INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS
TSP-3P Series
Order Code
TSP 240-124-3PAC400
TSP 480-124-3PAC400
Industrial
AC-Input
Output Boost
Output Nominal
Voltage Range Power max.
Output Boost for
5 Seconds
480 Watt
24.0Vdc / 10.0A
24.0Vdc / 20.0A
960 Watt
24.0Vdc / 20.0A
24.0Vdc / 40.0A
1920 Watt
24.0Vdc / 40.0A
24.0Vdc / 80.0A
480 Watt
24.0Vdc / 10.0A
24.0Vdc / 20.0A
960 Watt
24.0Vdc / 20.0A
24.0Vdc / 40.0A
1920 Watt
24.0Vdc / 40.0A
24.0Vdc / 80.0A
360Vac – 440Vac
47 – 63Hz
TSP 960-124-3PAC400
TSP 240-124-3PAC500
TSP 480-124-3PAC500
Power Supply
450Vac – 550Vac
TSP 960-124-3PAC500
47 – 63Hz
recommended
Circuit
breaker / fuse
6A
(Characteristic B
Order Code
Input Current
Order Code
Power Consumption
¾ TSP 240-124-3PAC400
0.50A typ Nominal Voltage
¾ TSP 240-124-3PAC400
19 Watt typ Nominal Voltage
¾ TSP 480-124-3PAC400
1.00A typ Nominal Voltage
¾ TSP 480-124-3PAC400
34 Watt typ Nominal Voltage
¾ TSP 960-124-3PAC400
1.88A typ Nominal Voltage
¾ TSP 960-124-3PAC400
68 Watt typ Nominal Voltage
¾ TSP 240-124-3PAC500
0.40A typ Nominal Voltage
¾ TSP 240-124-3PAC500
18 Watt typ Nominal Voltage
¾ TSP 480-124-3PAC500
0.77A typ Nominal Voltage
¾ TSP 480-124-3PAC500
32 Watt typ Nominal Voltage
¾ TSP 960-124-3PAC500
1.50A typ Nominal Voltage
¾ TSP 960-124-3PAC500
65 Watt typ Nominal Voltage
Operating temperature range: -25°C – +70°C max
Natural Air Convection Cooling -13°F – +158°F max
Output Power Derating:
above +55°C Î2.5%/K (6.0W/°C)
above 131°F Î1.4%/°F (3.35 W/°F)
above +55°C Î2.5%/K (12.0 W/°C)
above 131°F Î1.4%/°F (6.7 W/°F)
above +55°C Î2.5%/K (24.0 W/°C)
above 131°F Î1.4%/°F (13.4 W/°F)
Output Power Derating:
330Vac Î 360Vac Iout max = 100% Nominal
410Vac Î 430Vac Iout max = 50% Nominal
430Vac Î 450Vac Iout max = 100% Nominal
Î TSP240-124-3PAC400/TSP240-124-3PAC500
Î TSP240-124-3PAC400/TSP240-124-3PAC500
Î TSP480-124-3PAC400/TSP480-124-3PAC500
Î TSP480-124-3PAC400/TSP480-124-3PAC500
Î TSP960-124-3PAC400/TSP960-124-3PAC500
Î TSP960-124-3PAC400/TSP960-124-3PAC500
Storage temperature range:
-25°C – +85°C max
-13°F – +185°F max
Power Back Immunity
35Vdc continuous and 40Vdc for 1second max.
Over Voltage Protection in
single fault condition:
Typ 30Vdc Î 33Vdc
Connections:
AC Input:
Screw type terminal COMBI
Recommended tightening torque 0.5 to 0.6Nm.
DC Output:
Screw type terminal COMBI
Recommended tightening torque 0.5 to 0.6Nm.
Output Signal: Screw type terminal COMBI
Recommended tightening torque 0.5 to 0.6Nm.
Case material:
http://www.tracopower.com
Aluminium (chassis) and Zinc-plated steel (cover)
Rev: 1.2 / 5010
Safety Instructions:
¾ Before ins tallation read these ins tructions carefully and
completely. This ins tallation i nstruction cannot accou nt
for e very possible cond ition o f installation, o peration or
maintenance. Further information can be obtained from
your local distributor office or from the product datasheet,
which can be down loaded from ou
r website:
http://www.tracopower.com/products/tsp3p.pdf.
