Indoor Selectable- Output Horns, Strobes, and

Indoor SelectableOutput Horns,
Strobes, and
Horn Strobes for
Wall Applications
SpectrAlert® Advance audible visible notification products
are rich with features guaranteed to cut installation times
and maximize profits.
Features
• Plug-in design with minimal intrusion into the back box
• Tamper-resistant construction
• A
utomatic selection of 12- or 24-volt operation at
15 and 15/75 candela
• F
ield-selectable candela settings on wall units: 15, 15/75,
30, 75, 95, 110, 115, 135, 150, 177, and 185
• Horn rated at 88+ dBA at 16 volts
• Rotary switch for horn tone and three volume selections
• Universal mounting plate for wall units
• M
ounting plate shorting spring checks wiring continuity before
device installation
• Electrically Compatible with legacy SpectrAlert devices
• Compatible with MDL3 sync module
• Listed for ceiling or wall mounting
3023572
Like the entire SpectrAlert Advance product line, wall-mount horns,
strobes, and horn strobes include a variety of features that increase
their application versatility while simplifying installation. All devices
feature plug-in designs with minimal intrusion into the back box,
making installations fast and foolproof while virtually eliminating
costly and time-consuming ground faults.
To further simplify installation and protect devices from construction
damage, SpectrAlert Advance utilizes a universal mounting plate
with an onboard shorting spring, so installers can test wiring
continuity before the device is installed.
Installers can also easily adapt devices to a suit a wide range of
application requirements using field-selectable candela settings,
automatic selection of 12- or 24-volt operation, and a rotary switch
for horn tones with three volume selections.
Agency Listings
S4011 (chimes, horn strobes, horns)
S5512 (strobes)
The SpectrAlert Advance series offers the most versatile and
easy-to-use line of horns, strobes, and horn strobes in the industry.
With white and red plastic housings, wall and ceiling mounting
options, and plain and FIRE-printed devices, SpectrAlert Advance
can meet virtually any application requirement.
MEA452-05-E
7125-1653:186 (indoor strobes)
7125-1653:188 (horn strobes,
chime strobes)
7135-1653:189 (horns, chimes)
SpectrAlert Advance Specifications
Architect/Engineer Specifications
General
SpectrAlert Advance horns, strobes, and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or
double-gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall
be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate.
Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification
appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification
appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between
16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or fullwave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95,
110, 115, 135, 150, 177, and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service.
The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for
visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash
tube and associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for
fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light
shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch
between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. On four-wire
products, the strobe shall be powered independently of the sounder. The horn on horn strobe models shall operate on a coded or non-coded
power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module
shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair of wires. The module shall mount to a 411⁄16 × 411⁄16 × 21⁄8-inch back box. The module shall also
control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature
Humidity Range
Strobe Flash Rate
Nominal Voltage
Operating Voltage Range2
Operating Voltage Range MDL3 Sync Module
Input Terminal Wire Gauge
Wall-Mount Dimensions (including lens)
Horn Dimensions
Wall-Mount Trim Ring Dimensions (sold as a 5 pack) (TR-HS)
32°F to 120°F (0°C to 49°C)
10 to 93% non-condensing
1 flash per second
Regulated 12 DC/FWR or regulated 24 DC/FWR1
8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)
12 to 18 AWG
5.6˝ L × 4.7˝ W × 2.5˝ D (142 mm L × 119 mm W × 64 mm D)
5.6˝ L × 4.7˝ W × 1.3˝ D (142 mm L × 119 mm W × 33 mm D)
5.7˝ L × 4.8˝ W × 0.35˝ D (145 mm L × 122 mm W × 9 mm D)
Notes:
1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.
2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd.
