BP33-6 - BB

Maintenance-Free Rechargeable Sealed Lead-Acid Battery
BP33-6
The battery is constructed by plates,
separators,safety valves and container.
Since the electrolyte is held by a
glass-mat separator and plates , the
battery can use in any direction and
position without leakage.
PERFORMANCE SPECIFICATIONS
Nominal Voltage(V).............................................................................................................................6 volts(3 cells in series)
Nominal Capacity(AH)
20 hour rate F.V.(1.75V/cell) (1650mA to 5.25volts) ........................................................................................... .....33A.H.
10 hour rate F.V.(1.75V/cell) (3135mA to 5.25volts) ............................................................................................31.35 A.H.
5 hour rate F.V.(1.75V/cell) (5610mA to 5.25volts) ........................................................................................... 28.05 A.H.
1 hour rate F.V.(1.55V/cell) (19800mA to 4.65volts)..............................................................................................19.8A.H.
Approximate Weight........................................................................................................................................6000g.( 13.23lbs.)
Terminal
Standard.......................................................................................................................................................................Type B1
Optional....................................................................................................................................................................Type T2.I1
Internal Resistance (Fully Charged Battery)..................................................................................................................<4.5m
Maximum Discharge Current For 5 sec.(A)........................................................................................................................255A
Maximum Charge Current(A)................................................................................................................................................9.9A
Ambient Temperature
Charge..................................................................................................................................................0oC(32oF)~40oC(104oF)
Discharge...........................................................................................................................................-20oC(-4oF)~50oC(122oF)
Storage...............................................................................................................................................-20oC(-4oF)~40oC(104oF)
Vibration test:
Frequency: 16.7HZ
Amplitude: 4mm
Vibrate the battery horizontally or vertically for 60 minutes. The battery have no abnormality.
Case.......................................................................................................................................................................................ABS
Dimension(mm/inch)
Length
1.5mm........................................................................................................................................181/7.13
Width
1.5mm..........................................................................................................................................76/2.99
Container Height
1.5mm.......................................................................................................................................166/6.54
Total Height
1.5mm.......................................................................................................................................166/6.54
Application........................................................................................................................................................................Lighting.
O
O
BATTERY CHARGING CHARACTERISTICS
BP33-6 Battery discharge characteristics (25 C/77 F)
(Typical example of the charge characteristics for the standby use)
6.50
6.00
140
0.21
7.5
120
0.18
7.0
Charge voltage
3.14A
1.65A
8.25A
5.00
19.8A
4.50
100
80
60
40
4.00
99A
66A
2
3
5
10
0.03
0
0
20
30
60
2
3
5
1 Battery : BP33-6
2 Discharge
100%(0.05CA 20h)
50%(0.05CA 10h)
3 Constant voltage charging
Charge voltage:2.45V/cell
Charge current:0.1CA
4 Temperature 20 OC(68 O F)
6.0
5.5
5.0
10
20
0
30
0
5
10
15
20
25
Charge time (hr)
Hr
Effect of Temperature on Long Term Float Life
10
8
Charging Procedure
Charging time
O
0.1CA, 20 C
(h)
Temperature
Charging
compensation Max. charging
Voltage
current
coefficient of
O
at 20 C
(CA)
voltage
(V/cell) charging
(mV/ OC/cell)
2.25~2.30
-3
100%
discharge
24
0.3
Temp
O
( C)
50%
discharge
6
5
4
Life expectancy(year)
Constant
For standby
voltage &
power Source
Constant
current
charging
For
(with current
cycle service restrication)
0.06
20
Discharge time
Charging
method
0.09
vo lu m e
Charge current
Min
Application
0.12
6.5
33A
3.50
1
0.15
Charge voltage(V)
5.61A
Charge volume(%)
Terminal Voltage(V)
5.50
Charge current(CA)
C ha rg e
20
3
2
1
0~40
O
(32~104 F)
2.40~2.50
-4
0.3
16
Charging voltage :
2.275V/cell
10
0.5
O
20
68
O
*Temperature compensation of charging voltage is not needed, when using the batteries within 5 C to 35 C range.
30
86
50 oC
122 oF
40
104
Battery temperature
OUTER DIMENSIONS
TERMINAL TYPE
mm(inch)
Constant power discharge characteristics at 25 oC/77 oF
5.5( 0.22)
2(0.08)
76 1.5(2.99 0.06)
166 1.5(6.54 0.06)
181 1.5(7.13 0.06)
30Min
1Hr
3Hr
5Hr
10Hr
20Hr
Battery output power(W)
3.4(0.13)
7.85(0.31)
[M5 BOLT & NUT]
Discharge time
Final Voltage
0.8(0.03)
11(0.43)
5(0.20)
12(0.47)
6.35(0.25)
Terminal T2
Terminal B1
5.40V
209.4
120.09
48.09
33.16
18.53
9.69
5.25V
217.3
123.69
49.06
33.66
18.81
9.90
5.10V
222.3
125.91
49.50
33.84
18.90
9.95
4.95V
225.4
127.43
49.84
33.96
18.96
9.97
4.80V
227.7
128.70
50.14
34.06
18.96
9.97
TERMINAL POSITION
UL
R
MH19884
B.B. BATTERY CO., LTD.
Web Site: http://www.bb-battery.com
USA :
B&B BATTERY (USA) INC.
6415 RANDOLPH ST. COMMERCE,
CA, 90040 U.S.A.
TEL: 1-323-278-1900 . 1-800-278-8599
FAX: 1-323-278-1268
CHINA FACTORY:
CHENG DONG TRIAL AREA, HUANG GANG,
RAOPING GUANG DONG, CHINA, 515700
TEL: 86-768-7601001-2
FAX: 86-768-7601469
UK:
JAPAN:
B & B BATTERY (UK) CO., LTD.
TEL: 44-161-339-9458
FAX: 44-161-343-7030
B & B BATTERY(JAPAN) CO., LTD.
TEL: 81-426-256-537
FAX: 81-426-256-537
HONG KONG:
TAIWAN:
NATIONAL TRADING LTD.
B & B BATTERY CO., LTD.
TEL: 852-2301-3800
FAX: 852-2739-1182
TEL: 886-6-5898081~3
FAX: 886-6-5898087
QUALITY ASSURED
FIRM
NATIONAL
ACCREDITATION
OF CERTIFICATION
BODIES
I
S
O
1
4
0
0
1
UKAS
ENVIRONMENTAL
MANAGEMENT