Indoor SelectableOutput Horns, Strobes, and Horn Strobes for Wall Applications SpectrAlert® Advance audible visible notification products are rich with features guaranteed to cut installation times and maximize profits. Features • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • A utomatic selection of 12- or 24-volt operation at 15 and 15/75 candela • F ield-selectable candela settings on wall units: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185 • Horn rated at 88+ dBA at 16 volts • Rotary switch for horn tone and three volume selections • Universal mounting plate for wall units • M ounting plate shorting spring checks wiring continuity before device installation • Electrically Compatible with legacy SpectrAlert devices • Compatible with MDL3 sync module • Listed for ceiling or wall mounting 3023572 Like the entire SpectrAlert Advance product line, wall-mount horns, strobes, and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify installation and protect devices from construction damage, SpectrAlert Advance utilizes a universal mounting plate with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with three volume selections. Agency Listings S4011 (chimes, horn strobes, horns) S5512 (strobes) The SpectrAlert Advance series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry. With white and red plastic housings, wall and ceiling mounting options, and plain and FIRE-printed devices, SpectrAlert Advance can meet virtually any application requirement. MEA452-05-E 7125-1653:186 (indoor strobes) 7125-1653:188 (horn strobes, chime strobes) 7135-1653:189 (horns, chimes) SpectrAlert Advance Specifications Architect/Engineer Specifications General SpectrAlert Advance horns, strobes, and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or fullwave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411⁄16 × 411⁄16 × 21⁄8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature Humidity Range Strobe Flash Rate Nominal Voltage Operating Voltage Range2 Operating Voltage Range MDL3 Sync Module Input Terminal Wire Gauge Wall-Mount Dimensions (including lens) Horn Dimensions Wall-Mount Trim Ring Dimensions (sold as a 5 pack) (TR-HS) 32°F to 120°F (0°C to 49°C) 10 to 93% non-condensing 1 flash per second Regulated 12 DC/FWR or regulated 24 DC/FWR1 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) 12 to 18 AWG 5.6˝ L × 4.7˝ W × 2.5˝ D (142 mm L × 119 mm W × 64 mm D) 5.6˝ L × 4.7˝ W × 1.3˝ D (142 mm L × 119 mm W × 33 mm D) 5.7˝ L × 4.8˝ W × 0.35˝ D (145 mm L × 122 mm W × 9 mm D) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. UL Current Draw Data UL Max. Strobe Current Draw (mA RMS) 8–17.5 Volts Candela DC FWR Standard 15 123 128 Candela 15/75 142 148 Range 30 NA NA 75 NA NA 95 NA NA 110 NA NA 115 NA NA High 135 NA NA Candela 150 NA NA Range 177 NA NA 185 NA NA 16–33 Volts DC FWR 66 71 77 81 94 96 158 153 181 176 202 195 210 205 228 207 246 220 281 251 286 258 UL Max. Horn Current Draw (mA RMS) 8–17.5 Volts Sound Pattern dB DC FWR Temporal High 57 55 Temporal Medium 44 49 Temporal Low 38 44 Non-temporal High 57 56 Non-temporal Medium 42 50 Non-temporal Low 41 44 Coded High 57 55 Coded Medium 44 51 Coded Low 40 46 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd) 8–17.5 Volts 16–33 Volts DC Input 15 15/75 15 15/75 30 75 Temporal High 137 147 79 90 107 