MVAD040 Series - power, Murata

MVAD040 Series
www.murata-ps.com
40W 2" x 4" AC-DC Power Supply Converter
DESCRIPTION
The MVAD040 series switching power supplies utilize advanced component and circuit technologies
to deliver high efficiency. Designed for Medical, Telecom, and Industrial applications to satisfy 1U
height design considerations, the MVAD040 Series measures only 2.0" x 4.0" x 1.3". All models offer
universal AC input and compliance to worldwide safety and EMC standards.
ORDERING GUIDE
FEATURES
ATURES

ITE (2nd Ed.) and Medical (3rd ed.) MOPP safety
approved

30-40W compact high density

2" x 4" standard footprint

High efficiency up to 89%

Universal AC input

Low profile - 1U package

Convection-cooled operation up to 40W

Complies with 5000m altitude
Model Number
MVAD040-05
MVAD040-12
MVAD040-24
MVAD040-48
Natural Convection Cooling
30W
40W
INPUT CHARACTERISTICS
Parameter
Conditions
Single phase
DC
Input Voltage Operating Range
Input Frequency
Turn-on Input Voltage
Turn-off Input Voltage
Input Current
Input rising at full load
Input falling at full load
90Vac input, full load
At 264Vac, at 25°C cold
start
Inrush Current

