SynQor UPS Terminal Commands Rev D, 14 April 2014 The UPS external serial port uses 115.2kbaud, 8 data bits, no parity, and one stop bit. Commands can be sent, and output viewed, with any standard terminal emulator. To view user text, set the terminal emulator for local echo. All transmitted commands must be terminated with a line feed character (ASCII 10). The interface is not case sensitive. The UPS will transmit a prompt "SynQor>" to the terminal after each command. To execute a command, simply transmit the required ASCII text, terminated by a line feed character. Note that only the first 8 characters for any command are required to recognize and launch the command. Command Summary Command Description ? Display list of available terminal commands. ALARM DISABLE Disable audible alarm output. (Updates non-volatile memory.) ALARM ENABLE Enable audible alarm output. (Updates non-volatile memory.) ALARM SILENCE Silence currently active audible alarms. ANALOG IN? Display control board analog signal levels. ASTART DISABLE Disable auto-start mode (default factory setting). ASTART ENABLE Enable auto-start mode. BATT INFO Display manufacturer data and code revisions for installed battery pack. BATTERY? Display internal measurements and status for installed battery pack. CODE? Output code revision information for internal components. DEBUG OFF Disable automatic output of source data on startup (default factory setting). DEBUG ON Enable output of "SOURCE LOG" output on initial power application. DIGITAL IN? Display state of internal digital inputs of UPS control board. DIS AC1 Set AC Output inactive. DIS DC1 Set DC1 Output inactive. DIS DC2 Set DC2 Output inactive EMAIL RESTORE Restore Email alert notifications to factory default settings. ENA AC1 Set AC Output active. ENA DC1 Set DC1 Output active. ENA DC2 Set DC2 Output active. FAN SERVICE Execute fan service sequence immediately (cycles through fan speed settings). FAN SET x Manually set fan speed, x=0 to 4. FAN STATUS? Display inputs to fan controller. 065-0000020 Rev D Page 1 of 18 SynQor UPS Terminal Commands Command Description FAND DISABLE Disable execution of fan diagnostics every 24 hours. FAND ENABLE Enable execution of fan diagnositcs every 24 hours (default factory setting). FANS? Display fan speeds and input voltage. FOUT 400 Set AC Output frequency to 400 Hz. FOUT 50 Set AC Output frequency to 50 Hz. FOUT 60 Set AC Output frequency to 60 Hz. INPUTS? Display status of inputs to UPS system. NET RESTORE Restore network configuration settings to factory defaults. NETWORK? Display Ethernet IP address and MAC address. OUTPUT DISABLE Shutdown AC and DC outputs of UPS system, reverting to standby or off state. OUTPUT ENABLE Enable AC and DC outputs of UPS system. OUTPUTS? Display status of outputs from UPS system. RESTART x Shutdown output immediately, re-enable output after x seconds. RUNTEST x Run internal built-in test routine. SHUTDOWN x Shutdown output after x seconds. SNMP RESTORE Restore SNMP configuration to factory defaults. SOURCE LOG Begin real-time output of power source status and switchover events. SOURCES? Display status of each defined source for the UPS system (AC, DC, and battery). STARTUP x Enable outputs after x seconds. TEMPS? Display reported temperatures for internal subsystems. Command Details Command: ? Description: Display list of available terminal commands. Sample Output: SynQor>? ? ALARM DISABLE ALARM ENABLE ALARM SILENCE ׃ SynQor> Discussion: Output response format is a single row for each command available to the user. 065-0000020 Rev D Page 2 of 18 SynQor UPS Terminal Commands Command: ALARM DISABLE Description: Disable audible alarm output. (Updates non-volatile memory.) Sample Output: SynQor>ALARM DISABLE Flash Updated. SynQor> Discussion: This command will prevent the audible beeper from ever activating for any condition. Setting will be saved in non-volatile memory, and will persist until reversed with the "ALARM ENABLE" command. Command: ALARM ENABLE Description: Enable audible alarm output. (Updates non-volatile memory.) Sample Output: SynQor>ALARM ENABLE Flash Updated. SynQor> Discussion: This command will allow the audible beeper to sound during alarm conditions. This is the default factory state. See User Guide, "Fault Conditions" section for a description of audible alarms. The setting will be saved in non-volatile memory, and will persist until reversed with the "ALARM DISABLE" command. Command: ALARM SILENCE Description: Silence currently active audible alarms. Sample Output: SynQor>ALARM SILENCE Alarms Silenced. SynQor> Discussion: When there are current active alarms, issuing this command will silence the beeper. New alarm states that occur after the silence command will re-activate the audible beeper. This command is equivalent to holding up the front panel switch during operation. The beeper generates a brief two-toned signal when the silence command is issued. 