1 miniature industrial relays

RY2
miniature industrial relays
•Relays of general application
•For plug-in sockets: 35 mm rail mount acc. to PN-EN 60715;
on panel mounting
•For direct mounting on panel - cover with mounting flange
• Flat insert connectors - faston 187 (4,8 x 0,5 mm)
• Recognitions, certifications, directives: RoHS,
Contact data
Number and type of contacts
Contact material
Rated / max. switching voltage
AC
Min. switching voltage
Rated load AC1
DC1
Min. switching current
Max. inrush current
Rated current
Max. breaking capacity
AC1
Min. breaking capacity
Contact resistance
Max. operating frequency
• at rated load
AC1
• no load
2 CO
AgNi, AgCdO
250 V / 440 V
5 V AgNi, 10 V AgCdO
12 A / 250 V AC
12 A / 30 V DC
5 mA AgNi, 10 mA AgCdO
20 A
12 A
3 000 VA
0,3 W AgNi, 1 W AgCdO
 100 m
Rated voltage
50/60 Hz, 50 Hz AC
DC
Must release voltage
Operating range of supply voltage
Rated power consumption
AC
DC
6 ... 240 V
5 ... 220 V
AC:  0,2 Un DC:  0,1 Un
see Tables 1, 2, 3
1,6 VA
0,9 W
Insulation rated voltage
Rated surge voltage
Overvoltage category
Insulation pollution degree
Dielectric strength
• between coil and contacts
• contact clearance
• pole - pole
Contact - coil distance
• clearance
• creepage
250 V AC
4 000 V 1,2 / 50 µs
III
3
Operating / release time (typical values)
Electrical life
• resistive AC1
• cos
Mechanical life (cycles)
Dimensions (L x W x H)
Weight
Ambient temperature
• storage
• operating
Cover protection category
Shock resistance
Vibration resistance
15 ms / 10 ms
Coil data
Insulation according to PN-EN 60664-1
General data
1 200 cycles/hour
18 000 cycles/hour
2 500 V AC
1 000 V AC
2 500 V AC
type of insulation: basic
type of clearance: micro-disconnection
type of insulation: basic
 2,6 mm
 4 mm
> 105 12 A, 250 V AC
see Fig. 2
> 107
27,5 x 21,1 x 34,5 mm ❶
35 g
-40...+70 oC
-40...+55 oC
IP 40
PN-EN 60529
10 g
5 g 15...150 Hz
28.01.2014
The data in bold type pertain to the standard versions of the relays.
❶ For plug-in sockets version: standard
1
Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
www.relpol.com.pl
RY2
miniature industrial relays
Coil data - DC voltage version
Rated voltage
V DC
Coil resistance
at 20 °C

Acceptable
resistance
Coil operating range
V DC
min. (at 20 °C)
max. (at 55 °C)
1005
5
28
± 10%
4,0
1006
6
40
± 10%
4,8
5,5
6,6
1012
12
160
± 10%
9,6
13,2
1024
24
640
± 10%
19,2
26,4
1048
48
2 600
± 10%
38,4
52,8
1060
60
4 000
± 10%
48,0
66,0
1080
80
7 100
± 10%
64,0
88,0
1110
110
13 600
± 10%
88,0
121,0
1125
125
16 000
± 10%
100,0
137,5
1220
220
54 000
± 10%
176,0
242,0
Coil data - AC 50/60 Hz voltage version, basic
Coil code
Rated voltage
V AC
Table 2
Coil resistance
at 20 °C

Acceptable
resistance
Coil operating range
V AC
min. (at 20 °C)
max. (at 55 °C)
5006
6
9,8
± 10%
4,8
6,6
5012
12
39,5
± 10%
9,6
13,2
5024
24
158
± 10%
19,2
26,4
5042
42
470
± 10%
33,6
46,2
5048
48
640
± 10%
38,4
52,8
5060
60
930
± 10%
48,0
66,0
5080
80
1 720
± 10%
64,0
88,0
5110
110
3 450
± 10%
88,0
121,0
5120
120
3 770
± 10%
96,0
132,0
5127
127
4 000
± 10%
101,6
139,7
5220
220
15 400
± 10%
176,0
242,0
5230
230
16 100
± 10%
184,0
253,0
5240
240
16 800
± 10%
192,0
264,0
Coil data - AC 50 Hz voltage version, special
Coil code
Rated voltage
V AC
3006
6
3012
3024
Table 3
Coil resistance
at 20 °C