RoHS compliant

UL Class I and II approved
OUTPUT CHARACTERISTICS

Less than 0.3W no load input power
Model Number

Complies with ErP/Energy Star requirement
average efficiency>85.3% (24V and 48V)
Main Output (V1)
5V
12V
24V
48V
MVAD040-05
MVAD040-12
MVAD040-24
MVAD040-48
Min.
90
120
47
50
50
Typ.
120/230
50/60
60
Max.
264
300
63
70
70
0.9
Units
Vac
Vdc
Hz
Vac
A
Apk
Main Output
Line, Load, Cross Typical Efficiency
Load Current Peak Load3 Load Capacitance
Voltage (V1)
Regulation
@230Vac full load
5V
12V
24V
48V
0 to 6A
0 to 3.34A
0 to 1.67A
0 to 0.84A
5.0A
2.5A
1.25A
0 to 1200μF
0 to 680μF
0 to 330μF
0 to 220μF
± 2%
± 2%
± 2%
± 2%
80%
87%
88%
89%
Main Output Characteristics (all models)
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
Available now at
www.murata-ps.com/en/3d/acdc.html
For full details go to
www.murata-ps.com/rohs
Parameter
Conditions
Min.
Max.
Units
Transient Response (MVAD040-05 only)
±8
50% load step, 1A/μsec slew rate
%
Transient Response (all other models)
±5
Settling Time to 1% of Nominal
200
μsec
Turn On Delay
After application of input power
1
sec
Output Voltage Rise
Monotonic, 0 to 100% load
50
msec
Setpoint Accuracy
120Vac, 40W, 25°C
± 0.5
%
Output Holdup, MVAD040-05 only
115Vac, 100% load
20
msec
Output Holdup, all other models
115Vac, 100% load
15
msec
Temperature Coefficient
0.02
%/°C
1
%
Ripple Voltage & Noise1
1. Ripple and noise are measured with 0.1 μF of ceramic capacitance and 47 μF of electrolytic capacitance on
each of the power supply outputs. The output noise requirements apply over a 0 Hz to 20 MHz bandwidth. A
short coaxial cable with 50ohm scope termination is used.
2. Unless otherwise specified all readings are taken at 120Vac input and 25 °C ambient temperature.
3. Peak current lasting <15 seconds with a maximum 10% duty cycle and with an average output power of 40W.
CB
Test Certificate
and Test Report
www.murata-ps.com/support
MVAD040.B01 Page 1 of 6
MVAD040 Series
40W 2" x 4" AC-DC Power Supply Converter
ENVIRONMENTAL CHARACTERISTICS
Parameter
Storage Temperature Range
Operating Temperature Range
Operating Humidity
Operating Altitude
MTBF
Shock
Vibration
Safety
Warranty
Outside Dimensions
Weight
Conditions
Min.
-40
-20
-20
10
-200
-200
1M
Typ.
See thermal derating curves
Start up
Non-condensing
For Class I ITE Equipment deployment
Other
Telcordia SR-332 M1C3 25°C
Operating, IEC60068-2-27, half-sine 5G, 6ms,
Complies
3 times per face, 6 faces
Non-operating, IEC60068-2-27, half-sine,
30G, 18ms, 3 times per face, 6 faces
Complies
Operating, IEC60068-2-6, 1.0G, 10-150Hz,
10minutes per axis, on all 3 axes
Complies
Non-operating, IEC60068-2-6, 2.0G,
10-150Hz, 10minutes per axis, on all 3 axes
Complies
Max.
85
70
Units
95
5000
2000
%
°C
m
Hours
IEC60950-1:2005 (2nd Edition); Am1:2009
UL60950-1 2nd Edition,2011-12-19, CSA C22.2 No. 60950-1-07, 2nd Edition,2011-12
EN60950-1:2006 + A11:2009 + A1:2010 + A12:2011
IEC60601-1:2005 + CORR.1(2006) + CORR.2(2007)
ANSI/AAMI ES60601-1 (2005+C1:09 + A2:10), CSA-C22.2 No. 60601-1(2008), MOPP
CE Marking per LVD
2 years
2.0" x 4.0" x 1.3" (50.8mm x 101.6mm x 33.02mm)
0.28lbs (127g) typical (MVAD040-05 only)
0.27lbs (123g) typical (all other models)
PROTECTION CHARACTERISTICS
Parameter
Overvoltage Protection
Overcurrent Protection, MVAD040-05 only
Overcurrent Protection, all other models
Conditions
Latching (60% load)
Hiccup mode
Hiccup mode
Min.
110
110
170
Typ.
Max.
160
160
240
Units
%V1
%A
%A
Conditions
Primary to Earth Ground (1xMOPP)
Primary to Secondary (2xMOPP)4
Secondary to Earth Ground
240Vac, 60Hz, 25°C
264Vac, 60Hz, 25°C
264Vac, 60Hz, 25°C
Min.
1500
4000
500
Typ.
Max.
Units
ISOLATION CHARACTERISTICS
Parameter
Isolation
Leakage Current (under normal conditions)
Touch Current
Vac
Vdc
300
350
100
μA
EMISSIONS AND IMMUNITY
Characteristic
Input Current Harmonics
Voltage Fluctuation and Flicker
Conducted Emissions
ESD Immunity
Radiated Field Immunity
Electrical Fast Transient Immunity
Surge Immunity
RF Conducted Immunity
Magnetic Field Immunity
Voltage dips, interruptions
4. At class I equipment.
Standard
IEC/EN 61000-3-2
IEC/EN 61000-3-3
EN 55022
FCC Part 15
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
IEC/EN 61000-4-11
Compliance
Class A
Complies
Class B, Class A (at Class II equipment)
Class B, Class A (at Class II equipment)
Level 4, Criterion A
Level 2, Criterion A
Level 3, Criterion A
Level 4, Criterion A
Level 2, Criterion A
Level 2, Criterion A
Level 3, Criterion B
www.murata-ps.com/support
MVAD040.B01 Page 2 of 6
MVAD040 Series
40W 2" x 4" AC-DC Power Supply Converter
EMI CONSIDERATIONS
For optimum EMI performance, the power supply should be mounted to a metal plate grounded to all 4 mounting holes of the power supply. To comply with
safety standards, this plate must be properly grounded to protective earth (see mechanical dimension notes). Pre-compliance testing has shown the standalone power supply to comply with EN55022 class A radiated emissions. Radiated emission results vary with system enclosure and cable routing paths.
