LINEAR TROUBLESHOOTING GUIDE AN-109

Condor Application Note 5/00
LINEAR TROUBLESHOOTING GUIDE
AN-109
WARNING! RISK OF FIRE & SAFETY!
Repair must be performed by a Condor authorized personnel
No Output:
• Visually inspect the supply for open fuses, burnt or discolored parts vented capacitors
and loose wiring.
• Verify AC and DC fuses are not open.
• Verify AC voltage is reaching the input of the transformer.
• OHM output diodes and transistors to see if they are shorted.
• Check for solder fractures or traces of arcing on circuit side of PCB.
Low Output:
• Visually inspect for open fuses, loose wiring, burnt or discolored parts and vented
capacitors.
• Use sense wires to compensate for up to 0.25 volts of drop in the DC load cables.
• Monitor the output voltage and readjust the voltage POT if necessary.
• Check the current limit POT and verify the seal has not been broken, if so readjust it.
• With a meter, check the output diodes and transistors to see if they are shorted.
Poorly Regulated Output:
• Visually inspect for poorly soldered or loose output wiring.
• Verify pass transistors screws are properly not loose.
High Ripple:
• Visually inspect for poorly soldered or loose output wiring.
• Inspect for dried out capacitors or vented output capacitors.
Output Oscillates:
• Visually inspect for burnt or discolored parts, vented capacitors and shorted
components.
Adjustment of output voltage pot:
• To raise the output voltage, monitor the output and turn the voltage POT clockwise.
Environmental Specifications:
• Maximum ambient temperature for continuous output is 50°C.
• For operation above 50°C., see Operation Temperature Limits chart below.
• See installation instructions for models that require fan cooling.
• Operating temp: 0-50°C. full load, for 70 degrees C., de-rate to 40%.
• Non-Operating temp: -40 to +85 °C.
• Operating altitude: -500 to 10,000 feet.
Condor D.C. Power Supplies, Inc., 2311 Statham Parkway, Oxnard, CA 93033
800-235-5929 • Tel: 805-486-4565 • Fax: 805-487-8911• www.condorpower.com
Condor Application Note 5/00
•
•
Non-Operating altitude: -500 to 40,000 feet.
Maximum Relative Humidity 96%, non- condensing.
Linear Enclosures:
• Condor doesn’t provide off the shelf enclosures for the Linear line. An enclosure may
be used, but may require airflow and or de-rating of the output current. Verify the
heat sink temperature does not exceed 90°C. for any length of time.
Over Voltage Protection:
• OV-12 & OV-24 is user adjustable from 6.2 to 33 volts. A single OV module is
required for both single and dual output power supplies.
• For specific instructions see application data sheet #11327.
• OV-12 protects up to a maximum continuous current of 8A and protects up to 12
amps intermittent and is used on the 12V to 28V & +/- 12 & 15V models.
• OV-24: protects up to a maximum continuous current of 20A and protects up to
• Protects up to 24 amps and is used on the E & F Cases.
AC HOOK UP CHART
100 VAC
1
1
1
2
2
2
3
120 VAC
5
4
3
215 VAC
5
4
3
1
230-240
VAC
5
4
2
3
5
4
AC HOOK UP EXAMPLE:
For 120 VAC operation, connect AC Line to transformer pin 1, Neutral to
transformer pin 4,
and put a jumper wire from pin 1 to 3 and a separate jumper wire from pin 2 to 4.
OPERATING TEMPERATURE LIMITS
100
80
% OF
FULL LOAD 60
40
20
S1
0
0
10
20
30
40
50
60
70
TEMPERATURE, DEGREES C.