RTM - Recom International Power Gmbh

Features
●
●
●
●
●
●
Unregulated
Converters
ECONOLINE
1:1 Input Range
Efficiency up to 84%
2kVDC and 3kVDC Isolation Option
Approved for Medical Applications
-40°C to +90°C Operating Temperature Range
2W SMD Package
DC/DC-Converter
Selection Guide
Part
Isolation
Input
Output
Output
Number
Voltage
Voltage
Voltage
Current
Efficiency
Load
(kV)
(VDC)
(VDC)
(mA)
(max.)
(max.) (1)
RTM-0505S*
2
5
5
400
79%
2200µF
RTM-1205S*
2
12
5
400
83%
2200µF
RTM-2405S*
2
24
5
400
84%
2200µF
SMD
Capacitive
2 Watt SMD
Single Output
* add Suffix “/H“ for 3kVDC/1sec. Isolation e.g. RTM-0505S/H
* add Suffix “-R“ for tape&reel packing e.g. RTM-1205S-R or RTM-2405S/H-R
Specifications (measured at TA = 25°C, nominal input voltage and rated output current unless otherwise specified)
Input Voltage Range
±10% max.
Output Voltage Accuracy
-1% typ., ±5% max.
Line Voltage Regulation
(low line to high line at max. load)
Load Voltage Regulation
(10% to 100% full load)
Output Ripple and Noise (20MHz BW limited)
1.2% typ.
50mVp-p typ., 100mVp-p max.
Operating Frequency (Vin=nominal input)
20kHz min. / 40kHz typ. / 80kHz max.
Efficiency at Full Load
see Selection Guide
Minimum Load = 0%
Specifications valid for 10% minimum load only
Isolation Voltage
Isolation Voltage
(tested for 1 second)
2000 VDC
(rated for 1 minute**)
1600VDC
H-Suffix
(tested for 1 second)
3000 VDC
H-Suffix
(rated for 1 minute**)
2400VDC
Isolation Capacitance
(Viso=500V)
15GΩ min.
with Derating
-40°C to +90°C
Short-Circuit Protection
1 second
Storage Temperature
-55°C to +125°C
Reflow Temperature
RoHS compliant
Vapor Phase Process
(for more details see Application Notes)
95% RH
100
1.4g
80
All Types
27 pcs per Tube
All Types
500 pcs per Reel
using MIL-HDBK 217F
Detailed Information see
Application Notes chapter "MTBF" using MIL-HDBK 217F
3907 x 10³ hours
313 x 10³ hours
Certifications
EN Medical Safety
60
50
40
Report: MDD1112018 + RM1112018
IEC/EN 60601-1 3rd Edition
Report: SPCLVD1112018
Safe Operating Area
20
0
Medical Report + ISO14971 Risk Assessment
EN General Safety
(Ambient Temperature)
230°C (90 sec.) max.
Package Weight
Packing Quantity
Derating-Graph
245°C (30 sec.), Peak 255°C (5sec.) max.
Relative Humidity
MTBF (+85°C)
RTM
Output Power (%)
Operating Temperature Range
}
EN-60601-1 Certified
EN-60950-1 Certified
30pF typ., 50pF max.
Isolation Resistance
MTBF (+25°C)
RoHS
2011/65/EU
6/6
10% typ., 15% max.
-40
0
50 90100
150
Operating Temperature °C
EN60950-1, 2nd Edition
Note:
Note1: Maximum capacitive load is defined as the capacitive load that will allow start up in under
1 second without damage to the converter
**Any data referred to in this datasheet are of indicative nature
and based on our practical experience only. For further details,
please refer to our Application Notes.
Refer to Application Notes
www.recom-power.com
REV: 0/2015
E-83
RTM Series
ECONOLINE
DC/DC-Converter
Typical Characteristics
RTM-xx05S
Efficiency / Load
100
Deviation from Nominal (%)
2405
Efficiency %
80
0505
60
1205
40
20
0
Deviation / Load
25
20
15
40%
80%
60%
Total Output current (%)
20%
100%
2405
5
0
1205
-5
-10
0%
0505
10
0%
20%
40%
80%
60%
Total Output current (%)
100%
Tolerance Envelope
+10%
Typical L
o
+5%
V Nom.
ad Line
+5%
– 1%
Output Voltage
– 5%
10%
50%
100%
Output Load Current (%)
Package Style and Pinning
8.70
18.00
RTM
7.15
Pin Connections
Pin #
Function
4.05 max.
1
10.65
1.27x13
Recommended Footprint Details
17 16 15
1.40
28 27
TOP VIEW
Pb
12
12 13 14
-Vin
12
-Vout
13
+Vout
14~17
NC
27,28
NC
NC = No Connection
1.27
11.80
RECOM
RTM-xx05S
9.00
+Vin
2
Unit:
Tolerance:
mm
± 0.25 mm
0.90
13*1.27= 16.51
EMC Filtering - Suggestion for EN55022 Class B
470pF/4kVDC
Fuse
DC
Input
+
GND
Output
C1
DC
GND
Input
Voltage
Inductance/
Capacitance (C1)
5V
4.7µF
12V
2.2µF
24V
47µF
The product information and specifications are subject to change without prior notice. RECOM products are not authorized for use in safety-critical applications (such as life support) without RECOM’s explicit
written consent. A safety-critical application is defined as an application where a failure of a RECOM product may reasonably be expected to endanger or cause loss of life, inflict bodily harm or damage property. The buyer
shall indemnify and hold harmless RECOM, its affiliated companies and its representatives against any damage claims in connection with the unauthorized use of RECOM products in such safety-critical applications.
E-84
REV: 0/2015
www.recom-power.com