Specifications

AC/DC Power Modules
TMM 60 Series, 60 Watt
CB
Scheme
Features
◆ Fully encapsulated low profile plastic
UL 508
UL 60950-1
ES 60601-1
UL 60950-1
UL 60601-1
casing in PCB- or chassis mount version
◆ 2 x MOPP Medical safety according to
AAMI/ANSI ES 60601-1:2005(R) and
IEC/EN 60601-1 3rd edition
◆ IT and industrial safety according to
IEC/UL 60950-1 and UL 508
◆ Ready to meet ErP directive
<0.5 W no load power consumption
◆ -40°C start-up temperature
◆ Safety class II prepared
◆ Protection against over-temperature
overload and short circuit
◆ 3-year product warranty
Also see:
TMM 24 Series, 24 Watt
www.tracopower.com/products/tmm24.pdf
TMM 40 Series, 40 Watt
www.tracopower.com/products/tmm40.pdf
The TMM 60 Series of fully encapsulated 60 Watt AC/DC power supply modules feature a reinforced/double I/O isolation system according to latest medical
safety standards 60601-3 3rd edition for 2 x MOPP (Means Of Patient Protection). The high efficiency and the use of highest grade components make the units
suitable for an operating temperature range of –40°C to +60°C while it goes up
to 75°C with 50% load derating. EMI/EMC characteristics and the safety approval package qualify these modules not only for medical devices but also for
demanding applications in transportation systems and for equipment in industrial
an commercial environment.
Models
Order code
Output power max.
Output
Efficiency
PCB mount
Chassis mount
TMM 60105
TMM 60105C
5.1 VDC / 10000 mA
84 %
TMM 60112
TMM 60112C
12 VDC / 5000 mA
87 %
TMM 60115
TMM 60115C
15 VDC / 4000 mA
87 %
60 W
TMM 60124
TMM 60124C
24 VDC / 2500 mA
87 %
TMM 60148
TMM 60148C
48 VDC / 1250 mA
88 %
http://www.tracopower.com
Page 1 of 5
AC/DC Power Modules
TMM 60 Series
60 Watt
Input Specifications
Input voltage ranges
– nominal 100 – 240 VAC
– AC input 85 – 264 VAC
– DC Input 120 – 370 VDC
Input frequency 47 – 440 Hz
Input current at full load (115 VAC / 230 VAC nominal input)
5.1 VDC model: 860 mA / 515 mA typ.
other models: 1000 mA / 600 mA typ
Leakage current 80 µA typ.
No-Load power consumption <0.5 W
External input fuse required (recommended value) 3 A slow blow type or characteristic C
Output Specifications
Voltage set accuracy ±1% typ. / 2.0 % max.
Minimum load no minimum load required
Regulation – Input variation 0.2% typ. / 1.0 % max.
– Load variation (0-100%)
: 0.5% typ. / 1.0 % max.
Temperature coefficient 0.02 %/K
Ripple and noise (20 MHz bandwidth)
(measured with capacitor 0.1µF/50V MLCC and 1µ/50V e-cap) 5.1 VDC model: 3% of Vout [Vp-p] max.
other models: 1.5% of Vout [Vp-p] max.
Current limitation above 105 % of rated output current.
hiccup, auto recovery
Overvoltage protection by Zehner diode (main output only) 120 % of Vout typ.
Short circuit protection continous
Max. capacitive load
5.1
12
15
24
48
VDC
VDC
VDC
VDC
VDC
model:
model:
model:
model:
model:
8000 µF
3900 µF
3300 µF
1500 µF
680 µF
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com
Page 2 of 5
AC/DC Power Modules
TMM 60 Series
60 Watt
General Specifications
Temperature ranges
– Operating (natural convection cooling 20 LFM) –40°C to +75°C
– Power derating above +60°C 3.75 %/K
– Storage (non operating) –40°C to +95°C
Humidity (non condensing) 95 % rel max.
