APM-40 SERIES - MINMAX Technology

APM-40 SERIES
AC/DC Power Module 40W, Industrial & Medical Safety
FEATURES
►Fully Encapsulated Plastic Case for
PCB, Chassis and DIN-Rail Mounting Version
►Universal Input 85~264VAC, 47~440Hz
►Protection Class II as per IEC/EN 60536
►I/O Isolation 4000VAC with Reinforced Insulation
►Operating Temp. Range -40℃ to +80℃
►Overload/Voltage/Temp. and Short Circuit Protection
►EMI Emission meets EN55011/22 Class B & FCC Level B
►EMC Immunity meets EN61000-4-2,3,4,5,6,8,11
►UL/cUL/IEC/EN 60950-1 and UL508 Safety Approval
►Medical Safety meets 2xMOPP per 3rd Edition of IEC/EN
60601-1 & ANSI/AAMI ES60601-1
►CE Marking with EMC and LVD
PRODUCT OVERVIEW
The new MINMAX APM-40 series is a range of fully encapsulated AC/DC power modules. These high performance products feature an extended operating
temperature range of -40°C to +80°C. Universal input voltage 85-264VAC and UL/IEC/EN safety approvals including medical safety and UL508 listing
qualify these power supplies modules for applications in products with worldwide markets.EMI-filter meets EN55022, class B and FCC,part15, class B.
The APM-40 series power modules provide an economical solution for many space critical applications in commercial, medical and industrial electronic
equipment.
Model Selection Guide
Model
Number
Output
Voltage
Output Current
Input Current
115VAC, 60Hz
230VAC, 50Hz
Max.
@Max. Load
VDC
mA
mA(typ.)
APM-40S05
5
8000
716
APM-40S12
12
3330
APM-40S15
15
2660
APM-40S24
24
APM-40D12
APM-40D15
Max. capacitive
Load
Efficiency
(typ.)
@Max. Load, 115VAC
μF
%
429
8000
81
689
414
3900
84
680
408
3900
85
1660
687
413
680
84
±12
±1660
687
413
1500#
84
±15
±1330
680
408
1000#
85
# For each output
Input Specifications
Parameter
Model
Min.
Typ.
Max.
Unit
AC Voltage Input Range
85
---
264
VAC
Input Frequency Range
47
---
440
Hz
120
---
370
VDC
All Models
DC Voltage Input Range
No-Load Power Consumption
Inrush Current (Cold Start at 25℃)
E-mail:[email protected]
2015/05/22
REV:2
---
---
0.3
W
115VAC
---
---
30
A
230VAC
---
---
60
A
Tel:886-6-2923150
Page 1 of 5
APM-40 SERIES
AC/DC Power Module 40W, Industrial & Medical Safety
Output Specifications
Parameter
Conditions
Output Voltage Accuracy
Line Regulation
Min.
Typ.
--±2.0
Vin=Min. to Max. @Full Load
--±0.5
Single Output Model
--±1.0
Io=0% to 100%
Dual Output Models
--±2.0
No minimum Load Requirement
5V Output Models
1.5
--0-20 MHz Bandwidth
Other Output Models
1.0
--Zener diode clamp
120
----±0.02
----85VAC, Hiccup Mode, auto-recovery
105
--(long term overload condition may cause damage)
Hiccup mode, indefinite (Automatic Recovery)
Load Regulation
Minimum Load
Ripple & Noise(3)
Over Voltage Protection
Temperature Coefficient
Overshoot
Current Limitation
Short Circuit Protection
Max.
Unit
---------
%Vom.
%
%
%
1.8
1.3
----5
%VPP of Vo
%VPP of Vo
% of Vo
%/℃
%
---
% Inom.
General Specifications
Parameter
I/O Isolation Voltage
Leakage Current
I/O Isolation Resistance
Switching Frequency
Conditions
Min.
Typ.
Max.
Unit
Reinforced Insulation, Rated For 60 Seconds
4000
--1000
-------
--80
--130
25
80
200,000
-------------
VACrms
μA
MΩ
KHz
ms
ms
Hours
500 VDC
115VAC, 60Hz
230VAC, 50Hz
MIL-HDBK-217F@25℃, Ground Benign
Hold-up Time
MTBF (calculated)
Protection Class II
According IEC/EN 60536
IEC/EN 60950-1 CB Report, UL/cUL 60950-1, CSA-C22.2 No.60950-1, UL508 listed certificate
IEC/EN 60601-1 3rd Edition CB Report, ANSI/AAMI ES60601-1 2XMOPP, CAN/CSA-C22.2 No.60601-1 certificate
Safety Approvals
EMC Specifications
Parameter
Standards & Level
Performance
Conduction
EN55011, EN55022, EN61000-6-4, EN61000-6-3, FCC part 15
Radiation
EN60601-1-2, EN55024, EN61000-6-2, EN61000-6-1
ESD
EN61000-4-2 Air ± 8kV , Contact ± 4kV
Radiated immunity
EN61000-4-3 10V/m
Fast transient
EN61000-4-4 ±2kV
Surge
EN61000-4-5 ±1kV
EN61000-4-6 10Vrms
Conducted immunity
EN61000-4-8 30A/m
PFMF
EN61000-4-11 30% 10ms
Dips
EN61000-4-11 >95% 5000ms
Interruptions
EMI
EMS
Class B
A
A
A
A
A
A
A
B
Environmental Specifications
Parameter
Conditions
Min.
Max.
Temperature Range (operational)
Power Derating
Storage Temperature Range
Over Temperature Protection
Humidity (non condensing)
Cooling
Lead Temperature (1.5mm from case for
10Sec.)