UL Current Draw Data
UL Max. Strobe Current Draw (mA RMS)
8–17.5 Volts
Candela DC
FWR
Standard
15
123
128
Candela
15/75
142
148
Range
30
NA
NA
75
NA
NA
95
NA
NA
110
NA
NA
115
NA
NA
High
135
NA
NA
Candela
150
NA
NA
Range
177
NA
NA
185
NA
NA
16–33 Volts
DC
FWR
66
71
77
81
94
96
158
153
181
176
202
195
210
205
228
207
246
220
281
251
286
258
UL Max. Horn Current Draw (mA RMS)
8–17.5 Volts
Sound Pattern
dB
DC
FWR
Temporal
High
57
55
Temporal
Medium
44
49
Temporal
Low
38
44
Non-temporal
High
57
56
Non-temporal
Medium
42
50
Non-temporal
Low
41
44
Coded
High
57
55
Coded
Medium
44
51
Coded
Low
40
46
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd)
8–17.5 Volts
16–33 Volts
DC Input
15
15/75
15
15/75
30
75
Temporal High
137
147
79
90
107
176
Temporal Medium
132
144
69
80
97
157
Temporal Low
132
143
66
77
93
154
Non-Temporal High
141
152
91
100
116
176
Non-Temporal Medium
133
145
75
85
102
163
Non-Temporal Low
131
144
68
79
96
156
FWR Input
Temporal High
136
155
88
97
112
168
Temporal Medium
129
152
78
88
103
160
Temporal Low
129
151
76
86
101
160
Non-Temporal High
142
161
103
112
126
181
Non-Temporal Medium
134
155
85
95
110
166
Non-Temporal Low
132
154
80
90
105
161
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd)
16–33 Volts
DC Input
135
150
177
185
FWR Input
Temporal High
245
259
290
297
Temporal High
Temporal Medium
235
253
288
297
Temporal Medium
Temporal Low
232
251
282
292
Temporal Low
Non-Temporal High
255
270
303
309
Non-Temporal High
Non-Temporal Medium
242
259
293
299
Non-Temporal Medium
Non-Temporal Low
238
254
291
295
Non-Temporal Low
Horn and Horn Strobe Output (dBA)
Switch
Position
1
2
3
4
5
6
7†
8†
9†
Sound Pattern
Temporal
Temporal
Temporal
Non-Temporal
Non-Temporal
Non-Temporal
Coded
Coded
Coded
dB
High
Medium
Low
High
Medium
Low
High
Medium
Low
8–17.5
Volts
DC FWR
78 78
75 75
71 71
82 82
78 78
73 74
82 82
78 78
74 75
16–33
Volts
DC FWR
84 84
80 80
76 76
88 88
85 85
81 81
88 88
85 85
81 81
Settings 7, 8, and 9 are not available on 2-wire horn strobes.
†
95
194
182
179
201
187
182
110
212
201
198
221
207
201
115
218
210
207
229
216
210
190
184
184
203
189
184
210
202
194
221
208
202
218
206
201
229
216
211
16–33 Volts
135
150
215
231
209
224
207
221
233
248
219
232
214
229
Horn Tones and Sound Output Data
24-Volt Nominal
Reverberant Anechoic
DC
FWR
DC FWR
88
88
99 98
86
86
96 96
83
80
94 89
93
92
100 100
90
90
98 98
88
84
96 92
93
92
101 101
90
90
97 98
88
85
96 92
16–33 Volts
DC
FWR
69
75
58
69
44
48
69
75
60
69
50
50
69
75
56
69
52
50
177
258
250
248
275
262
256
185
265
258
256
281
267
262
SpectrAlert Advance Dimensions
4.7˝
6.8˝
Dia.
2.5˝
2.5˝
5.6˝
Wall-mount horn strobes
SpectrAlert Advance Ordering Information
Model
Description
Wall Horn Strobes
P2R
2-Wire Horn Strobe, Standard cd, Red
P2R-P
2-Wire Horn Strobe, Standard cd, Red, Plain
P2R-SP
2-Wire Horn Strobe, Standard cd, Red, “FUEGO”
P2RH
2-Wire Horn Strobe, High cd, Red
P2RH-P
2-Wire Horn Strobe, High cd, Red, Plain
P2W
2-Wire Horn Strobe, Standard cd, White
P2W-P
2-Wire Horn Strobe, Standard cd, White, Plain
P2WH
2-Wire Horn Strobe, High cd, White
P2WH-P
2-Wire Horn Strobe, High cd, White, Plain
P4R
4-Wire Horn Strobe, Standard cd, Red
P4R-P
4-Wire Horn Strobe, Standard cd, Red, Plain
P4RH
4-Wire Horn Strobe, High cd, Red
P4W
4-Wire Horn Strobe, Standard cd, White
Wall Strobes
SR
Strobe, Standard cd, Red
SR-P
Strobe, Standard cd, Red, Plain
SR-SP
Strobe, Standard cd, Red, “FUEGO”
Model
Description
Wall Strobes (cont.)
SRH
Strobe, High cd, Red
SRH-P
Strobe, High cd, Red, Plain
SRH-SP
Strobe, High cd, Red, “FUEGO”
SW
Strobe, Standard cd, White
SW-P
Strobe, Standard cd, White, Plain
SWH
Strobe, High cd, White
SWH-P
Strobe, High cd, White, Plain
Horns
HR
Horn, Red
HW
Horn, White
Accessories
TR-HS
Trim Ring, Wall, Red
SBBR
Indoor Surface Mount Back Box, Red
SBBW
Indoor Surface Mount Back Box, White
Notes:
All -P models have a plain housing (no “FIRE” marking on cover)
All -SP models have “FUEGO” marking on cover
“Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings.
“High cd” refers to strobes that include 135, 150, 177, and 185 candela settings.
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
www.systemsensor.com
©2014 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
AVDS10201 • 1/14