Acceptable
resistance
5
± 10%
12
50
24
190
3036
36
3042
Coil operating range
V AC
min. (at 20 °C)
max. (at 55 °C)
4,8
6,6
± 10%
9,6
13,2
± 10%
19,2
26,4
400
± 10%
28,8
39,6
42
565
± 10%
33,6
46,2
3048
48
785
± 10%
38,4
52,8
3060
60
1 240
± 10%
48,0
66,0
3080
80
2 190
± 10%
64,0
88,0
3110
110
3 880
± 10%
88,0
121,0
3120
120
4 150
± 10%
96,0
132,0
3127
127
4 940
± 10%
102,0
140,0
3220
220
16 300
± 10%
176,0
242,0
3230
230/240
17 400
± 10%
184,0
253,0
28.01.2014
Coil code
Table 1
2
Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
www.relpol.com.pl
RY2
miniature industrial relays
AC1
28.01.2014
N - electrical life
at AC1
2 CO
Note: the indicated polarity of the supply refers to the relays
with extra equipment D - surge suppression element (diode)
- for DC coils only.
3
Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
www.relpol.com.pl
RY2
miniature industrial relays
Mounting
Relays RY2 are offered in versions: • standard, for plug-in sockets • with mounting flange in the upper wall of the cover.
Relays RY2 are designed for: • screw terminals plug-in sockets GZY2G with clips GZY2G-0041 ❶, 35 mm rail mount
acc. to PN-EN 60715 or on panel mounting with two M3 screws • flat insert connectors - faston 187 (4,8 x 0,5 mm),
relays are direct on panel mounting with two M3 screws - cover with mounting flange.
❶ For each GZY2G socket a set of two GZY2G-0041 clips shall be ordered.
Ordering codes
Cover protection
category
Type
Contact
material
Number and type
of contacts
R Y 2 —
Connection
mode
—
Coil code
—
Additional
features
—
Contact material
10 - AgCdO
20 - AgNi
see Tables 1, 2, 3 page 2
Number and type of contacts
12 - 2 CO
Cover protection category
2 - in cover, IP 40 version
4 - in cover with mounting flange, IP 40 version
Connection mode
6 - for flat insert connectors - faston 187 (4,8 x 0,5 mm)
and for plug-in sockets
Additional features ❷
without marks - without additional features
L
- light indicator (LED diode)
D
- surge suppression element (diode)
LD - light indicator (LED diode) + surge suppression element (diode)
❷ D, LD - only for DC coils
Note:
For relays with additional features D - surge suppression element (diode) (versions D and LD) - fixed supply polarity
compulsory for the DC load of coils: +A1(7) / -A2(8). The polarity is indicated on the relay cover. For other versions
of the relays with DC coils any polarity is possible.
RY2-2012-26-1024relay RY2, for plug-in sockets, two changeover contacts, contact material AgNi, coil voltage
24 V DC, in cover IP 40
RY2-2012-26-5230-Lrelay RY2, for plug-in sockets, two changeover contacts, contact material AgNi, coil voltage
230 V AC 50/60 Hz, with light indicator (LED diode), in cover IP 40
RY2-1012-46-3230relay RY2, for flat insert connectors - faston 187 (4,8 x 0,5 mm), two changeover contacts,
contact material AgCdO, coil voltage 230/240 V AC 50 Hz, in cover with mounting flange,
IP 40 version
28.01.2014
Examples of ordering codes:
4
Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
www.relpol.com.pl
Plug-in sockets and accessories
GZY2G
For RY2
Screw terminals
Max. tightening moment
for the terminal: 0,7 Nm
35 mm rail mount
acc. to PN-EN 60715
or on panel mounting
78,7 x 28 x 32,4 mm
Two poles
12 A, 250 V AC
Connection diagram
Dimensions
NC
NO
COM
COIL
Accessories
GZY2G-0041
GZY2G
PRECAUTIONS:
1. Ensure that the parameters of the product described in its specification provide a safety margin for the appropriate operation of the device or system and never use
the product in circumstances which exceed the parameters of the product. 2. Never touch any live parts of the device. 3. Ensure that the product has been connected
correctly. An incorrect connection may cause malfunction, excessive heating or risk of fire. 4. In case of any risk of any serious material loss or death or injuries
of humans or animals, the devices or systems shall be designed so to equip them with double safety system to guarantee their reliable operation.
28.01.2014
Screw terminals
plug-in sockets
for RY2
5
Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
www.relpol.com.pl