¾ These pow er s upplies are c onstructed in accor dance
with the safety r equirements o f IEC /EN/UL 60 950-1,
UL508, EN 60
204, EN
50178, EN 61558-2-8,
CSA22.2-60950-1 and CSA22.2-107. They are approved (BG-mark) in accordance with EN 60 950-1, EN
50178, EN 60204 and fulfil the requirements of the Low
Voltage D irective (L VD). They w ill be UL an d cUL
approved in accordance to UL60950-1 (recognised) and
UL508 (listed) (Approvals pending).
¾ Before an y installation, ma intenance or mod ification
work en sure that t he m ain swit ch i s swi tched of f and
prevented fro m be ing sw itched o n aga in.
Non-observance, touch ing of an y live components or
improper handling o f th is power supply ca n result i n
death, sev ere personal in jury or sub stantial pro perty
damage. Prop er and safe op eration is de pendent on
proper storage, handling, installation and operation.
¾ Compliance with the relevant national regulations (in the
USA, Europe and other countries) must be ensured. Before operation is started the following conditions must be
ensured:
™ Connection to mains supply in compliance with national regulations (e.g. VDE0100 and EN50178).
™ By use of st randed wi res, all stra nds must be fastened i n th e te rminal blocks. (Potential da nger o f
contact with the case)
™ Power supply and mains cables must be sufficiently
fused.
™ Degree o f protection = 1 according to IEC5 36. The
non-fused protective earth connection must be connected to the FG terminal (Protection Class I).
™ All output wires must be rated for the power supply
output current and must be c onnected with the correct polarity.
™ All output terminals have to be used
™ Sufficient cooling must be ensured.
¾ Never work on the power supply if power is supplied! Ri sk of electric a rcs an d el ectrical shock, wh ich
can caus e death, se vere pers onal injury or s ubstantial
property damage.
¾ Warning: Hazardous voltages and components storing
a very substantial amount of energy are present in this
power supply during normal operating conditions. However, these are inaccessible. Improper handling may result in an electric shock or serious burns! Do not open
the power supply until at least 5 minutes after it has
been disconnected from the mains on all poles.
™ Only trained personnel may open the power supply.
™ Do not introduce any objects into the power supply.
The ou tput voltage adjustment po tentiometer may
only be actuated using an insulated screwdriver.
™ Keep away from fire and water
http://www.tracopower.com
Installation Instructions:
¾ This p ower sup ply is designed for profe ssional
indoor systems. In operat ion the powe r supply must
not be accessible. It may be inst alled and put into
service by qualified personnel only.
¾ Do not op erate without PE conne ction! T o comply
with EMC and safety standards (CE mark, approval s)
the power supply must be operated only if PE terminal is connected to the non-fused earth conductor.
¾ The co rrect mountin g position for optimal coolin g
performance must be ob served. Do not cover any
ventilation holes. Leave a free sp ace of minimum
80mm (3in.) above and below the power supply. Observe power derating.
¾ The inte rnal f uses a re n ot acce ssible, a s it may not
be repl aced by the user . If any of this internal fuse
has blown, the po wer su pply ha s mo st pro perly an
internal defe ct and, for safety rea sons, mu st be
shipped to the local dist ributor. In case this internal
fuse has to be replaced in the field, replace only with
same type and rating of fuse for continued protection
against risk of fire.
¾ To comply with the ATEX directive (Ex nAC IIC T3) the
following installation instructions have to be observed.
1.
The Series TSP-3PAC power supply units can be
installed in Switch cabinets or protective housing that
meet the requirements of EN 60079-15 or if applicable
EN 60079-0 (housing protection type min. IP54)
2.
The permissible ambient temperature range is -25°C to
+70°C [-4°F to 158°F]. Observe load derating above an
Operating temperature of +55°C [-131°F]. and at a use at
Vin = 320Vac – 550Vac.
3.
For installation in switch cabinets or in protective
housings, it must be ensured that the stipulated
maximum temperatures (Ta) are not exceeded on these
power supplies.
4.
The power supply units are Unit Group II Category 3G
components (ex components) as defined by RL 94/9/EG
(ATEX 95) Appendix I. A separate conformity on the
end-equipment which contains these components
evaluation process must be performed.
5.
For use / Installation also the requirements defined in
EN60079-14 must be observed.
¾ Recycling: The unit contains elements that are suit able for recycling, and components that need special
disposal. You are th erefore re quested t o ma ke sure
that the power su pply will be recy cled environm ent
friendly at the end of its service life.
Rev: 1.2 / 5010