Altitude during operation 5000 m
Switching frequency (pulse width modulation PWM) 100 kHz typ.
Hold-up time
115 VAC: 20 ms typ.
230 VAC: 80 ms typ.
Isolation voltage
– Input/Output 4‘000 VAC
Isolation resistance
– at 500 VDC 1‘000 MOhm
Reliability /calculated MTBF (MIL-HDBK-217F, at +25°C, ground benign) >125’000 h
EMI / RFI conducted and radiated EN 55022, class B, FCC part 15, level B
EN 55011 class B
Electromagnets compatibility – Electrostatic discharge ESD (EMC), immunity – RF field immunity – Electrical fast transients/burst immunity – Surge
– Conducted RF – Magnetic field immunity
IEC / EN 61000-4-2, 8kV/4kV perf. criteria A
IEC / EN 61000-4-3, 10V/m perf. criteria A
IEC / EN 61000-4-4, ±2kV perf. criteria A
IEC / EN 61000-4-5, ±1kV perf. criteria A
IEC / EN 61000-4-6, 10 Vr.m.s perf. criteria A
IEC / EN 61000-4-8, 30A/m perf. criteria A
Voltage dip and interruptions according to EN 61000-4-11
30%, 10ms perf. criteria A
reference: 115 VAC / 60Hz 60%, 100ms perf. criteria A
95%, 5000ms perf. criteria B
Protection class II according IEC/EN 60536
Safety standards UL 60950-1, IEC/EN 60950-1,
IEC/EN 60601-1 3rd edition, 2 x MOPP
ANSI/AAMI ES60601-1:2005(R)2012
UL 508 for chassis mount version
– Certification documents
www.tracopower.com/overview/tmm60
Casing material plastic resin (UL 94V-0 rated)
Environmental compliance – Reach www.tracopower.com/overview/tmm60
– RoHS RoHS directive 2011/65/EU
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com
Page 3 of 5
AC/DC Power Modules
TMM 60 Series
60 Watt
DIN-Rail Mounting Kit
Adapter for mounting on DIN-rails as per EN 50022-35 (snap-on mounting)
DIN-Rail Mounting Kit
Order code
For models
TMP-MK2
TMM 60xxxC
Kit contains interface plate, DIN-rail clip and necessary screws.
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com
Page 4 of 5
AC/DC Power Modules
TMM 60 Series
60 Watt
Outline Dimensions
TMM 60:
for PCB mount:
67.5 (2.66)
12.70
12.70
(0.50)
(0.50)
36.45 (1.44)
88.9 (3.50)
2 x M4 THD
Bottom view
81.3 (3.20)
4
17.0 (0.67)
6
34.2 (1.35)
3.85
17.5
(0.70)
27.94 (1.10)
(0.15)
1
2
0.7 (0.03)
6.0
(0.24)
27.94 (1.10)
33.75 (1.33)
Weight: 360 g (12.70oz)
Pin diameter ø 1.0 mm (0.039)
TMM 60C:
for chassis mount:
67.8 (2.67)
38.0 (1.50)
50.0 (1.97)
3
4
5
6
8.9
5.0
11.8
(0.35)
(0.20)
(0.46)
Pinout / Connection
7
4 x ø3.5
90.0 (3.54)
Single
1
AC (N)
2
AC (L)
3
No Pin / NC
4
+Vout
5
No Pin / NC
6
-Vout
7
No Pin / NC
NC = not to connect
11.0
Weight: 380 g (13.4oz)
(0.43)
6.0
2
(0.24)
1
112.0 (4.41)
Top view
100.0 (3.94)
Indication LED
Pin/con.
Dimensions in[mm], () = Inches
Tolerances = ±1.0 mm (0.04)
Pin diameter ø ±0.1 mm (0.004)
Specifications can be changed without notice! Make sure you are using the latest documentation, downloadable at www.tracopower.com
www.tracopower.com
http://www.tracopower.com
Rev. April 20. 2015
Page 5 of 5