CABLE REQUIREMENT: Terminates most 22-26 AWG solid

GIGA-PUNCH ™
Punchdown System
PNS153F
© Panduit Corp. 2002
INSTALLATION INSTRUCTIONS
CABLE REQUIREMENT: Terminates most 22-26 AWG solid or stranded
IWC wire with a .050” (1.27mm) max. o.d., either PVC or Plenum rated.
Printed in Singapore
LOCATION
Mounting a system at the right height will make wiring changes and additions cost efficient. The optimum height, from the
floor to the top of a 72 port/432 pair GIGA-PUNCH ™ base, is 68 inches. If the customer needs don’t exceed the wiring
capacity of one base of 24 port/144 pair, the optimum distance from the floor to the top of the system can be reduced to 43
inches. This height will allow for expansion of 72 port/144 pair on top and 72 port/432 pair underneath.
WALL MOUNT BASES WITH LEGS
72 PORT / 432 PAIR BASE
24 PORT / 144 PAIR BASE
DISTANCE FROM FLOOR
TO TOP OF BASE: 68”
DISTANCE FROM FLOOR
TO TOP OF BASE: 43”
19" RACK MOUNT PANELS
48 PORT BASE WITH
JUMPER TROUGHS
DISTANCE FROM FLOOR
TO TOP OF BASE: 43”
48 PORT BASE
DISTANCE FROM FLOOR
TO TOP OF BASE: 43”
INSTALLATION
Fig. 1
1. Use appropriate mounting hardware to install base
on desired surface as shown in Fig. 1, 3/4” plywood is recommended. (Tip: PANDUIT lettering
should be upright.)
2. Route cables through the slots in the base as
shown in Fig. 2.
3. Cable jacket end should be within 1/2” from where
cable pairs are inserted. Cable pairs must remain
twisted up to the point of connection for Category 6
installation.
Note: When using 4-pair cable, high density
bases must be wired from the center out to
each side, as shown in Fig. 3a.
Fig. 2
CATEGORY 6 DATA WIRING SCHEME
Fig. 3b
WHITE/BLUE
WHITE/GREEN
WHITE/ORANGE
WHITE/BROWN
Fig. 3a
BLUE
FOR TECHNICAL SUPPORT CALL: 866-405-6654
Page 1 of 2
ORANGE GREEN BROWN
PNS153F
INSTALLATION INSTRUCTIONS
CABLE REQUIREMENT: Terminates most 22-26 AWG solid or stranded
IWC wire with a .050” (1.27mm) max. o.d., either PVC or Plenum rated.
4. Inspect cable pair color placement prior to using
either a GPST single wire punchdown tool or
GPDTM multi-pair punchdown tool to seat and cut
the pairs to length.
Note: When using a single wire punchdown
tool to insert and cut wires, the HIGH impact
setting should be used.
Fig. 4
5. Position the connecting block over the wired base.
6. Secure the connecting block in place using the
GPDTM multi-pair punchdown tool. It is important
to keep the tool perpendicular to the base to
ensure a good termination.
Fig. 5
7. Once the connecting blocks have been seated,
cross-connect wires can be terminated to the top
of the connecting blocks or GIGA-PUNCH ™ patch
cords can be installed. If cross-connecting,
reference Fig. 3b.
Note: Optional retaining cap can be installed at
this time.
Fig. 6
8. Add cable identification to the label, fold label, and
slide it into the label holder. The label and label
holder snap into position on the base in-between
rows of connecting blocks as shown in Fig. 6.
P110LH
GPRC4-X LABEL HOLDER
RETAINING
CAP
(Optional)
GPCB4
CONNECTING BLOCK
GPB24 BASE
Pair
Tip Color
Ring Color
1
White/Blue
Blue
2
White/Orange
Orange
3
White/Green
Green
4
White/Brown
Brown
INSTALLATION TIPS:
1. GIGA-PUNCH ™ product terminates most 22-26 AWG solid or stranded IWC wire with a .050” (1.27mm) max. o.d., either PVC or Plenum rated.
2. Never install wire into a slot previously used for a larger gauge.
3. Be careful to strip back cable jacket only as required for termination.
4. Use care to maintain pair twists up to the termination strip.
5. When stripping cable jacket, be careful not to cut the insulation on the individual wires.
6. Avoid sharp bends when routing cable.
As with all Wiring Accessories, the following statements apply:
1. Never install communications wiring during a lightning storm.
2. Never install communications wiring in wet locations unless the product is specifically designed for use in wet locations.
3. Never touch uninsulated communications wiring or terminals unless the communication line has been disconnected at the network interface.
4. Use caution when installing or modifying communication wiring.