QUICKTRONIC® ECG for compact and tubular fluorescent lamps Technical Information QT-T/E 1x18/230-240 Edition: September 2007 subject to change Produkteigenschaften: • • • • • • • • Preheat start, suitable for applications in which lamps are switched on and off frequently Constant flicker-free light without stroboscopic effects CELMA energy classification EEI = A2 50.000 hours lifetime with 10% max. failure rate at tc = 70°C max. Reliable lamp ignition between -15°C...+50°C Reliable and safe shutdown of defective lamps Automatic restart after lamp replacement Suitable for emergency installations (DC operation) Technische Daten: Reference: Lamps: QT-T/E 1x18/230-240 HF-Lamp wattage: [WHF] 18 18 DULUX D/E 18 W DULUX T/E 18 W Preheating time: Supply voltage: Voltage range (AC): Voltage range (DC): Rated frequency: Inrush current: Max. Anzahl EVG 10 A-Automat Charakteristik B: Max. Anzahl EVG 16 A-Automat Charakteristik B: Operating frequency: Power factor: Temperature range ta: Case temperature tc: Dimensions (l x w x h): Distance between mounting holes: Weight: Safety: Radio interference: Harmonic content: Immunity: Packaging unit: Approval marks: 1) System wattage: [W] 20 20 Line current: Luminous flux at 25°C: [A] [lm] 0.08 1150 0.08 1150 1) t < 1.5 sec. 230 V – 240 V 207 V – 254 V 176 V – 254 V; for lamp ignition min. 198 V 0/50-60 Hz Ip = 11 A; TH = 310 µs 17 28 ca. 40 kHz λ = 0.99c -15°C to +50°C max. +70°C K2 (103 x 67 x 31 mm) 110 mm 145 g acc. to EN 61347-2-3 / IEC 61347-2-3 acc. to EN 55015 / CISPR 15 acc. to EN 61000-3-2 / IEC 61000-3-2 acc. to EN 61547 / IEC 61547 20 pieces If there is a temporary interruption in the power supply (< 0.5 sec.) the lamp will start within 0.3 sec. QUICKTRONIC® ECG for compact and tubular fluorescent lamps Vorläufige Technische Technical Information QT-T/E 1x18/230-240 Ausgabe: Edition: July September Juni Juli 2006 2006 20062007 subject Änderungen to change vorbehalten Product number: Product number QT-T/E 1x8/230-240 EAN 10 / Single unit (1 pc.) 4050300 326382 EAN 40 / Package unit (20 pcs.) 4050300 326399 Lamp wiring: Max. permitted cable length in between EVG and lamp: 2.0 m (PIN 1;2); 1.0 m (PIN 3;4)