ECG for T8/26mm fluorescent lamps
QTP8
®
LUMILUX T8
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
01
QUICKTRONIC PROFESSIONAL QTP8
Product Features:









Up to 100.000 hours lifetime1
Lamp start with optimised filament preheating within 2 sec.
Reliable lamp ignition between -25°C ...+55°C
Suitable for luminaires of PC I + II
Constant light output for UN = 198V ... 264V
CELMA energy classification EEI = A2
Automatic safety shut down at lamp failure
Automatic restart after lamp replacement
Suitable for emergency installations (DC operation)
Technical Data
Max. cable diameter
for IDC-contakt [mm2]:
s2: 0.5; s-f3: 0.75
Max. cable diameter for
push-in contact [mm2]:
s2: 0.5...1.0
Starting time:
t < 2 sec.
Line voltage:
230 - 240 V
Voltage range (AC):
198 - 264 V
Voltage range (DC):
154-276 V; min. 198 V for lamp ignition
Line frequency:
0, 50 - 60 Hz
Operating frequency:
45 - 60 kHz
Electrical strength:
300 V  permanent
Ambient temperature ta:
-25 °C to +55 °C
Measuring point temperature tc:
Max. +75 °C
U-OUT:
380 V
1
at T = 65°C @ Tc. 50.000 h with max. 10% failure rate at tc = 75°C max
s = stranded wire
3
s-f = stranded-flexible wire
2
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
02
QUICKTRONIC PROFESSIONAL QTP8
Inrush current and max. number of ECG per circuit breaker
ECG
QTP8
QTP8
QTP8
QTP8
QTP8
QTP8
QTP8
QTP8
Inrush Current
Ip [A]
14
17
20
20
17
20
20
28
1x18
2x18
3x18
4x18
1x36
2x36
1x58
2x58
Max. number of ECG per circuit breaker
TH [µs]
140
155
210
210
155
210
210
230
C: 10A
36
25
17
17
25
17
17
8
B: 16A
59
41
28
28
41
28
28
13
C: 16 A
101
69
47
47
69
47
47
20
Standards and approval marks
Safety:
acc. to EN 61347-2-3 / IEC 61347-2-3
Radio interference:
acc. EN 55015: 2006 + A1: 2007 + A2: 2009
Harmonic content:
acc. to EN 61000-3-2 / IEC 61000-3-2
Immunity:
acc. to EN 61547 / IEC 61547
Approval marks:
Dimensions & weight
Description
Description
Length
[mm]
Width [mm]
Height [mm]
Distance
Weight [g]
Mounting
Holes [mm]
QTP8 1x18
360
30
30
350
270
QTP8 2x18
423
30
30
415
404
QTP8 3x18
423
40
30
415
500
QTP8 4x18
423
40
30
415
500
QTP8 1x36
360
30
30
350
261
QTP8 2x36
423
30
30
415
404
QTP8 1x58
360
30
30
350
309
QTP8 2x58
423
30
30
415
400
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
03
QUICKTRONIC PROFESSIONAL QTP8
Lamp wiring
QTP8 1x…
QTP8 1x
Max. permitted cable length in between ECG and lamp: 2.0 m (PIN 21, 22); 1.5 m (PIN 26, 27)
QTP8 2x…
QTP8 2x
Max. permitted cable length in between ECG and lamp: 3.0 m (PIN 21, 22, 23); 1.5 m (PIN 24, 25, 26, 27)
QTP8 3x18, 4x18 – 3 lamp operation
QTP8 3x18, 4x18
Max. permitted cable length in between ECG and lamp: 1.0 m (PIN 22, 23, 27, 28); 1.5 m (PIN 4, 5, 6, 7, 24, 25,
26)
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
04
QUICKTRONIC PROFESSIONAL QTP8
QTP8 3x18, 4x18 – 4 lamp operation
QTP8 3x18, 4x18
Max. permitted cable length in between ECG and lamp: 1.0 m (PIN 22, 23, 27, 28); 1.5 m (PIN 4, 5, 6, 7, 24, 25,
26)
Logistic Data
Description
EAN 10
EAN 40
Packaging Unit
QTP8 1x18
4008321131584
4008321131591
20
QTP8 2x18
4008321131607
4008321131614
20
QTP8 3x18
4008321131706
4008321131713
20
QTP8 4x18
4008321131706
4008321131713
20
QTP8 1x36
4008321131621
4008321131638
20
QTP8 2x36
4008321131645
4008321131652
20
QTP8 1x58
4008321131669
4008321131676
20
QTP8 2x58
4008321131683
4008321131690
20
Lifetime
Measuring point
temperature tc:
Lifetime
with max. 10% failure rate
75 °C
50,000 h
65 °C
100,000 h
GL LB EU&LM FT, Edition: 13.03.2012. Subject to change without notice. Despite careful review, the possibility of mistakes cannot be excluded – no guaranty will be provided.
TECHNICAL INFORMATION
05
QUICKTRONIC PROFESSIONAL QTP8
Lamp/ECG System Combination
ECG
QTP8
QTP8
QTP8
QTP8
Lamp
1x18
2x18
3x18
4x18
QTP8 1x36
QTP8 2x36
QTP8 1x58
QTP8 2x58
L18
2x L18
3x L18
4x L18
L36
L38
2x L36
2x L38
L58
2x L58
HF lamp
wattage [W]
16
2x16
3x16
4x16
32
32
32
32
50
2x50
System
wattage [W]
18
35
56
73
35
35
71
71
55
110
Line current [A]
0.09
0.17
0.26
0.32
0.16
0.16
0.31
0.31
0.24
0.45
Luminous flux at
25°C [lm]
1300
2x1300
3x1300
4x1300
3200
3200
2x3200
2x3200
5000
2x5000
Luminous flux at
35°C [lm]
-
Power factor
[λ]
0.96
0.97
0.99
0.99
0.96
0.96
0.96
0.96
0.98
0.98
For more information on ECG refer to http://www.osram.com/ecg