065-0000020 Rev D Page 3 of 18 SynQor UPS Terminal Commands Command: ANALOG IN? Description: Display control board analog signal levels. Sample Output: SynQor>ANALOG IN? 5V Supply = 5.16 V External DC Input = 0.5 V Cold-start Voltage = 29.2 V Main Bus Voltage = 29.4 V Fan Current = &H0000 Fan Voltage = 0.0 V Battery Voltage = 0.5 V Motherboard Temperature = 24 C Charger Current = &H01F7 DC Out Readback = 0.11 V SynQor> Discussion: Command displays translated values from ADC measurements on UPS control board. No user action based on these outputs should taken. Note that Fan Current and Charger Current are not directly translateable to actual current readings. The DC Out Readback represents the output of a current amplifier; it does not represent the DC output voltage. An analog representation of the DC output voltage is not available. Command: ASTART DISABLE Description: Disable auto-start mode (default factory setting). Sample Output: SynQor>ASTART DISABLE Flash Updated. SynQor> Discussion: Command disables auto-start mode. This is the default factory configuration. With auto-start disabled, when the UPS receives AC or DC input power, it will enter standby mode. In standby mode, the battery will charge and the terminal interface is active, but the output will not enable until the user takes action to enable the output, either through a terminal command, the front panel switch, or a rear panel I/O signal. Command: ASTART ENABLE Description: Enable auto-start mode. Sample Output: SynQor>ASTART ENABLE Flash Updated. SynQor> Discussion: Command enables auto-start mode. In auto-start mode, when the UPS first receives AC or DC input power from an off state, it will automatically enable the AC and DC outputs after a brief delay. This is not the default factory setting. Once the autostart mode is set, it will persist until disabled with the "ASTART DISABLE" command. Note that autostart will only enable the output from a powered down state; if the output disables due to a fault or user action, but input power is still present, the output will not automatically re-enable. 065-0000020 Rev D Page 4 of 18 SynQor UPS Terminal Commands Command: BATT INFO Description: Display manufacturer data and code revisions for installed battery pack. Sample Output: SynQor>BATT INFO Manufacturer: SynQor, Inc. Device Type: 8SnP UPS Battery Chemistry: LiPo Serial Number: 1 Manufacture Date: 2009/9/1 Num ID Code Rev 0 &HFFFF 43, 32 1 &H6666 32, 17 2 &H3333 32, 17 3 &H1111 32, 17 4 &H7777 32, 17 5 &H4444 32, 17 6 &H5555 32, 17 7 &H2222 32, 17 SynQor> Discussion: Command displays data and code revisions read from an installed battery pack. No user action based on these outputs should be taken. The code revision data gives one row (Row 0) for the front panel board, and then an additional row for each detected battery string. Command: BATTERY? Description: Display internal measurements and status for installed battery pack. Sample Output: SynQor>BATTERY? Num Strings = 7 Voltage = 33342 mV Current = 480 mA SBS Status = &H4000 Battery Temperature = 24.8 C Temp Severity = 2 Requested Chg V = 33200 mV Requested Chg I = 250 mA Charge vs. Full = 99 % Charge vs. Designed = 99 % Battery Flags = 0x0000 Comm Fault = &H0000 Min to Empty = >65535 min Min to Full = 12 min Min at Present Power = 366 min Charge Cycles = 11 SynQor> 065-0000020 Rev D Page 5 of 18 SynQor UPS Terminal Commands Discussion: Displays summary of telemetry data from installed battery pack. All measurements are as reported or estimated by the internal battery monitoring circuitry. Notes on data values: Current values are positive for charging current, negative for discharge currents. SBS Status is compliant with the SBS Standard. Temp Severity: 0 = Too cold to discharge, 1 = Too cold to charge, 2 = Normal, 3 = Too hot to charge, 4 = unused, 5 = Too hot to discharge "vs. Full" is measured relative to the current charge capacity of available strings in the battery pack; "vs. Designed" is relative to the designed capacity of the battery pack. The "Min to Empty" and "Min to Full" parameters are based on the current charge or discharge current and estimated pack capacity. The "Min at Present Power" shows the predicted runtime based on the