SAFETY CONSIDERATIONS
1. This power supply is a component level power supply intended for use in class I or class II applications. Secondary ground traces need to be suitably isolated from primary ground traces when used in class II applications.
2. When the power supply is used in class II equipment, all ground traces and components connected to the primary side are considered primary for
spacing and insulation considerations.
3. Double pole/neutral fusing.
PERFORMANCE DATA
MVAD040-12 Eĸciency (%)
MVAD040-05 Eĸciency (%)
88
95
86
93
84
91
82
89
80
87
78
85
76
83
AC90V
AC115V
AC230V
AC264V
74
72
70
AC90V
AC115V
AC230V
AC264V
81
79
77
75
68
0
1
2
3
4
5
6
0
0.5
1
1.5
2
2.5
3
3.5
Output current (A)
Output current (A)
MVAD040-24 Eĸciency (%)
MVAD040-48 Eĸciency (%)
95
95
93
93
91
91
89
89
87
87
85
85
83
83
AC90V
AC115V
AC230V
AC264V
81
79
77
AC90V
AC115V
AC230V
AC264V
81
79
77
75
75
0
0.3
0.6
0.9
1.2
1.5
1.8
0.0
0.2
0.4
Output current (A)
0.6
0.8
1.0
Output current (A)
Inrush waveform (AC264V 25°C)
45
Output power (W)
40
35
30
25
MVAD040-12/24/48 Thermal DeraƟng
MVAD040-05 Thermal DeraƟng
20
15
10
5
0
-20
-10
0
10
20
30
40
50
Ambient temperature (°C)
60
70
80
www.murata-ps.com/support
MVAD040.B01 Page 3 of 6
MVAD040 Series
40W 2" x 4" AC-DC Power Supply Converter
MECHANICAL DIMENSIONS – MVAD040-05 ONLY
All dimensions in inches (mm). tolerance is +/-0.02’ (0.5)
Mounting holes H1 and H2 should be earth-grounded for EMI purpose
Mounting holes H2 is earth ground connection
This power supply requires mounting on standoffs minimum 0.2' (5.0) in height
Dimensions: 2.0" x 4.0" x 1.3" (50.8mm x 101.6mm x 33.02mm)
INPUT/OUTPUT CONNECTOR AND SIGNAL SPECIFICATION AND MATING CONNECTORS
PIN
Description
Input Connector CN1 : Molex 26-62-4030
1
AC Line (V-)
3
AC Neutral (V+)
Spade Connector: #250
GND
Earth Ground
Output Connector CN2 : Molex 26-60-4040
1, 2
V1
3, 4
DC Return
Mating Housing
Crimp terminal/pins
Molex 09-50-8031 with locking ramp
Molex 6838 Series
Molex 09-50-8041 with locking ramp
Molex 6838 Series
www.murata-ps.com/support
MVAD040.B01 Page 4 of 6
MVAD040 Series
40W 2" x 4" AC-DC Power Supply Converter
MECHANICAL DIMENSIONS – MVAD040-12 ONLY
All dimensions in inches (mm). tolerance is +/-0.02’ (0.5)
Mounting holes H1 and H2 should be earth-grounded for EMI purpose
Mounting holes H2 is earth ground connection
This power supply requires mounting on standoffs minimum 0.2' (5.0) in height
Dimensions: 2.0" x 4.0" x 1.3" (50.8mm x 101.6mm x 33.02mm)
INPUT/OUTPUT CONNECTOR AND SIGNAL SPECIFICATION AND MATING CONNECTORS
PIN
Description
Input Connector CN1 : Molex 26-62-4030
1
AC Line (V-)
3
AC Neutral (V+)
Spade Connector: #250
GND
Earth Ground
Output Connector CN2 : Molex 26-60-4040
1, 2
V1
3, 4
DC Return
Mating Housing
Crimp terminal/pins
Molex 09-50-8031 with locking ramp
Molex 6838 Series
Molex 09-50-8041 with locking ramp
Molex 6838 Series
www.murata-ps.com/support
MVAD040.B01 Page 5 of 6
MVAD040 Series
40W 2" x 4" AC-DC Power Supply Converter
MECHANICAL DIMENSIONS – MVAD040-xx 24V and 48V MODELS
All dimensions in inches (mm). tolerance is +/-0.02’ (0.5)
Mounting holes H1 and H2 should be earth-grounded for EMI purpose
Mounting holes H2 is earth ground connection
This power supply requires mounting on standoffs minimum 0.2' (5.0) in height
Dimensions: 2.0" x 4.0" x 1.3" (50.8mm x 101.6mm x 33.02mm)
INPUT/OUTPUT CONNECTOR AND SIGNAL SPECIFICATION AND MATING CONNECTORS
PIN
Description
Input Connector CN1 : Molex 26-62-4030
1
AC Line (V-)
3
AC Neutral (V+)
Spade Connector: #250
GND
Earth Ground
Output Connector CN2 : Molex 26-60-4040
1, 2
V1
3, 4
DC Return
Murata Power Solutions, Inc.
11 Cabot Boulevard, Mansfield, MA 02048-1151 U.S.A.
ISO 9001 and 14001 REGISTERED
Mating Housing
Crimp terminal/pins
Molex 09-50-8031 with locking ramp
Molex 6838 Series
Molex 09-50-8041 with locking ramp
Molex 6838 Series
This product is subject to the following operating requirements and the Life and Safety Critical Application Sales
Policy. Refer to: http://www.murata-ps.com/requirements/
Murata Power Solutions, Inc. (“Murata”) makes no representation that the use of its products in the circuits described herein, or the use of other technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do not imply the
granting of licenses to make, use, or sell equipment constructed in accordance therewith. Buyer represents and agrees that it has all the necessary expertise to create and implement safeguards that anticipate dangerous consequences of failures, monitor failures and their consequences, lessen
the likelihood of failures that might cause harm, and take appropriate remedial actions. Buyer will fully indemnify Murata, its affiliated companies, and its representatives against any damages arising out of the use of any Murata products in safety-critical applications. Specifications are subject
to change without notice.
© 2014 Murata Power Solutions, Inc.
www.murata-ps.com/support
MVAD040.B01 Page 6 of 6