PR-Line – PDF 164 KB

PR - PCB relay
the PR-PCB relay
PCB-Relay from the PR family are small
relays. The version has forced guided
contacts, 2 normally open contacts, 2
normally closed contacts.
In the industrial electronic as well as in
the control industry they are used as
fail-save elements.
The forced guided contact version are
often used in control systems of high
safe applications.
features
applications
•
•
•
•
•
•
• devices of automation and control
simple fail-save construction
high switching power
high load current
extraordinary life time
high contact force
security distance according to VDE
and CSA
• minimal dimensions
• the forced guided contact version,
SUVA approved.
42
catalog 2002 e / 04.03
By using best materials and because of
the simple construction the highest failsecurity was achieved.
High precision in mechanical and electrical control guarantees the high and
stable quality of the relays.
type number key
PR 4 ... 024 VDC
coil voltage
VDC = direct current
standard voltage
VDC: 024, 110
option
F = flat version
H = tall version
relay version
PR 4 (forced guided contacts)
order sample
PR 4 F 024 VDC
- PCB-relay with forced guided
contacts
- flat version
- coil voltage 24 VDC
catalog 2002 e / 04.03
43
PR 4F - PCB relay
PCB-relay with forced guided contacts, flat
version with 2 normally open contacts,
and 2 normally closed contacts
order numbers
serial version
PR 4F .. VDC
contact specifications
(see data sheet for curves)
contact material
contact type
nominal switching capacity
electric life expectancy
AgCuNi
single contact
250 VAC 6 A AC1 1500 VA
app. 100'000 operations
250 VAC 6A AC1 (360 Schaltung/h)
15 A for 200 ms
50 mA to 6A
0,3VA to 1500VA
inrush current
switching current range
switching power range
general data
mechanic life expectancy
mechanical switching frequency
pull-in time
release time
bounce time normally open contact
bounce time break contact
test voltage, coil/contact
test voltage, open contact
insulation resistance
weight
installation situation
ambient temperature
> 20 x 106 operations
20 Hz
10 ms
2,5 ms
6 ms
6 ms
2'000 Veff / 50 Hz
1'500 Veff
2x1011 Ohm
30 g
any
max. +60 °C
tests, instructions
certificates
44
catalog 2002 e / 04.03
CSA, VDE, SUVA
45,1
7x2,54
circuit diagram (view from the top)
5,08
ø 1,3 mm ± 0,1
3,0
27,9
36,4
2,5
20,3
drilling plan (view on solder side)
dimensions
3,0 12,2
36,4
45,1
1x0,2
5,08
2,5
7x2,54
20,3
27,9
3,0
coil specifications
standard coils for direct current (other voltages on enquiry)
rated
voltage
VDC
pull-in
voltage
at 20 °C
reset
voltage
at 20 °C
nominal
current
mA
resistance
Ohm
at 20 °C
tolerance
%
6
5,1
≥ 0,3
222
27
+/-10
12
10,2
≥ 0,6
109
110
+/-10
24
20,4
≥ 1,2
54,5
440
+/-10
48
40,8
≥ 2,4
30
1'600
+/-10
110
93,5
≥ 5,5
10,3
10'600
+/-13
catalog 2002 e / 04.03
45
PR 4H - PCB relay
PCB-relay with forced guided contacts, tall
version with 2 normally open contacts,
and 2 normally closed contacts
order numbers
serial version
PR4H .. VDC
contact specifications
(see data sheet for curves)
contact material
contact type
nominal switching capacity
electric life expectancy
AgCuNi
single contact
250 VAC 6 A AC1 1500 VA
app. 100'000 operations
250 VAC 6A AC1 (360 operations/h)
15 A for 200 ms
50 mA to 6A
0,3VA to 1500VA
inrush current max.
switching current range
switching power range
general data
mechanic life expectancy
mechanical switching frequency
pull-in time
release time
bounce time normally open contact
bounce time break contact
test voltage, coil/contact
test voltage, open contact
insulation resistance
weight
installation situation
ambient temperature
> 20 x 106 operations
20 Hz
10 ms
2,5 ms
6 ms
6 ms
2'000 Veff / 50 Hz
1'500 Veff
2x1011 Ohm
30 g
any
max. +60 °C
tests, instructions
certificates
46
catalog 2002 e / 04.03
CSA, VDE, SUVA
7,62
13,3
ø 1,3 mm ± 0,1
7x2,54
2,9
2,9
20,3
45,5
circuit diagram (view from the top)
drilling plan (view on solder side)
3,0
36,1
dimensions
1x0,2
2,9
20,3
7x2,54
45,5
2,9
7,62
13,3
coil specifications
standard coils for direct current (other voltages on enquiry)
rated
voltage
VDC
min. pull-in
voltage
at 20 °C
release
voltage
at 20 °C
nominal
current
mA
resistance
Ohm
at 20 °C
tolerance
%
6
5,1
≥ 0,3
222
27
+/-10
12
10,2
≥ 0,6
109
110
+/-10
24
20,4
≥ 1,2
54,5
440
+/-10
48
40,8
≥ 2,4
30
1'600
+/-10
110
93,5
≥ 5,5
10,3
10'600
+/-13
contact specifications (AgCuNi 6A single contact)
data valid for relay
current (A)
DC breaking capacity
10
8
6
4
3
contact material
contact type
nominal switching capacity
electric life expectancy
2
2
1
1
0,8
0,6
0,4
0,3
0,2
0,1
0
50
100
voltage (VDC)
150
200
250
inrush current max.
switching current range*
switching power range*
contact resistance
PR 4F
PR 4H
AgCuNi (AgCu1,8Ni0,12)
single contact
250VAC 6A AC1 1500VA
app. 100'000 operations
250 VAC 6A AC1 (360 operations/h)
15A for 200 ms
50mA to 6A
0,3VA(W) to 1500VA(W)
≤ 120mΩ in the new condition
*typical values
1) inductive load, L/R 40 ms
2) resitive load
catalog 2002 e / 04.03
47