RY2 Miniature plug

RY2
Miniature plug-in power relays
107
•
•
•
•
•
•
General purpose relays
Plug-in version - 35 mm DIN rail mount, EN 50022
Panel mounting - faston connections
Accessories: sockets
WT - flag indicator and mechanical latching - option
P type buttons and plugs (no latching) or plugs are available
for relays equipped with WT - page 167
Contacts
Contact number & arrangement
Contact material
Max. switching voltage
Min. switching voltage
Rated load
AC/DC
AC1
DC1
Min. switching current
Max. inrush current
Rated current
Max. breaking capacity
Min. breaking capacity
Resistance
Max. operating frequency
• at rated load
• no load
AC1
AC1
2C/O
AgCdO
250 V / 250 V
10 V
12 A / 250 V AC
12 A / 30 V DC
10 mA
20 A
12 A
3 000 VA
1W
≤ 100 mΩ
1 200 cycles/hour
18 000 cycles/hour
Coil
Rated voltage
50/60 Hz
Must release voltage
Operating range of supply voltage
Rated power consumption
AC
DC
AC
DC
6...240 V
5...220 V
AC: ≥ 0,2 Un DC: ≥ 0,1 Un
see Table 1, 2
1,6 VA
0,9 W
Insulation
Insulation category
Insulation rated voltage
Dielectric strength
• coil - contact
• contact - contact
• pole - pole
Contact - coil distance
• clearance
• creepage
B250
250 V AC
2 500 V AC
1 000 V AC
2 500 V AC
≥ 2,6 mm
≥ 4 mm
General data
Operating time (typical value)
Release time (typical value)
Electrical life
• resistive AC1
• cosφ
Mechanical life (cycles)
Dimensions (L x W x H)
Weight
Ambient temperature
• storing
• operating
Cover protection category
Shock resistance
Vibration resistance
Standard contact material marked with bolt type.
❶ Standard plug-in version (without WT)
❷ Plug-in version (WT)
www.relpol.com.pl
15 ms
10 ms
≥ 105
12 A, 250 V AC
see Fig. 2
≥ 107
27,5 x 21,1 x 34,5 mm ❶
35 g
-40...+70 oC
-40...+55 oC
IP 40
10 g
5 g 15...150 Hz
27,5 x 21,1 x 37 mm ❷
RY2
Miniature plug-in power relays
108
www.relpol.com.pl
RY2
Miniature plug-in power relays
109
P type buttons and plugs and plugs need to ordered saparately.
Exchange of the buttons is done by Customer.
Information on P type buttons and plugs and plugs on page 167.
www.relpol.com.pl
RY2
Miniature plug-in power relays
110
Mounting
RY2 relays are offered in versions: • standard, plug-in version (without WT) • plug-in version with flag indicator
and machanical latching (WT). Customer may exchange T type button with P type button (no latching) or with plug
(no mechanical operation). P type buttons and plugs and plugs need to ordered saparately • with mounting flange
(without WT).
Relays RY2 are designed for: • screw terminals sockets GZY2 with clip GZY 2000, 35 mm DIN rail mount, EN 50022
or on panel mounting • faston connector.
see Table 1, 2 page 108
* D, LD, WTD, WTLD - only for DC coils
P type buttons and plugs and plugs ordered separately for substition of T type button by Customers themselves:
• Button P R4 AC - orange (coils AC)
• Button P R4 DC - green (coils DC)
• Plug R4 AC - orange (coils AC)
• Plug R4 DC - green (coils DC)
Information on P type buttons and plugs and plugs on page 167.
www.relpol.com.pl