FKHD - Power Entry Modules with Line Filter

FKHD
Power Entry Modules with Line Filter
www.schurter.com/PG06
IEC Appliance Inlet C14 with Filter 2-Stage, Fuseholder 1-pole, Line Switch 2-pole
Standard- or Medical-Filter
C14
70° C
Description
-Panel Mount:
Screw-on mounting from front side
-4 Functions:
Appliance Inlet Protection class I, Fuseholder for fuse-links 5 x 20 mm
1‑pole, Line Switch 2-pole, Line-filter in standard version, 2 positions
-Quick connect terminals 6.3 x 0.8 mm
Approvals
-VDE Certificate Number: 40004665
-UL File Number: E72928
Characteristics
-Compact design with optimal shielding
-All single elements are already wired
-Plug removal necessary for fuse-link replacement
-2-stage line filter with increased attenuation
With EMC-shield
-Suitable for use in equipment according to IEC/UL 60950
Suitable for use in medical equipment according to IEC/UL 60601-1
Other versions on request
-Medical version M80
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, Mating
Connectors, e-Shop, SCHURTER-Stock-Check, Distributor-StockCheck, CAD-Drawings, Accessories, Detailed request for product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz
standard < 0.25 mA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
Appliance-Inlet/-Outlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Switch
Line Filter
MTBF
C14 acc. to IEC 60320,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class I
1-pole, Shocksafe category PC2 acc. to
IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 1.6 W (1 pole)
Admissible power acceptance at higher
ambient temperature see derating curves
2-pole, non-illuminated, acc. to IEC
61058-1
Technical Details
Standard Version, IEC 60939, UL 1283,
CSA C22.2 no. 8
Technical Details
> 1'200'000 h acc. to MIL-HB-217 F
Connectors
1
FKHD
Power Entry Modules with Line Filter
www.schurter.com/PG06
Dimension
Case 45
40 ±0.15
+0.5
61–0.2
R1
60.4
6.3x0.8
ø 6.3x90°
ø 3.2
49
63
65 ±0.5
40
M3
3.5
28
R4
50 ±0.5
29.5±0.5
14
5.5
61.3
28.7
67
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type
Inductances
L [mH]
Capacitance
CX [nF]
Capacity
Cy1 [nF]
Capacity
Cy2 [nF]
R [MΩ]
1
Standard Version
2 x 10
68
1.5
1
1
2
Standard Version
2x4
68
1.5
1
1
4
Standard Version
2 x 1.5
68
1.5
1
1
6
Standard Version
2 x 0.8
68
1.5
1
1
10
Standard Version
2 x 0.3
68
1.5
1
1
1
Medical Version (M5)
2 x 10
68
-
-
1
2
Medical Version (M5)
2x4
68
-
-
1
4
Medical Version (M5)
2 x 1.5
68
-
-
1
6
Medical Version (M5)
2 x 0.8
68
-
-
1
10
Medical Version (M5)
2 x 0.3
68
-
-
1
Diagrams
Standard version
N
F2
1) PE
Medical version (M5)
L1
2)
R
F1
L
R = 1MΩ
Cy1
Cx
Cx = 68nF
L2
Cx
Cy1
Cy1 = 1.5 nF
Cy2
L2
Cy2
PE’ 3)
L’
N
L
1) Line
2) Load
Connectors
F2
1) PE
Cy2 = 1nF
1) Line
2) only FKID
3) Load
2
N’
L1
L1
R
F1
Cx
L2
L1
Cx
N’
PE’ 2)
L2
L’
FKHD
Power Entry Modules with Line Filter
www.schurter.com/PG06
Derating Curves
Admissible power
acceptance in Watt
1-pole
1.6
1.4
1.2
I = 1.0 In
1.0
0.8
I = 0.7 In
0.6
I = << In
0.4
0.2
0.0
0
20
40
60
80
100
Ambient air temperature Ta °C
Attenuation Loss
- - - - differential mode _____ common mode
Standard version
1A
2A
4A
6A
2A
4A
6A
10 A
Medical version (M5)
1A
10 A
Connectors
3
FKHD
Power Entry Modules with Line Filter
www.schurter.com/PG06
All Variants
Type
Rated Current
[A]
FKHD
1
FKHD
2
FKHD
Filter-Type
Fuseholder
Line Switch
Housing
Material: Housing
Order Number
Standard Version
1-pole
2-pole
Standard Version
1-pole
2-pole
45
Aluminum
4304.5041
45
Aluminum
4
Standard Version
1-pole
4304.5042
2-pole
45
Aluminum
FKHD
6
Standard Version
4304.5043
1-pole
2-pole
45
Aluminum
4304.5044
FKHD
10
Standard Version
1-pole
2-pole
45
Aluminum
4304.5045
FKHD
FKHD
1
Medical Version (M5)
1-pole
2-pole
45
Aluminum
4304.5046
2
Medical Version (M5)
1-pole
2-pole
45
Aluminum
4304.5047
FKHD
4
Medical Version (M5)
1-pole
2-pole
45
Aluminum
4304.5048
FKHD
6
Medical Version (M5)
1-pole
2-pole
45
Aluminum
4304.5049
FKHD
10
Medical Version (M5)
1-pole
2-pole
45
Aluminum
4304.5050
FKHD
1
Standard Version
1-pole
2-pole
45
Nickel plated steel
4304.5001
FKHD
2
Standard Version
1-pole
2-pole
45
Nickel plated steel
4304.5002
FKHD
4
Standard Version
1-pole
2-pole
45
Nickel plated steel
4304.5003
FKHD
6
Standard Version
1-pole
2-pole
45
Nickel plated steel
4304.5004
FKHD
10
Standard Version
1-pole
2-pole
45
Nickel plated steel
4304.5005
█
█
█
█ Most Popular.
Availability for all products can be searched real-time:http://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
Packaging unit 10 Pcs Accessories
Description
Assorted Covers
Rear Cover
0859.0074
Mating Outlets/Connectors
Category / Description
Appliance Outlet Overview complete
IEC Appliance Outlet F, Screw-on Mounting, Front Side, Solder Terminal
4787
IEC Appliance Outlet F, Snap-in Mounting, Front Side, Solder or Quick-connect Terminal
4788
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder, PCB or Quick-connect Terminal
5091
Appliance Outlet further types to FKHD
4
4782 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4782
4022 Mounting: Power Supply Cord, 3 x 1.5 mm², Screw clamps, Connector: IEC C13
4022
4785 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4785
4300-06 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4300-06
4012 Mounting: Power Supply Cord, 3 x 1.5 mm², Screw clamps, