typical Wiring Diagram
L1/1
T1/2
L2/3
T2/4
L3/5
T3/6
3-Phase
M❶
Input Power
Fast-acting
SCR Fuses
(optional) ❶
❶
Branch
Protection ❶
❶
SMC Dialog Plus
Controller
❶
Fan Power
Stop ❶
Start ❶
11
12
13
14
15
16
18
19
20
Internal
Auxiliary
Contacts
SMC Dialog Plus
ControlTerminals
❶
17
Customer supplied.
Figure 3
Heatsink Fan Wiring
97A
and
Factory Set
110/120 VAC
1
2
180–500A
Factory Set
110/120 VAC
To
Supply
To
Supply
Jumpers
650–1000A
Factory Set
110/120 VAC
To
Supply
Jumpers
3
4
1
2
3
4
5
1
2
3
4
5
6
Refer to Chapter 3 of the SMC Dialog Plus Controller User Manual
(Publication 150-5.3) for optional 220/240V AC fan power
connections and other sample wiring diagrams. Chapter 7 o
Publication 150-5.3 also provides typical wiring diagrams for the
control options (for example, Pump Control).