INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS
TSPC-DCM600 Series
Redundancy/Isolation Module.
This module contains two diodes that provide isolation for two power supplies in case one power supply output
becomes short circuit.
Order Code
* Input Voltage
range
** Output
Max. Reverse Voltage
[Vdc]
Voltage drop across the
diodes/internal losses
TSPC-DCM600
24Vdc nom.
24Vdc nom / 25A max.
35Vdc
0.75 [Vdc typ.] 1.2 [Vdc max.]
*
Note 1 (5 – 28Vdc)
**
Note 2 (Output voltage = Input voltage – Load dependent dropout voltage)
Input current:
TSPC-DCM600
@ Vin = 24Vdc
20mA min.
@ Vin = 24Vdc
25A max.
Power Consumption @ Vin = 24Vdc @ Vin = 24Vdc
0.5Watt min. 28.8 Watt max.
TSPC-DCM600
Operational Output Voltage range
Operating temperature range:
Natural Air Convection Cooling
Output Power Derating:
Boost Power
Boost Power Operating temperature range:
Natural Air Convection Cooling
Storage temperature range:
IP Class
Connections:
Input
Output
Wire Size: Input & Output
Case material:
E x a m p le T S P C u n it# 1
-
+
5Vdc min. – 28Vdc max.
–25°C up to +70°C max
–13°F up to +158°F max
see TSPC Datasheet for power supply de-rating.
see TSPC Datasheet for Boost power operation.
–25°C up to +60°C max
–13°F up to +140°F max
–25°C up to +85°C max
–13°F up to +185°F max
IP20
2 x 2 Screw type terminal Combi – Typ. Recommended tightening torque 0.5 to 0.6Nm
4 Screw type terminal Combi – Typ. Recommended tightening torque 0.5 to 0.6Nm
0.5mm2 – 4.0mm2 [AWG 20 – AWG 10]
Aluminium (chassis) and Zinc-plated steel (cover)
E x a m p le T S P C u n it# 2
-
+
T S P C D C M M o d u le
( T y p . L a b e l)
- - + +
- +
N
L
http://www.tracopower.com
N
+
+
LO AD
- +
L
Rev:1.1/ 2811
Safety Instructions:
Before installation read these instructions carefully and completely. This installation instruction cannot account for every
possible condition of installation, operation or maintenance.
Further information can be obtained from your local distributor
office or from the product datasheet, which can be
downloaded from our website:
http://www.tracopower.com/products/tspc.pdf.
This isolation module is constructed in accordance with the
safety requirements of IEC/EN/UL 60950-1, EN 60204, EN
50178, UL508, IEC/EN/UL 60079-15 (protection type “n”
Class I, Zone 2, AEx nA IIC T4 Gc and Class I, Division 2,
Group A,B,C,D), EN 61558-2-7 and IEC62103. They are
approved to UL and cUL approved in accordance to UL508
(Listed) & UL 60079-15 via CSA. They fulfil the
requirements of the Low Voltage Directive (LVD) as well as
the ATEX Directive.
Before any installation, maintenance or modification work
ensure that the main switch is switched off and prevented
from being switched on again. Non-observance, touching
of any live components or improper handling of this power
supply can result in death, severe personal injury or
substantial property damage. Proper and safe operation is
dependent on proper storage, handling, installation and
operation.
Compliance with the relevant national regulations (in the
USA, Europe and other countries) must be ensured.
Before operation is started the following conditions must
be ensured:
Connection to power supply in compliance with national
regulations (e.g. VDE0100 and EN50178).
By use of stranded wires, all strands must be fastened
in the terminal blocks. (Potential danger of contact with
the case)
All output wires must be rated for the TSPC-DCM600
output current and must be connected with the correct
polarity.
Sufficient cooling must be ensured.
Never work on the TSPC-DCM600 if power is supplied!
Risk of electric arcs and electrical shock, severe personal
injury or substantial property damage.
Warning: Hazardous voltages and components storing a
very substantial amount of energy will be connected to this
device during normal operating conditions. However, these
are inaccessible. Improper handling may result in an
electric shock or serious burns! Do not open the TSPCDCM600 until at least 5 minutes after it has been
disconnected from the power supply units on all
poles.
Only trained personnel may open the TSPC-DCM600.
Do not introduce any objects into the TSPC-DCM600.
Keep away from fire and water
http://www.tracopower.com
Installation Instructions:
This TSPC-DCM600 is designed for professional indoor
systems. In operation the TSPC-DCM600 must not be
accessible. It may be installed and put into service by
qualified personnel only.
The correct mounting position for optimal cooling
performance must be observed. Do not cover any
ventilation holes. Leave a free space of minimum 50mm
(2in.) above and below the power supplies and isolation
module.
To comply with the ATEX directive following installation
instructions have to be observed.
1.
The Series TSPC power supply units and the TSPCDCM600 module must be installed in Switch cabinets or
protective housing that meet the requirements of EN
60079-15 or if applicable EN 60079-0 (housing protection
type min. IP54)
2.
The permissible ambient temperature range is -20°C to
+70°C [-4°F to 158°F]. Observe load derating above an
operating temperature of +40°C [104°F] and at a use at
Vin = 85Vac – 100Vac.
3.
For installation in switch cabinets or in protective
housings, it must be ensured that the stipulated
maximum temperatures (Ta) are not exceeded on the
TSPC-DCM600.
4.
When assembling and maintenance of the power supply
pluggable terminals its always must be completely
pushed in. In particular the snap-in locking devices at the
pluggable terminals are to be examined for correct
locking. Terminals with defective snap-in locking devices
may not be used.
5.
The power supply units are Unit Group II Category 3G
components (ex components) as defined by RL 94/9/EG
(ATEX 95) Appendix I. A separate conformity on the endequipment which contains these components evaluation
process must be performed.
6. For use / Installation also the requirements defined in
EN60079-14 must be observed.
Recycling: The unit contains elements that are suitable for
recycling, and components that need special disposal. You
are therefore requested to make sure that the TSPCDCM600 will be recycled environment friendly at the end of
its service life.
Rev:1.1/ 2811