present delivered power and battery capacity if the AC and DC inputs failed. [Note that for Communication Board code Revs prior to 2.0, there were minor differences in the BATTERY? query output.] Command: CODE? Description: Output code revision information for internal components. Sample Output: SynQor>CODE? AC/DC Rev 1 = &H0072 AC/DC Rev 2 = &H006A DC/AC Rev = &H0071 Control Rev = 78, 62 Comm Code Rev = 2, 0 SynQor> Discussion: Outputs reported code revision of internal modules. Note that modules which are not active will not report a valid value. For example, with no AC power applied, the AC/DC revisions will not be valid. If the AC output is not active, the DC/AC revision will not be valid. Command: DEBUG OFF Description: Disable automatic output of source data on startup (default factory setting). Sample Output: SynQor>DEBUG OFF Flash Updated. SynQor> Discussion: Disables automatic output of "SOURCE LOG" command after intial power application. This is the default factory setting. This command will reverse the action of the "DEBUG ON" command. 065-0000020 Rev D Page 6 of 18 SynQor UPS Terminal Commands Command: DEBUG ON Description: Enable output of "SOURCE LOG" output on initial power application. Sample Output: SynQor>DEBUG ON Flash Updated. SynQor> Discussion: Enables automatic output of "SOURCE LOG" command after intial power application for debugging purposes. Issuing the "DEBUG OFF" command will revert to standard operation. Command: DIGITAL IN? Description: Display state of internal digital inputs of UPS control board. Sample Output: SynQor>DIGITAL IN? DC Out 0 Fault = High DC Out 1 Fault = Low AC input Alarm = Low External Input Alarm = High Front Switch UP = Low Remote Start = Low Front Switch DOWN = Low SynQor> Discussion: Command displays translated values from digital inputs UPS control board. No user action based on these outputs should taken. Note that the presence of DC Out 0 & DC Out 1 inputs does not imply that DC outputs are or are not available on a given system. Command: DIS AC1 Description: Set AC Output inactive. Sample Output: SynQor>DIS AC1 Flash Updated. SynQor> Discussion: Command sets the AC Output to remain disabled and not follow the enable state of the UPS output. This is a non-volatile setting. Once set, the AC Output will remain disabled until the "ENA AC1" command is transmitted. [Command available for Communication Board Code Rev 2.0 and later.] 065-0000020 Rev D Page 7 of 18 SynQor UPS Terminal Commands Command: DIS DC1 Description: Set DC1 Output inactive. Sample Output: SynQor>DIS DC1 Flash Updated. SynQor> Discussion: Command sets the DC1 Output to remain disabled and not follow the enable state of the UPS output. This is a non-volatile setting. Once set, the DC1 Output will remain disabled until the "ENA DC1" command is transmitted. [Command available for Communication Board Code Rev 2.0 and later. This command is only available if the DC1 Output Option is installed.] Command: DIS DC2 Description: Set DC2 Output inactive Sample Output: SynQor>DIS DC2 Flash Updated. SynQor> Discussion: Command sets the DC2 Output to remain disabled and not follow the enable state of the UPS output. This is a non-volatile setting. Once set, the AC Output will remain disabled until the "ENA DC2" command is transmitted. [Command available for Communication Board Code Rev 2.0 and later. This command is only available if the DC2 Output Option is installed.] Command: EMAIL RESTORE Description: Restore Email alert notifications to factory default settings. Sample Output: SynQor>EMAIL RESTORE Factory Email Defaults Restored. SynQor> Discussion: Command restores settings for Email alerts to factory defaults (no alerts transmitted). [This command is only available with the Ethernet Option installed.] Command: ENA AC1 Description: Set AC Output active. Sample Output: SynQor>ENA AC1 Flash Updated. SynQor> Discussion: Command sets the AC Output to activate with the enable state of the UPS output. This is a nonvolatile setting. Sending this command will not immediately activate the AC Output unless the UPS Output is already enabled with the front panel switch or "OUTPUT ENABLE" command. [This command is only available for Communication Board Code Rev 2.0 and later.] 