AYM-60 SERIES AC/DC Power Module 60W, Industrial & Medical Safety FEATURES ►Fully Encapsulated Plastic Case for PCB, Chassis and DIN-Rail Mounting Version ►Universal Input 85~264VAC, 47~440Hz ►Protection Class II as per IEC/EN 60536 ►I/O Isolation 4000VAC with Reinforced Insulation ►Operating Ambient Temp. Range -40℃ to +80℃ ►Overload/Voltage and Short Circuit Protection ►Designed-in EMI Emission meets EN55011/22 Class B & FCC Level B ►Designed-in EMC Immunity meets EN61000-4-2,3,4,5,6,8,11 ►Medical EMC Standard meets EMI EN55011 & EMS EN60601-1-2 ►Medical Safety meets 2xMOPP per 3rd Edition of IEC/EN 60601-1 & ANSI/AAMI ES60601-1 ►UL508 Safety Approval Specifically for Industrial Application ►UL/cUL/IEC/EN 60950-1 Safety Approval & CE Marking PRODUCT OVERVIEW The new MINMAX AYM-60 series is a range of fully encapsulated AC/DC power modules. These high performance products feature an extended operating temperature range of -40°C to +80°C. Universal input voltage 85-264VAC and UL/IEC/EN safety approvals including medical safety and UL508 listing qualify these power supplies modules for applications in products with worldwide markets.EMI-filter meets EN55022, class B and FCC,part15, class B. The AYM-60 series power modules provide an economical solution for many space critical applications in commercial, medical and industrial electronic equipment. Model Selection Guide Model Number Output Voltage Output Current Input Current 115VAC, 60Hz 230VAC, 50Hz Max. @Max. Load VDC mA mA(typ.) AYM-60S051 5.1 10000 880 AYM-60S12 12 5000 AYM-60S15 15 AYM-60S24 24 AYM-60S48 48 Max. capacitive Load Efficiency (typ.) @Max. Load, 115VAC μF % 528 8000 84 1000 600 3900 87 4000 1000 600 3300 87 2500 1000 600 1500 87 1250 988 593 680 88 Input Specifications Parameter Model AC Voltage Input Range Input Frequency Range All Models DC Voltage Input Range No-Load Power Consumption Inrush Current (Cold Start at 25℃) E-mail:[email protected] 2015/12/28 REV:5 Typ. Max. Unit 85 --- 264 VAC 47 --- 440 Hz 120 --- 370 VDC --- --- 0.5 W 115VAC --- --- 30 A 230VAC --- --- 60 A Tel:886-6-2923150 Page 1 of 5 Min. AYM-60 SERIES AC/DC Power Module 60W, Industrial & Medical Safety Output Specifications Parameter Conditions / Model Output Voltage Setting Accuracy Line Regulation Load Regulation Minimum Load Min. ------No minimum Load Requirement 5.1VDC Output Models --0-20 MHz Bandwidth Other Output Models --Zener diode clamp ------85VAC, Hiccup Mode, auto-recovery 105 (long term overload condition may cause damage) Hiccup mode, Automatic Recovery Vin=Min. to Max. @Full Load Io=0% to 100% Ripple & Noise(3) Over Voltage Protection Temperature Coefficient Overshoot Current Limitation Short Circuit Protection Typ. Max. Unit ±1.0 ±0.2 ±0.5 ±2.0 ±1.0 ±1.0 %Vnom. % % 2.0 1.0 120 ±0.02 --- 3.0 1.5 ----5 %VPP of Vo %VPP of Vo % of Vo %/℃ % --- --- %Inom. General Specifications Parameter I/O Isolation Voltage Leakage Current I/O Isolation Resistance Switching Frequency Conditions Min. Typ. Max. Unit Reinforced Insulation, Rated For 60 Seconds 4000 --1000 ------- --80 --65 20 80 125,000 ------------- VACrms μA MΩ KHz ms ms Hours 500 VDC 115VAC, 60Hz 230VAC, 50Hz MIL-HDBK-217F@25℃, Ground Benign Hold-up Time MTBF (calculated) Protection Class II According IEC/EN 60536 UL/cUL 60950-1, CSA C22.2 No 60950-1 ANSI/AAMI ES60601-1, CAN/CSA-C22.2 No. 60601-1 IEC/EN 60950-1, IEC/EN 60601-1 3rd Edition 2xMOPP UL508, CSA C22.2 No.107.1-01 UL/cUL 60950-1 recognition (UL certificate), IEC/EN 60950-1 (CB-report), UL/cUL 508 listed certificate ANSI/AAMI ES60601-1 2xMOPP recognition (UL certificate), IEC/EN 60601-1 3rd Edition (CB-report) Safety Standards Safety Approvals EMC Specifications Parameter Standards & Level EMI Conduction and Radiation Performance EN55011, EN55022, EN61000-6-4, EN61000-6-3, FCC part 15 EN60601-1-2, EN55024, EN61000-6-2, EN61000-6-1 ESD EN61000-4-2 Air ± 8kV , Contact ± 4kV Radiated immunity EN61000-4-3 10V/m Fast transient EN61000-4-4 ±2kV