176 Temporal Medium 132 144 69 80 97 157 Temporal Low 132 143 66 77 93 154 Non-Temporal High 141 152 91 100 116 176 Non-Temporal Medium 133 145 75 85 102 163 Non-Temporal Low 131 144 68 79 96 156 FWR Input Temporal High 136 155 88 97 112 168 Temporal Medium 129 152 78 88 103 160 Temporal Low 129 151 76 86 101 160 Non-Temporal High 142 161 103 112 126 181 Non-Temporal Medium 134 155 85 95 110 166 Non-Temporal Low 132 154 80 90 105 161 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd) 16–33 Volts DC Input 135 150 177 185 FWR Input Temporal High 245 259 290 297 Temporal High Temporal Medium 235 253 288 297 Temporal Medium Temporal Low 232 251 282 292 Temporal Low Non-Temporal High 255 270 303 309 Non-Temporal High Non-Temporal Medium 242 259 293 299 Non-Temporal Medium Non-Temporal Low 238 254 291 295 Non-Temporal Low Horn and Horn Strobe Output (dBA) Switch Position 1 2 3 4 5 6 7† 8† 9† Sound Pattern Temporal Temporal Temporal Non-Temporal Non-Temporal Non-Temporal Coded Coded Coded dB High Medium Low High Medium Low High Medium Low 8–17.5 Volts DC FWR 78 78 75 75 71 71 82 82 78 78 73 74 82 82 78 78 74 75 16–33 Volts DC FWR 84 84 80 80 76 76 88 88 85 85 81 81 88 88 85 85 81 81 Settings 7, 8, and 9 are not available on 2-wire horn strobes. † 95 194 182 179 201 187 182 110 212 201 198 221 207 201 115 218 210 207 229 216 210 190 184 184 203 189 184 210 202 194 221 208 202 218 206 201 229 216 211 16–33 Volts 135 150 215 231 209 224 207 221 233 248 219 232 214 229 Horn Tones and Sound Output Data 24-Volt Nominal Reverberant Anechoic DC FWR DC FWR 88 88 99 98 86 86 96 96 83 80 94 89 93 92 100 100 90 90 98 98 88 84 96 92 93 92 101 101 90 90 97 98 88 85 96 92 16–33 Volts DC FWR 69 75 58 69 44 48 69 75 60 69 50 50 69 75 56 69 52 50 177 258 250 248 275 262 256 185 265 258 256 281 267 262 SpectrAlert Advance Dimensions 4.7˝ 6.8˝ Dia. 2.5˝ 2.5˝ 5.6˝ Wall-mount horn strobes SpectrAlert Advance Ordering Information Model Description Wall Horn Strobes P2R 2-Wire Horn Strobe, Standard cd, Red P2R-P 2-Wire Horn Strobe, Standard cd, Red, Plain P2R-SP 2-Wire Horn Strobe, Standard cd, Red, “FUEGO” P2RH 2-Wire Horn Strobe, High cd, Red P2RH-P 2-Wire Horn Strobe, High cd, Red, Plain P2W 2-Wire Horn Strobe, Standard cd, White P2W-P 2-Wire Horn Strobe, Standard cd, White, Plain P2WH 2-Wire Horn Strobe, High cd, White P2WH-P 2-Wire Horn Strobe, High cd, White, Plain P4R 4-Wire Horn Strobe, Standard cd, Red P4R-P 4-Wire Horn Strobe, Standard cd, Red, Plain P4RH 4-Wire Horn Strobe, High cd, Red P4W 4-Wire Horn Strobe, Standard cd, White Wall Strobes SR Strobe, Standard cd, Red SR-P Strobe, Standard cd, Red, Plain SR-SP Strobe, Standard cd, Red, “FUEGO” Model Description Wall Strobes (cont.) SRH Strobe, High cd, Red SRH-P Strobe, High cd, Red, Plain SRH-SP Strobe, High cd, Red, “FUEGO” SW Strobe, Standard cd, White SW-P Strobe, Standard cd, White, Plain SWH Strobe, High cd, White SWH-P Strobe, High cd, White, Plain Horns HR Horn, Red HW Horn, White Accessories TR-HS Trim Ring, Wall, Red SBBR Indoor Surface Mount Back Box, Red SBBW Indoor Surface Mount Back Box, White Notes: All -P models have a plain housing (no “FIRE” marking on cover) All -SP models have “FUEGO” marking on cover “Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2014 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS10201 • 1/14