Indoor SelectableOutput Speaker Strobes and Dual Voltage Evacuation Speakers for Ceiling Applications SpectrAlert® Advance selectable-output speaker strobes and dual-voltage evacuation speakers can reduce ground faults and enable faster installation. Features • Plug-in design and protective cover reduce ground faults • U niversal mounting plate with an onboard shorting spring tests wiring continuity before installation • No extension ring required • F ield selectable candela settings: Standard: 15, 15/75, 30, 75, 95, 110, 115 High: 135, 150, 177, 185 • A utomatic selection of 12- or 24-volt operation at 15 and 15/75 candela • R otary switch simplifies field selection of speaker voltage (25 and 70.7 Vrms) and power settings (¼, ½, 1 and 2 watts) • SP speakers offer high fidelity sound output • SPV speakers offer high volume sound output • Compatible with System Sensor synchronization protocol • Electrical compatibility with existing SpectrAlert products • Tamper-resistant construction • Listed for ceiling or wall mounting Agency Listings S4048 7320-1653:201 10-08-E The SpectrAlert Advance Series of speakers and speaker strobes reduce costly ground faults using a plug-in design and universal mounting plate that allow the installer to pre-wire mounting plates, dress the wires, and confirm wiring continuity before plugging in the speakers. In addition, a protective plastic cover prevents nicked wires by covering exposed speaker components. These devices also enable faster installations by providing instant feedback to ensure that wiring is properly connected, rotary switches to select voltage and power settings, and 11 field-selectable candela settings for both wall and ceiling speaker strobes. The low total harmonic distortion of the SP speaker offers high fidelity sound output while the SPV speaker offers high volume sound output for use in high ambient noise applications. SpectrAlert Advance makes installation easy • Attach a universal mounting plate to a 4 × 4 × 21⁄8 inch back box . Flush-mount applications do not require an extension ring. • Connect the notification appliance circuit or speaker wiring to the terminals on the mounting plate. • Attach the speaker or speaker strobe to the mounting plate by inserting the product tabs into the mounting plate grooves. Hinge the device into position to lock the product pins into the mounting plate terminals. The device will temporarily hold in place with a catch until it is secured with a captured mounting screw. SpectrAlert Advance Speaker and Speaker Strobe Specifications Architectural/Engineering Specifications General SpectrAlert Advance speaker and speaker strobes shall mount to a 4 × 4 × 21⁄8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance speaker strobes, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32°F and 120°F from a regulated DC, or full-wave rectified, unfiltered power supply. Speaker strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, 185. Speaker The speaker shall be a System Sensor SpectrAlert Advance model _______ dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. It should be listed to UL 1480 and shall be approved for fire protective service. The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F. The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe combination The speaker strobe shall be a System Sensor SpectrAlert Advance model __________ listed to UL1480 and UL 1971 and be approved for fire protective signaling systems. The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch, and shall have a frequency range of 400 to 4,000 Hz. The speaker shall have power taps that are selected by rotary switch. The strobe shall comply with the NFPA 72 requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz. The module shall mount to a 411⁄16 × 411⁄16 × 21⁄8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical Specifications Operating Temperature Humidity Range Dimensions, Ceiling-Mount SPC Speaker SPCV Speaker With Surface Mount Back Box SPSC Speaker Strobe SPSCV Speaker Strobe With Surface Mount Back Box Electrical/Operating Specifications Nominal Voltage (speakers) Maximum Supervisory Voltage (speakers) Strobe Flash Rate Nominal Voltage (strobes) Operating Voltage Range (includes fire alarm panels with built in sync) Operating Voltage with MDL3 Sync Module Frequency Range Power 32°F to 120°F (0°C to 49°C) 10 to 93% non-condensing Diameter 6.8 in, 173 mm 6.8 in, 173 mm 6.9 in, 175 mm 6.8 in, 173 mm 6.8 in, 173 mm 6.9 in, 175 mm Depth 2.8 in, 71 mm 2.9 in, 74 mm 3.4 in, 86 mm 2.8 in, 71 mm 2.9 in, 74 mm 5.325 in, 135 mm 25 Volts or 70.7 Volts (nominal) 50 VDC 1 flash per second Regulated 12 V DC/FWR or regulated 24 DC/FWR 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) 400 to 4,000 Hz ¼, ½, 1, 2 watts UL Current Draw Data UL Max. Strobe Current Draw (mA RMS) Candela 15 15/75 30 75 95 110 115 135 150 177 185 Standard Candela Range High Candela Range Sound Output UL Reverberant (dBA @ 10 ft.) Ceiling-Mount SPC Series Ceiling-Mount SPCV Series Ceiling-Mount SPSC Series Ceiling-Mount SPSCV Series 8 to 17.5 Volts DC 123 142 NA NA NA NA NA NA NA NA NA FWR 128 148 NA NA NA NA NA NA NA NA NA 16 to 33 Volts DC 66 77 94 158 181 202 210 228 246 281 286 FWR 71 81 96 153 176 195 205 207 220 251 258 2W 86 90 85 89 1W 83 87 82 86 ½W 80 84 79 83 ¼W 77 81 76 80 Dimensions 6.81˝ .97˝ 1.96˝ 6.81˝ Ceiling-Mount SPV Speaker .97˝ 1.84˝ Ceiling-Mount SP Speaker 6.81˝ 2.83˝ 1.60˝ Ceiling-Mount SPS Speaker Strobe 1.84˝ Surface Mounting Ceiling-Mount Speaker with SBBCR/SBBCW Surface Mount Back Box Skirt Ordering Information for SpectrAlert® Advance Speakers and Speaker Strobes Ceiling Mount White SPCW SPCWV SPSCW SPSCW-P SPSCWH SPSCWH-P SPSCWV SPSCWV-P SPSCWVH SPSCW-CLR-ALERT Accessories White RFPW SBBCW TRCW Red SPCR SPCRV SPSCR — SPSCRH — SPSCRV — SPSCRVH — Description Speaker only Speaker only, High dB Speaker Strobe, Standard cd Plain Speaker Strobe, Standard cd Speaker Strobe, High cd Plain Speaker Strobe, High cd Speaker Strobe, Standard cd, High dB Plain Speaker Strobe, High Volume, Clear Lens, White Speaker Strobe, High cd, High dB Speaker Strobe, Standard cd, Clear Lens Red RFP SBBCR TRC Description 7 in × 9.5 in Retrofit Plate Surface Mount Back Box Ceiling Mount Trim Ring Notes: All -P models have a plain housing (no “FIRE” marking on cover) “Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2015 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS11102 • 2/15