Surge EN61000-4-5 ±1kV EN61000-4-6 10Vrms Conducted immunity EN61000-4-8 30A/m PFMF EN61000-4-11 30% 10ms Dips EN61000-4-11 >95% 5000ms Interruptions EMS Class B A A A A A A A B Environmental Specifications Parameter Operating Ambient Temperature Range (See Power Derating Curve) Storage Temperature Range Humidity (non condensing) Power Derating Cooling Lead Temperature (1.5mm from case for 10Sec.) E-mail:[email protected] 2015/12/28 REV:5 Conditions Min. Max. Unit Natural Convection -40 +80 ℃ -40 --- +95 95 ℃ % rel. H W/℃ 260 ℃ Above +60℃ 2.3 Natural Convection --- Tel:886-6-2923150 Page 2 of 5 AYM-60 SERIES AC/DC Power Module 60W, Industrial & Medical Safety Notes 1 2 3 4 5 6 7 8 This product is not designed for use in critical life support systems, equipment used in hazardous environment, nuclear control systems or other such applications which necessitate specific safety and regulatory standards other the ones listed in this datasheet. Specifications typical at Ta=+25℃, resistive load, 115VAC, 60Hz input voltage, after warm-up time rated output current unless otherwise noted. Ripple & Noise of PCB mounting type measured with a 0.1μF/50V MLCC and a 1μF/50V Aluminum electrolytic. Safety approvals cover frequency 47-63 Hz. We recommend to protect the converter by a slow blow fuse in the input supply line. Other input and output voltage may be available, please contact factory. That “natural convection” is about 20LFM but is not equal to still air (0 LFM). Specifications are subject to change without notice. Package Specifications PCB Mounting Mechanical Dimensions Pin Connections 25.4 [1.00] 6 1.0 [ 0.04] 4 Pin Function 1 AC (N) 2 AC (L) 4 +Vout 6 -Vout 88.9 [3.50] 17.00 [0.67] Bottom View 81.3 [3.20] Mounting M4 Thread 36.45 [1.44] 17.75 [0.70] 1 2 ►All dimensions in mm 55.88 [2.20] 0.7 [0.03] 67.5 [2.66] 6.0 [0.24] Physical Characteristics Case Size : 88.9x67.5x34.2mm (3.50x2.66x1.35 inches) Case Material : Plastic resin (flammability to UL 94V-0 rated) Pin Material : Copper Alloy with Gold Plate Over Nickel Subplate Weight : 360g E-mail:[email protected] 2015/12/28 REV:5 Tel:886-6-2923150 Page 3 of 5 34.2 [1.35] ►Tolerance: ►Pin (inches) ±1.0 (±0.04) diameter 1.0 ±0.1 (0.04±0.004) AYM-60 SERIES AC/DC Power Module 60W, Industrial & Medical Safety Package Specifications Chassis Mounting (order code suffix C) Mechanical Dimensions Connections 4x 3.5 2 5 Top View 1 4 Indication LED 67.8 [2.67] 6 50.0 [1.97] 7 3 DCON POWER"GOOD"INDICATOR Pin Function 1 AC (N) 2 AC (L) 3 NC 4 +Vout 5 NC 6 -Vout 7 NC 100.0 [3.94] NC: No Connection 112.0 [4.41] Physical Characteristics Case Size : 112.0x67.8x38.0mm (4.41x2.67x1.50 inches) Case Material : Plastic resin (flammability to UL 94V-0 rated) Weight : 380g Package Specifications with DIN Rail Mounting Bracket Mechanical Dimensions 4x 3.5 Top View 4 1 67.8 [2.67] 2 5 50.0 [1.97] 7 6 3 Indication LED DCON POWER"GOOD"INDICATOR 100.0 [3.94] 112.0 [4.41] Physical Characteristics Case Size : 112.0x67.8x38.0mm (4.41x2.67x1.50 inches) Case Material : Plastic resin (flammability to UL 94V-0 rated) Weight : 433g E-mail:[email protected] 2015/12/28 REV:5 Tel:886-6-2923150 Page 4 of 5 38.0 [1.50] 11.0 [0.43] 3.0 [0.12] 5.0[0.20] 11.0 [0.43] 16.8 [0.66] 90.0 [3.54] 38.0 [1.50] 5.0[0.20] 11.0 [0.43] 16.8 [0.66] 90.0 [3.54] ►All dimensions in mm ►Tolerance: (inches) ±1.0 (±0.04) AYM-60 SERIES AC/DC Power Module 60W, Industrial & Medical Safety DIN-Rail Mounting Bracket (Order Code for Kit : AC-DIN-02) Order Code Table PCB Mounting AYM-60S051 Chassis Mounting AYM-60S051C With DIN Rail Mounting by two Order Code AYM-60S051C AC-DIN-02 AYM-60S12 AYM-60S12C AYM-60S12C AC-DIN-02 AYM-60S15 AYM-60S15C AYM-60S15C AC-DIN-02 AYM-60S24 AYM-60S24C AYM-60S24C AC-DIN-02 AYM-60S48 AYM-60S48C AYM-60S48C AC-DIN-02 Minmax Technology Co., Ltd. 18, Sin Sin Road, An-Ping Industrial District, Tainan 702, Taiwan Tel: 886-6-2923150 Fax: 886-6-2923149 E-mail: [email protected] 2015/12/28 REV:5 Page 5 of 5