INSTALLATION INSTRUCTIONS TSP BCMU360 Battery Controller

INSTALLATION INSTRUCTIONS
TSP BCMU360
Battery Controller
Output Current
Mode
*
Iout Nominal @ 24V
Iout Nominal @ 48V
Iout Boost @ 24V
Iout Boost @ 48V
Normal
15A
7.5A
-
-
Buffer
10A*
5A*
15A**
7.5A***
Observe output current de-rating: 2%/°C (Between +50°C and +60°C for 24V operation or between +40°C and +60°C for 48V operation)
**
Ambient temperature up to +40°C for max. 10 minutes.
***
Ambient temperature up to +40°C for max. 3 minutes.
Parameter
Condition
Settings
24V
48V
Output Voltage [V]
Normal Mode
Vin- (0.4…0.8)
Vin- (0.4…0.7)
Output Voltage [V]
Buffer Mode
22.2…22.6
44.6…45.2
Electrical Connections
& Wire Size
Battery Charging Current [A]
Nominal Battery Voltage [V]
Battery Adjustment Range [V]
Battery Resistance Test [mΩ]
Battery Test Current [A]
Battery Test Interval [s]
Battery Warning Voltage [V]
Battery Disconnection Voltage [V]
Thermal Protection
Automatic Battery Temperature
Compensation Range
Input & Output
Battery Input
Tightening Torque
Normal Mode
25°C Ambient
Normal Mode
Normal Mode
Normal Mode
Normal Mode
Buffer Mode
Buffer Mode
Buffer Mode
Normal Mode
Battery Remote ON/OFF
Buffer Mode
Signal Relay Contact Rating
Input DC Monitoring
User Settings:
2
2
2-10 mm [AWG14-AWG7]
1-10 mm [AWG17-AWG7]
(Max. resistance 20mΩ)
(Max. resistance 40mΩ)
2
4-10 mm [AWG11-AWG7]
(Max. resistance 10mΩ )
1.76Nm
0.8…1.2
13.6 (Factory Set)
13.0…14.4
100 (max)
2.5A for 60ms (typ)
15s (Jumper A fitted: Fig.1 )
8..10mins (Jumper A not fitted: Fig.1)
10.4...11.4
9.1…9.7
100°C (at back of chassis)
-15°C…50°C (external sensor temp. Fig.2)
Switch 5V/5mA (min) to GND (Fig.2)
Level: 0…1.5V
30VDC 1.0A
(Fig.2)
60VDC 0.5A
(Fig.2)
Figure 1:
C B A
PCB
J6
A: Battery Test Period 10 min (not fitted, default); 15 sec (fitted)
B: Output Voltage Settings 48V (not fitted); 24V (fitted, default)
C: Not in use (spare jumper fitted)
Chassis
J6 Link
Signal Connector:
Connector
Figure 2:
Temp.Sensor: Connect optional external sensor for automatic end of
Temp. Battery
DC-IN
charge battery compensation. (Traco Power P/N: TSP-TC)
DC OK Bat OK
Sensor Remote
OK
ON/OFF
Battery Remote ON/OFF: Enables remote disconnection of the
battery in buffer mode.
DC OK: Closed contact indicate that the output voltage is higher
than 85-90% of the nominal output voltage.
BAT OK: Closed contact indicates that the battery is charged and
has low resistance. During battery operation, it indicates that the battery
is approaching disconnection point.
DC-IN-OK: Closed contact indicates that at least one of the inputs is present and has voltage within +20 / -3% tolerance.
Remark: Apply torque 0.19Nm for all contacts.
http://www.tracopower.com
Rev:0.2 / 3414
Safety Instructions:
 Before installation read these instructions carefully and completely. This installation instruction cannot account for every
possible condition of installation, operation or maintenance.
Further information can be obtained from your local distributor
office or from the product datasheet, which can be
downloaded from our website:
www.tracopower.com/products/tsp-bcmu.pdf
 Before any installation, maintenance or modification work
ensure that the main switch is switched off and prevented
from being switched on again. Non-observance, touching of
any live components or improper handling of this power
supply can result in death, severe personal injury or
substantial property damage. Proper and safe operation is
dependent on proper storage, handling, installation and
operation.
 Compliance with the relevant national regulations (in the USA,
Europe and other countries) must be ensured. Before
operation is started the following conditions must be ensured:
 By use of stranded wires, all strands must be fastened in
the terminal blocks. (Potential danger of contact with the
case)
 Power supply and mains cables must be sufficiently fused.
 All output wires must be rated for the equipment output
current and must be connected with the correct polarity.
 Sufficient cooling must be ensured.
Installation Instructions:
 This equipment is designed for professional indoor
systems. In operation the equipment must not be
accessible. It may be installed and put into service by
qualified personnel only.
 The correct mounting position for optimal cooling
performance must be observed. Do not cover any
ventilation holes. Leave a free space of minimum 80mm
(3.15in.) above and below the power supply and on each
side of the power supply a minimum space of 25mm
[0.98in] which allows air convection. Observe power
derating.
 Recycling: The unit contains elements that are suitable for
recycling, and components that need special disposal. You
are therefore requested to make sure that the power
supply will be recycled environment friendly at the end of
its service life.
 Never work on the equipment if power is supplied! Risk of
electric arcs and electrical shock, which can cause death,
severe personal injury or substantial property damage.
 Warning: Hazardous voltages and components storing a very
substantial amount of energy are present in this power supply
during normal operating conditions. However, these are
inaccessible. Improper handling may result in an electric
shock or serious burns! Do not open the equipment until at
least 5 minutes after it has been disconnected from the
power supply on all poles.
 Only trained personnel may open the equipment.
 Do not introduce any objects into the equipment.
 Adjustment potentiometer(s) may only be actuated using
an insulated screwdriver.
 Keep away from fire and water
http://www.tracopower.com