allen-bradley bulletin 1336 plus 120 volt interface grounded

ALLEN-BRADLEY
ALLEN-BRADLEY
BULLETIN 1336 PLUS
120 VOLT INTERFACE
GROUNDED/UNGROUNDED
APPLICATION NOTE #1336S - 12
May 19, 1997
PURPOSE
The purpose of this document is to provide guidelines for wiring and control
schemes for the Bulletin 1336S AC Drive. This document is to be used as a
suggestion only. Users must ensure that installations meet applicable codes and
are suitable for the existing conditions.
The Bulletin 1336S User Manual should be used as a reference to ensure that
proper wire selection, routing and fusing guidelines are followed.
WHAT THIS NOTE
CONTAINS
The Bulletin 1336S-L6 Logic Interface may be used on a grounded or
ungrounded 120VAC supply. This note will provide assistance in implementing
this interface.
INTENDED
AUDIENCE
This application note is intended to be used by personnel familiar with the
hardware components and programming procedure necessary to operate the
Bulletin 1336S.
WHERE IT
IS USED
The diagrams, parameter settings and auxiliary hardware used in this application
note are designed to address specific issues in many different applications. Some
changes by the User may be necessary to apply the concepts of this document to
a specific application.
DESCRIPTION
GROUNDED 120VAC The 1336S-L6 Interface is isolated from the internal
circuitry of the drive. For a grounded 120VAC system, it is recommended that only
the "hot" side of the secondary be fused. Refer to Figure 1 for the diagram.
UNGROUNDED 120VAC When a 120VAC supply does not have a grounded
secondary, fuses are required for both the "hot" and "common" legs of the
transformer. Refer to Figure 2 for the diagram.
APPLICATION
CONSIDERATIONS
The transformer and fusing selected for the 120VAC power must be capable of
supplying 10ma of current for each input to the 1336S-L6 Interface.
Faxback Document # 3032 Web location Http://WWW.AB.COM
Page 1 of 3
ALLEN-BRADLEY
FIGURE 1 GROUNDED CONTROL WITH 115VAC INTERFACE
R
115V AC
S
T
GND
TB1
1
POT HIGH
2
POT WIPER
3
POT COMMON
4
SIGNAL COMMON
5
0-10V INPUT
6
4-20ma INPUT
7
PULSE INPUT (-)
8
PULSE INPUT (+)
9
METER OUTPUT
+DC
BRK/-DC
JUMPER J5
1-2 (4-20ma)
3-4 (0-10vdc)
10
CR1
11
CR2
12
13
CR3
14
CR3
15
16
CR4
17
CR4
18
START
TB3
L6E
115VAC INTERFACE
TB3
19
START
ENCODER B
31
20
STOP
ENCODER A
32
21
COMMON
ENCODER B
33
22
REVERSE
ENCODER A
34
23
JOG
+12VDC
35
24
AUXILIARY
ENC COM
36
25
COMMON
26
SPD SEL 3
27
SPD SEL 2
28
SPD SEL 1
29
COMMON
30
ENABLE
STOP
EXT FAULT
INTERLOCK
ENABLE
INTERLOCK
INPUT MODE 2
TB1
U
V
W
GND
Faxback Document # 3032 Web location Http://WWW.AB.COM
Page 2 of 3
ALLEN-BRADLEY
FIGURE 1 UNGROUNDED CONTROL WITH 115VAC INTERFACE
R
115V AC
S
T
GND
+DC
BRK/-DC
TB1
1
POT HIGH
2
POT WIPER
3
POT COMMON
4
SIGNAL COMMON
5
0-10V INPUT
6
4-20ma INPUT
1-2 (4-20ma)
7
PULSE INPUT (-)
3-4 (0-10vdc)
8
PULSE INPUT (+)
9
METER OUTPUT
JUMPER J5
10
CR1
11
CR2
12
13
CR3
14
CR3
15
16
CR4
17
CR4
18
START
TB3
L6E
115VAC INTERFACE
TB3
19
START
ENCODER B
31
20
STOP
ENCODER A
32
21
COMMON
ENCODER B
33
22
REVERSE
ENCODER A
34
23
JOG
+12VDC
35
24
AUXILIARY
ENC COM
36
25
COMMON
26
SPD SEL 3
27
SPD SEL 2
28
SPD SEL 1
29
COMMON
30
ENABLE
STOP
EXT FAULT
INTERLOCK
ENABLE
INTERLOCK
INPUT MODE 2
TB1
U
V
W
GND
Faxback Document # 3032 Web location Http://WWW.AB.COM
Page 3 of 3