Ambient
Above +60℃
-40℃
+80℃
1.5W / ℃
+95℃
E-mail:[email protected]
2015/05/22
REV:2
-40℃
Shutdown at 90℃ (automatic recovery at approx. 67℃)
--Natural Convection
---
Tel:886-6-2923150
Page 2 of 5
95% rel. H
260℃
APM-40 SERIES
AC/DC Power Module 40W, Industrial & Medical Safety
Notes
1
This product is not designed for use in critical life support systems, equipment used in hazardous environment, nuclear control systems or other
such applications which necessitate specific safety and regulatory standards other the ones listed in this datasheet.
Specifications typical at Ta=+25℃, resistive load, 115VAC, 60Hz input voltage, after warm-up time rated output current unless otherwise noted.
Ripple & Noise measured with a 0.1μF/50V MLCC and a 1μF/50V Aluminum electrolytic.
Safety approvals cover frequency 47-63 Hz.
We recommend to protect the converter by a slow blow fuse in the input supply line.
Other input and output voltage may be available, please contact factory.
That “natural convection” is about 20LFM but is not equal to still air (0 LFM).
Specifications are subject to change without notice.
2
3
4
5
6
7
8
Package Specifications PCB Mounting
Mechanical Dimensions
Pin Connections
12.7
[0.50]
6
4
0.7
[0.03]
3
Pin
Single Output
Dual Output
1
AC (N)
AC (N)
2
AC (L)
AC (L)
3
+Vout
+Vout
4
No Pin
No Pin
5
-Vout
Common
6
No Pin
No Pin
7
NC
-Vout
[
7
5
6.0
[0.24]
15.24
[0.60]
12.7
[0.50]
1.0
0.04]
15.24
[0.60]
30.0
[1.18]
15.9 [0.63]
88.9 [3.50]
81.3 [3.20]
31.6 [1.24]
NC: No Connection
53.3 [2.10]
Mounting M4.0 Thread
Bottom View
2
1
5.0
[0.20]
►All dimensions in mm
55.88 [2.20]
63.5 [2.50]
Physical Characteristics
Case Size
:
88.9x63.5x30.0mm (3.50x2.50x1.18 inches)
Case Material
:
Plastic resin (flammability to UL 94V-0 rated)
Pin Material
:
Copper Alloy with Gold Plate Over Nickel Subplate
Weight
:
310g
E-mail:[email protected]
2015/05/22
REV:2
Tel:886-6-2923150
Page 3 of 5
►Tolerance:
►Pin
(inches)
±0.5 (±0.02)
diameter  1.0 ±0.1 (0.04±0.004)
APM-40 SERIES
AC/DC Power Module 40W, Industrial & Medical Safety
Package Specifications Chassis Mounting (order code suffix C)
Mechanical Dimensions
Connections
Indication LED
2
Top view
1
63.8 [2.51]
7
6
5
4
3
50.0 [1.97]
4 x 3.5
DCON
POWER "GOOD" INDICATOR
Pin
Single Output
Dual Output
1
AC (N)
AC (N)
2
AC (L)
AC (L)
3
+Vout
+Vout
4
NC
NC
5
-Vout
Common
6
NC
NC
7
NC
-Vout
100.0 [3.94]
112.0 [4.41]
NC: No Connection
92.0 [3.62]
16.8 [0.66]
5.0 [0.20]
34.1 [1.34]
10.0 [0.39]
Physical Characteristics
Case Size
:
112.0x63.8x34.1mm (4.41x2.51x1.34 inches)
Case Material
:
Plastic resin (flammability to UL 94V-0 rated)
Weight
:
320g
Package Specifications with DIN Rail Mounting Bracket
Mechanical Dimensions
7
6
5
4
3
Indication LED
Top view
2
1
63.8 [2.51]
3.5
50.0 [1.97]
4x
DCON
POWER "GOOD" INDICATOR
100.0 [3.94]
112.0 [4.41]
34.1 [1.34]
11.0 [0.43]
3.0 [0.12]
5.0
[0.20]
10.0 [0.39]
16.8 [0.66]
92.0 [3.62]
Physical Characteristics
Case Size
:
112.0x63.8x34.1mm (4.41x2.51x1.34 inches)
Case Material
:
Plastic resin (flammability to UL 94V-0 rated)
Weight
:
374g
E-mail:[email protected]
2015/05/22
REV:2
Tel:886-6-2923150
Page 4 of 5
►All dimensions in mm
►Tolerance:
(inches)
±0.5 (±0.02)
APM-40 SERIES
AC/DC Power Module 40W, Industrial & Medical Safety
DIN-Rail Mounting Bracket (Order code for Kit : AC-DIN-02)
Order Code Table
PCB Mounting
APM-40S05
Chassis Mounting
APM-40S05C
With DIN Rail Mounting by two Order Code
APM-40S05C
AC-DIN-02
APM-40S12
APM-40S12C
APM-40S12C
AC-DIN-02
APM-40S15
APM-40S15C
APM-40S15C
AC-DIN-02
APM-40S24
APM-40S24C
APM-40S24C
AC-DIN-02
APM-40D12
APM-40D12C
APM-40D12C
AC-DIN-02
APM-40D15
APM-40D15C
APM-40D15C
AC-DIN-02
APM-40S05
APM-40S05C
APM-40S05C
AC-DIN-02
Minmax Technology Co., Ltd.
18, Sin Sin Road, An-Ping Industrial District, Tainan 702, Taiwan
Tel: 886-6-2923150 Fax: 886-6-2923149 E-mail: [email protected]
2015/05/22
REV:2
Page 5 of 5