065-0000020 Rev D Page 8 of 18 SynQor UPS Terminal Commands Command: ENA DC1 Description: Set DC1 Output active. Sample Output: SynQor>ENA DC1 Flash Updated. SynQor> Discussion: Command sets the DC1 Output to activate with the enable state of the UPS output. This is a non-volatile setting. Sending this command will not immediately activate the DC1 Output unless the UPS Output is already enabled with the front panel switch or "OUTPUT ENABLE" command. [This command is only available for Communication Board Code Rev 2.0 and later. This command is only available if the DC1 Option is installed.] Command: ENA DC2 Description: Set DC2 Output active. Sample Output: SynQor>ENA DC2 Flash Updated. SynQor> Discussion: Command sets the DC2 Output to activate with the enable state of the UPS output. This is a non-volatile setting. Sending this command will not immediately activate the DC2 Output unless the UPS Output is already enabled with the front panel switch or "OUTPUT ENABLE" command. [This command is only available for Communication Board Code Rev 2.0 and later. This command is only available if the DC2 Option is installed.] Command: FAN SERVICE Description: Execute fan service sequence immediately (cycles through fan speed settings). Sample Output: SynQor>FAN SERVICE Fan service initiated SynQor> Discussion: The fan service sequence cycles the fans through their different speed ranges, and compares the measured fan RPM to the factory-new levels. Significant speed degradation will be indicated by a "fan service required" LED on the front panel. Note that the fan service sequence will not slow the fans down below the speed dictated by the internal temperatures. The fan service sequence normally runs automatically after every 24 hours of continuous operation, or more frequently if a fan speed degradation condition is detected. Fan service sequence will not run on battery power. 065-0000020 Rev D Page 9 of 18 SynQor UPS Terminal Commands Command: FAN SET x Description: Manually set fan speed, x=0 to 4. Sample Output: SynQor>FAN SET 1 Fan speed set. SynQor> Discussion: Manually increase the fan speed. Fans will not slow to a speed below that dictated by internal temperatures. Manually setting a higher fan speed will modify the UPS Cooling System Indicator LED (F0) as indicated in the User Guide. Command: FAN STATUS? Description: Display inputs to fan controller. Sample Output: SynQor>FAN STATUS? Current Speed: 0 Last Trigger Up: Manual Control Decel Timer: &H0000 &H0000 Var: value / thresh_down / thresh_up / type Manual Control: &H0000 / &H0000 / &H0000 / higher value -> speed up Diag Timer: &H0003 / &H4381 / &H4380 / higher value -> speed up AcuQor Prim: &H00F5 / &H0000 / &H0136 / higher value -> speed up AcuQor Sec: &H00F1 / &H0000 / &H0136 / higher value -> speed up Control PCB: &H0134 / &H0000 / &H01AD / higher value -> speed up Battery: &H0BA2 / &H0000 / &H0C08 / higher value -> speed up SynQor> Discussion: Displays inputs and status of the fan speed controller. The Last Trigger Up reflects which input to the controller last caused an increase in the fan speed. The list of fan controller inputs indicates which modules are online and providing triggers to control the fan speed. For each input, the present value is listed, as well as the thresholds applied to that value to cause a trigger to a higher or lower fan speed. Manual Control is the terminal interface and Diag Timer is the interval counter for the fan service sequence. Some inputs may be omitted from the list. For example, if there is no AC input power present then the ACuQor inputs will not be returned. Command: FAND DISABLE Description: Disable execution of fan diagnostics every 24 hours. Sample Output: SynQor>FAND DISABLE Flash Updated. SynQor> Discussion: Disables automatic execution of the fan diagnostic sequence after every 24 hours of operation. If the fan diagnositic sequence is disabled, a transient fan speed fault may not be cleared automatically. 065-0000020 Rev D Page 10 of 18 SynQor UPS Terminal Commands Command: FAND ENABLE Description: Enable execution of fan diagnositcs every 24 hours (default factory setting). Sample Output: SynQor>FAND ENABLE Flash Updated. SynQor> Discussion: Allows execution of the fan diagnostics automatically based on internal timing intervals. The fan diagnostics cycle the fan through the various speeds and compares detected fan RPM to factory-new values. Command: FANS? Description: Display fan speeds and input voltage. Sample Output: SynQor>FANS? Fan0 RPM = 10699 Fan1 RPM = 10344 Fan Voltage = 11.9 V Fan Status / State = &H2100 Fan Diag Timer [h:mm] = 23:59 SynQor> Discussion: Reports measure fan speed and applied voltage. The Fan Status / State variable provides additional information about the fan status. Fan Status bit decoding: b15-13: Fan speed value from 0-4. In sample, speed b15-13=001, indicating speed 1 b11: Machine status is Faulted b10: Machine status is Starting b9: Machine status is Running b8: Machine status is Standby (indicated in sample) b7: Fan service is required b6: Fan diagnostics mode active The Fan Diag Timer variable displays the time until the next scheduled fan diagnostics routine. Command: FOUT 400 Description: Set AC Output frequency to 400 Hz. Sample Output: SynQor>FOUT 400 Flash Updated. SynQor> Discussion: Command sets UPS AC Output frequency to 400Hz. WARNING: This setting may damage connected AC loads if the loads are not rated for 400Hz operation. [This command is only available for Communication Board Code Rev 2.0 and later.] 