allen-bradley bulletin 1336 plus fault reset/auto restart

ALLEN-BRADLEY
ALLEN-BRADLEY
BULLETIN 1336 PLUS
FAULT RESET/AUTO RESTART
APPLICATION NOTE #1336S - 7
May 19, 1997
PURPOSE
The purpose of this document is to provide guidelines for wiring and control
schemes for the Bulletin 1336S AC Drive. This document is to be used as a
suggestion only. Users must ensure that installations meet applicable codes and
are suitable for the existing conditions.
The Bulletin 1336S User Manual should be used as a reference to ensure that
proper wire selection, routing and fusing guidelines are followed.
WHAT THIS NOTE
CONTAINS
The Bulletin 1336S drive can be configured to automatically reset a fault and then
restart the drive. This is useful for unmanned areas that may have frequent power
outages.
The start/stop control inputs must be TWO-WIRE control to allow the drive logic to
perform the auto restart function. This note contains diagrams and parameter
programming used to implement the auto restart function. Two wire control is only
available with INUT MODES 12 - 16, 20, 21 and 24.
INTENDED
AUDIENCE
This application note is intended to be used by personnel familiar with the
hardware components and programming procedure necessary to operate the
Bulletin 1336S.
WHERE IT
IS USED
The diagrams, parameter settings and auxiliary hardware used in this application
note are designed to address specific issues in many different applications. Some
changes by the User may be necessary to apply the concepts of this document to
a specific application.
Faxback Document # 3027 Web location Http://WWW.AB.COM
Page 1 of 3
ALLEN-BRADLEY
DESCRIPTION
The 1336S requires that a 2-wire start/stop circuit be used with the auto restart
function. The start command must remain "logically true" for the auto restart to
function properly. One of the Logic Interface cards must be installed on the drive.
The fault reset function is enabled by setting [Reset/Run Tries] (Parameter 85) to
a value between 1 and 9. This setting then becomes the "counter" value for the
Restart attempts. [Run On Power Up] (parameter 14) must be set to a value of 1.
[Reset/Run Time] (parameter 15) must be set to the time between restart attempts
adjustable between 0.5 sec. and 30 sec.
The drive may be reset by one of 4 methods.
1. Set [Flt Clear Mode] (parameter 39) to “Disabled” (0). Cycle the input power to
the drive and allow the drive to completely discharge the stored energy in the
capacitor bank.
2. Set [Flt Clear Mode] (parameter 39) to “Enabled” (1). This will allow the fault to
be cleared by cycling the STOP input, TB2 terminal 20, false then true. Or
cycle input power to the drive as described in number 1.
3. Set [Flt Clear Mode] (parameter 39) to “Enabled” (1). A write command from a
communications interface to the [Clear Fault] (parameter 51).
4. Set [Flt Clear Mode] (parameter 39) to “Enabled” (1). A Clear Fault input to the
Logic Command word via one of the communication interfaces.
Refer to Figure 1 for diagram.
PARAMETER
SETTINGS
Number
14
Group
Feature Select
Name
Auto Restart
15
Feature Select
Reset/Run Time
85
Feature Select
Reset/Run Tries
Faxback Document # 3027 Web location Http://WWW.AB.COM
Page 2 of 3
Setting
0 = Disabled
1 = Enabled
0.5 - 30 Sec
1.0 = Default
0 = Disabled
1-9 = Attempts
ALLEN-BRADLEY
FIGURE 1 AUTO RESTART WITH 115VAC INTERFACE
R
115V AC
S
T
GND
TB1
1
POT HIGH
2
POT WIPER
3
POT COMMON
4
SIGNAL COMMON
5
0-10V INPUT
6
4-20ma INPUT
7
PULSE INPUT (-)
8
PULSE INPUT (+)
9
METER OUTPUT
+DC
BRK/-DC
JUMPER J5
1-2 (4-20ma)
3-4 (0-10vdc)
10
CR1
11
CR2
12
13
CR3
14
CR3
15
16
CR4
17
CR4
18
TB3
L6E
115VAC INTERFACE
TB3
RUN
19
START
ENCODER B
31
20
STOP
ENCODER A
32
21
COMMON
ENCODER B
33
22
REVERSE
ENCODER A
34
23
JOG
+12VDC
35
24
AUXILIARY
ENC COM
36
25
COMMON
26
SPD SEL 3
27
SPD SEL 2
28
SPD SEL 1
29
COMMON
30
ENABLE
RESET
EXT FAULT
INTERLOCK
INPUT MODE 2
ENABLE
TB1
U
V
W
GND
Faxback Document # 3027 Web location Http://WWW.AB.COM
Page 3 of 3