Technical Data Sheet

www.osram.com
QUICKTRONIC® PROFESSIONAL QTP5
for HE lamps
QTP5 1x14-35, QTP5 2x14-35
QUICKTRONIC® PROFESSIONAL QTP5
for HO lamps
QTP5 1x/2x24-39, QTP5 1x/2x49,
QTP5 1x/2x54, QTP5 1x80
Your benefits:
• Dedicated ECG types for HO and
HE lamps in PRO3 technology
• 50,000 hours lifetime*
• Preheat start within 1 second
• Constant light output for
UN = 198 V to 264 V
• Reliable lamp ignition at
ta = −20 °C to +50 °C
• Cut-Off technology
• Suitable for luminaires of PC I and II
• EEI = A2
• Automatic safety shut down at end
of lamp life or in case of failure acc.
to EoL T.2
• Automatic ignition after lamp
replacement
• Suitable for emergency lighting
(DC operation, 0 Hz)
• CW terminal for manual and robotic
wiring
* for t = 75 °C at tc; max. failure rate of 10 %
QUICKTRONIC® PROFESSIONAL QTP5
Reliable longlife ECG for economic lighting.
UN
QTP5 1x…
Product
reference
Product
number
1
1
2
3
4
5
6
7
QTP5 1x…
21
22
23
24
25
26
27
1
2
3
4
5
6
7
QTP5 2x…
21
22
23
24
25
26
27
2
QUICKTRONIC® PROFESSIONAL T5 for HE lamps – single-lamp application
QTP5 1x14-35
4008321061515
1xHE 14
1xHE 21
1xHE 28
1xHE 35
198…264 154…276 40…50 0.08
0.11
0.14
0.18
0.93
0.95
0.96
0.97
16
24
32
39
14
21
28
35
1200
1900
2600
3300
–20…+50 360 30
21
350
20
240
32
46
62
78
2x14
2x21
2x28
2x35
2x1200 –20…+50 423 30
2x1900
2x2600
2x3300
21
415
20
300
QUICKTRONIC® PROFESSIONAL T5 for HE lamps – double-lamp application
QTP5 2x14-35
4008321061539
2xHE 14
2xHE 21
2xHE 28
2xHE 35
198…264 154…276 40…50 0.15
0.21
0.28
0.35
0.98
0.98
0.98
0.99
1
Sinusoidal line voltage
2
As with fluorescent lamps in general, the rated luminous flux for T5 fluorescent lamps is specified at 25 °C.
The maximum luminous flux here however is measured at 34 °C to 38 °C.
cut
off
1
2
3
4
5
6
7
UN
Product
reference
Product
number
1
2
3
4
5
6
7
UN
QTP5 1x…
1
QTP5 1x…
21
22
23
24
25
26
27
QTP5 2x…
21
22
23
24
25
26
27
2
QUICKTRONIC® PROFESSIONAL T5 for HO lamps – single-lamp application
QTP5 1x24-39
4008321123190
QTP5 1x49
QTP5 1x54
QTP5 1x80
4008321061614
4008321061553
4008321061591
1xHO 24
1xHO 39
1xHO 49
1xHO 54
1xHO 80
198…264 154…276 40…50 0.12
0.20
198…264 154…276 40…50 0.24
198…264 154…276 40…50 0.27
198…264 154…276 40…50 0.39
0.96
0.96
0.98
0.98
0.98
27
44
55
61
88
24
39
49
54
80
1750
3100
4300
4450
6150
–20…+50
360 30
21
350 20
240
–20…+50
–20…+50
–20…+50
360 30
360 30
360 30
21
21
21
350 20
350 20
350 20
240
250
270
54
84
110
121
2x24
2x39
2x49
2x54
2x1750 –20…+50
2x3100
2x4300 –20…+50
2x4450 –20…+50
423 30
21
415 20
300
423 30
423 30
21
21
415 20
415 20
380
380
QUICKTRONIC® PROFESSIONAL T5 for HO lamps – double-lamp application
QTP5 2x24-39
4008321123671
QTP5 2x49
QTP5 2x54
4008321123831
4008321061577
2xHO 24 198…264 154…276 40…50
2xHO 39
2xHO 49 198…264 154…276 40…50
2xHO 54 198…264 154…276 40…50
0.22
0.36
0.48
0.53
0.98
0.98
0.98
0.98
1
Sinusoidal line voltage
2
As with fluorescent lamps in general, the rated luminous flux for T5 fluorescent lamps is specified at 25 °C.
The maximum luminous flux here however is measured at 34 °C to 38 °C.
cut
off
OSRAM System+ Guarantee
If OSRAM ECGs and LUMILUX ® fluorescent lamps are used together (selected series or types), OSRAM offers a full five-year guarantee for the
QUICKTRONIC ® electronic control gear and a three-year guarantee for the LUMILUX ® fluorescent lamps. For the System+ Guarantee the lighting
system must be registered with OSRAM. For terms and conditions and information on registration go to www.osram.com/system-guarantee.
OSRAM CRM CC 04/08 Subject to modification without notice. Errors and omissions excepted.
UN
z Printed on paper treated with chlorine-free bleach.
TECHNICAL DATA