E-Stop Circuitry

ALLEN-BRADLEY
ALLEN-BRADLEY
BULLETIN 1336 PLUS
ALL - STOP CIRCUIT
APPLICATION NOTE #1336S - 4
June 24, 1997
PURPOSE
The purpose of this document is to provide guidelines for wiring and control
schemes for the Bulletin 1336S AC Drive. This document is to be used as a
suggestion only. Users must ensure that installations meet applicable codes and
are suitable for the existing conditions.
The Bulletin 1336S User Manual should be used as a reference to ensure that
proper wire selection, routing and fusing guidelines are followed.
WHAT THIS NOTE
CONTAINS
The stop circuitry described in this document can be utilized to quickly remove
power from the motor should an All-Stop (E - STOP) be initiated. This circuitry will
not control the braking of the motor but will allow the motor to coast to a stop.
Other means of "braking" the motor and connected load should be utilized for
rapid stopping the machine if required. Refer to Application Note #6, 1336S Motor
Stop-Mechanical, or Application Note #5, 1336S Motor Stop-Electrical.
The normal operation of the drive (start/stop functions) should be through the
control inputs, NOT the ALL-STOP.
Two different control methods are commonly implemented to address the ALLSTOP condition. It is important to note the subtle differences and how they suit a
given application.
INTENDED
AUDIENCE
This application note is intended to be used by personnel familiar with the
hardware components and programming procedures necessary to operate the
Bulletin 1336S.
WHERE IT
IS USED
The diagrams, parameter settings and auxiliary hardware used in this application
are designed to address specific issues in many different applications. Some
changes by the Users may be necessary to apply the concepts of this document to
a specific application.
Faxback Document # 3024 Web location Http://WWW.AB.COM
Page 1 of 5
ALLEN-BRADLEY
TERMS AND
DEFINITIONS
Input contactor - labeled 1K is located between the line supply and the drive
Output contactor - labeled 2K is located between the drive and the motor.
Enable - control input to the drive at TB3 terminal 30 used to enable or disable
the inverter.
DESCRIPTION
One way to accomplish the ALL-STOP is by coordinated control of the ENABLE
input of the drive and an INPUT CONTACTOR. The ENABLE signal must be
present at terminal 30 located on TB3 to "enable" the drive. This signal is used as
a hardware permissive to allow the drive inverter section to operate.
The ALL-STOP button should open the ENABLE circuit and also interrupt power to
the coil of the INPUT CONTACTOR. This circuit will turn off the drive output and
remove power from the drive. Refer to Figure 1 for the circuit diagram.
The second method for removing power to the motor during an ALL-STOP is
coordinated control of the drive ENABLE input and OUTPUT CONTACTOR. The
ALL-STOP will be used to open the circuit to the ENABLE input of the drive and
the OUTPUT CONTACTOR. The Bulletin 100 type contactor has a 6-20 mSec
coil drop out time. This time delay will ensure that the drive output has been turned
off and the motor flux field has decayed prior to opening the contactor. The
OUTPUT CONTACTOR must be energized (closed) prior to a start command.
This allows the contactor to be rated for the
drive amperage rather than full HP rating (600% FLA start).
Refer to figure 2 for the circuit diagram.
Actual drop out time is dependent upon the rating of the contactor. The times
stated above are based on 120 VAC coils and specific Allen-Bradley contactor
models.
APPLICATION
CONSIDERATIONS
Several items will affect the actual timing of each circuit. The following items
should be considered prior to implementing these circuits for use during an ALLSTOP.
The Auto Restart function of the drive will be "active" when two-wire control of the
start/stop functions is used. If these inputs are logically true, the drive will restart
when the ENABLE input returns. Extreme caution should be exercised when
using the Auto Restart function.
Systems using this control configuration should utilize a
separate "reset" switch
or appropriate logic to ensure that the drive is not unintentionally started when the
ENABLE signal is reapplied.
• The input contactor must remain de-energized for at least one minute after
power has been removed from the drive. No more than 3 cycles are allowed within
a five minute period. A ten minute delay is required before attempting the next
three cycles.
• The type of Logic Interface card used on the 1336S will determine how fast the
drive will react to input signals.
Faxback Document # 3024 Web location Http://WWW.AB.COM
Page 2 of 5
ALLEN-BRADLEY
Logic Interface throughput times
INTERFACE CARD
1336-MOD-L4 (TTL)
1336-MOD-L5 (24VDC)
1336-MOD-L6(115VAC)
PICK-UP TIME
1 mSec
4 mSec
7 mSec
DROP-OUT TIME
2 mSec
7 mSec
10 mSec
NOTE: For ungrounded 120V AC systems, refer to Application Note #1336S-12,
1336S 120V AC Interface Grounded/Ungrounded.
Faxback Document # 3024 Web location Http://WWW.AB.COM
Page 3 of 5
ALLEN-BRADLEY
FIGURE 1 ALL-STOP WITH INPUT CONTACTOR
1K
R
115V AC
S
T
GND
TB1
1
POT HIGH
2
POT WIPER
3
POT COMMON
4
SIGNAL COMMON
5
0-10V INPUT
6
4-20ma INPUT
7
PULSE INPUT (-)
8
PULSE INPUT (+)
9
METER OUTPUT
JUMPER J5
1-2 (4-20ma)
3-4 (0-10vdc)
10
CR1
11
CR2
12
13
CR3
14
CR3
15
16
CR4
17
CR4
18
TB3
START
L6E
115VAC INTERFACE
TB3
19
START
ENCODER B
31
20
STOP
ENCODER A
32
21
COMMON
ENCODER B
33
22
REVERSE
ENCODER A
34
23
JOG
+12VDC
35
24
AUXILIARY
ENC COM
36
25
COMMON
26
SPD SEL 3
27
SPD SEL 2
28
SPD SEL 1
29
COMMON
30
ENABLE
STOP
EXT FAULT
INTERLOCK
ALL-STOP
1K
INPUT MODE 2
TB1
U
V
W
GND
Faxback Document # 3024 Web location Http://WWW.AB.COM
Page 4 of 5
ALLEN-BRADLEY
FIGURE 2 ALL-STOP WITH OUTPUT CONTACTOR
R
115V AC
S
T
GND
TB1
1
POT HIGH
2
POT WIPER
3
POT COMMON
4
SIGNAL COMMON
5
0-10V INPUT
6
4-20ma INPUT
7
PULSE INPUT (-)
8
PULSE INPUT (+)
9
METER OUTPUT
JUMPER J5
1-2 (4-20ma)
3-4 (0-10vdc)
10
CR1
11
CR2
12
13
CR3
14
CR3
15
16
CR4
17
CR4
18
TB3
START
L6E
115VAC INTERFACE
TB3
19
START
ENCODER B
31
20
STOP
ENCODER A
32
21
COMMON
ENCODER B
33
22
REVERSE
ENCODER A
34
23
JOG
+12VDC
35
24
AUXILIARY
ENC COM
36
25
COMMON
26
SPD SEL 3
27
SPD SEL 2
28
SPD SEL 1
29
COMMON
30
ENABLE
STOP
EXT FAULT
INTERLOCK
ALL-STOP
2K
INPUT MODE 2
TB1
U
V
W
GND
2K
Faxback Document # 3024 Web location Http://WWW.AB.COM
Page 5 of 5