065-0000020 Rev D Page 11 of 18 SynQor UPS Terminal Commands Command: FOUT 50 Description: Set AC Output frequency to 50 Hz. Sample Output: SynQor>FOUT 50 Flash Updated. SynQor> Discussion: Command sets UPS AC Output frequency to 50Hz. WARNING: This setting may damage connected AC loads if the loads are not rated for 50Hz operation. [This command is only available for Communication Board Code Rev 2.0 and later.] Command: FOUT 60 Description: Set AC Output frequency to 60 Hz. Sample Output: SynQor>FOUT 60 Flash Updated. SynQor> Discussion: Command sets UPS AC Output frequency to 60Hz. WARNING: This setting may damage connected AC loads if the loads are not rated for 60Hz operation. [This command is only available for Communication Board Code Rev 2.0 and later.] Command: INPUTS? Description: Display status of inputs to UPS system. Sample Output: SynQor>INPUTS? AC In Voltage = 113 V AC In Current = 1990 mA AC In Frequency = 60.3 Hz Ext DC In Voltage = 0.5 V Fault Register = &H0000 Multi-unit Config = &H000F Non-volatile Config = &H1D01 SynQor> 065-0000020 Rev D Page 12 of 18 SynQor UPS Terminal Commands Discussion: Reports status of inputs to UPS system. The Fault Register decoding is as follows: b15: Internal Bus Average Voltage Low b14: Remote Shutdown requested from back panel b13: Remote start requested from back panel b12: Front panel switch pressed down (off) b11: External DC Input Fault b10: Software Disable Command b9: Software Enable Command b8: DCOUT2 Fault b7: DCOUT1 Fault b6: Internal Bus High b5: Internal Bus Low b4: Front panel switch pressed up (on / cold-start) b3: Internal 5V supply High b2: Internal 5V supply Low b1: Over-temperature Warning b0: Over-temperature condition [Revisions of Communication Board Code before Rev 2.0 report 'Switch Status' instead of 'Fault Register'.] The Multi-unit Config register is determined by the connection of a paralleling cable on the rear panel male DB15 connector. The Non-volatile Config register gives the FLASH memory options as follows: b12: AC Output Active b11: DC2 Output Active b10: DC1 Output Active b9: External DC Input Option Installed b8: AC Output Option Installed b7: DC2 Output Option Installed b6: Ungrounded Output Option b5: AC Output Autostart Enabled b4: DC1 Output Option Installed b3: Fan Diagnostics Disabled b2: Audible Alarm Disabled b1: Debug Mode on Startup Enabled b0: Fan Calibration Done Command: NET RESTORE Description: Restore network configuration settings to factory defaults. Sample Output: SynQor>NET RESTORE Factory Networking Defaults Restored. SynQor> Discussion: Command restores settings for network configuration to factory defaults. [This command is only available with the Ethernet Option installed.] 065-0000020 Rev D Page 13 of 18 SynQor UPS Terminal Commands Command: NETWORK? Description: Display Ethernet IP address and MAC address. Sample Output: SynQor>NETWORK? IP Address = 10.2.6.8 MAC Address = 00:04:A3:B5:73:AC SynQor> Discussion: Command displays the device pre-set MAC address and currently active IP address. [This command is only available with the Ethernet Option installed.] Command: OUTPUT DISABLE Description: Shutdown AC and DC outputs of UPS system, reverting to standby or off state. Sample Output: SynQor>OUTPUT DISABLE Output Disabled. SynQor> Discussion: Disables output on AC and DC outputs if currently active. This terminal command is equivalent to holding down the front panel switch. Command: OUTPUT ENABLE Description: Enable AC and DC outputs of UPS system. Sample Output: SynQor>OUTPUT ENABLE Output Enabled. SynQor> Discussion: Enables output on AC and DC outputs. This terminal command is equivalent to pushing the front panel switch upwards. 065-0000020 Rev D Page 14 of 18 SynQor UPS Terminal Commands Command: OUTPUTS? Description: Display status of outputs from UPS system. Sample Output: SynQor>OUTPUTS? Total Power Out =9W AC Out Power = 2W DC Out Power = 7W AC Out Voltage RMS = 115650 mV AC Out Current RMS =633 mA AC Out Frequency = 60 Hz Alarm Status = &H0400 Fan Status / State = &H2400 BIT Result = &H1002 SynQor> Discussion: Reports telemetry data on AC and DC outputs. DC output power will appear even if DC output option is not installed. The Alarm Status variable details the state of the audible alarms: b7 : Audible alarm is muted (not disabled) b3 : Four beep alarm active b2 : Three beep alarm active b1 : Two beep alarm active b0 : One beep alarm active The "FANS?" Command description details the Fan Status / State register. The BIT Result variable displays the last result from a built-in test routine, if applicable. Command: RESTART x Description: Shutdown output immediately, re-enable output after x seconds. Sample Output: SynQor>RESTART 5 Timed reboot started. SynQor> Discussion: If outputs are enabled, they will be immediately disabled. After the requested delay, outputs will enable. Outputs will enable whether or not they were in an enabled state when the command was first issued. Maximum permissible value for restart time is 10,737,418 seconds, approximately 4 months. 065-0000020 Rev D Page 15 of 18 SynQor UPS Terminal Commands Command: RUNTEST x Description: Run internal built-in test routine. Sample Output: SynQor>RUNTEST 3 General System Test Started. SynQor>Test Complete. Result=&H1002 Test Passed. SynQor> Discussion: Runs internal built-in test routine. Legal values for x: x=0 or 2 : Abort test in progress. x=3 : Run General Systems Test; verifies internal bias voltages, fans, voltage inputs and outputs. x=4 : Quick Battery Test; verifies proper battery operation. x=5 : Deep Battery Test; switches to battery power and runs battery down to 20% charge to test battery runtime. [Test time depends strongly on output load.] [This command is only available for Communication Board Code Rev 2.0 and later.] Command: SHUTDOWN x Description: Shutdown output after x seconds. Sample Output: SynQor>SHUTDOWN 5 Timed shutdown started. SynQor> Discussion: Outputs will be disabled after the requested delay time. Maximum permissible value for shutdown delay is 10,737,418 seconds, approximately 4 months. Command: SNMP RESTORE Description: Restore SNMP configuration to factory defaults. Sample Output: SynQor>SNMP RESTORE Factory SNMP Defaults Restored. SynQor> Discussion: Command restores SNMP configuration to factory defaults (SNMP disabled). [This command is only available with the Ethernet Option installed.] Command: SOURCE LOG Description: Begin real-time output of power source status and switchover events. Sample Output: SynQor>SOURCE LOG SynQor>[…continuous debug output will follow] Discussion: Source log output is useful to monitor input source switching and detected faults with supervision from SynQor factory personnel. To terminate source logging, send several newline characters through the terminal interface. 065-0000020 Rev D Page 16 of 18 SynQor UPS Terminal Commands Command: SOURCES? Description: Display status of each defined source for the UPS system (AC, DC, and battery). Sample Output: SynQor>SOURCES? AC Input Module - Faults: &H0000 - Ok for load: YES - Ready for load: YES - Loaded: YES - Fault Count: 0 External DC Input - Faults: &H0101 - Ok for load: NO - Ready for load: NO - Loaded: NO - Fault Count: 0 Internal Battery - Faults: &H0000 - Ok for load: YES - Ready for load: YES - Loaded: NO - Fault Count: 0 SynQor> Discussion: Displays summary of each available input source and whether they appear ready to accept load power. Note that External DC Input will be listed even if the DC input is not installed. Command: STARTUP x Description: Enable outputs after x seconds. Sample Output: SynQor>STARTUP 5 Timed startup begun. SynQor> Discussion: Outputs will be enabled after the requested delay time. Maximum permissible value for enable delay is 10,737,418 seconds, approximately 4 months. [This command is only available for Communication Board Code Rev 2.0 and later.] 065-0000020 Rev D Page 17 of 18 SynQor UPS Terminal Commands Command: TEMPS? Description: Display reported temperatures for internal subsystems. Sample Output: SynQor>TEMPS? AC/DC Temperature 1 = 30 C AC/DC Temperature 2 = 29 C Control Brd Temp = 25 C DC/AC Temperature = -50 C Battery Temperature = 24.8 C SynQor> Discussion: Displays measured temperature for installed components. Note that unpowered components will display invalid results. For example, in the sample above, the output voltage is disabled, so the DC/AC readback temperature is invalid. Information Subject to Change Without Notice 065-0000020 Rev D Page 18 of 18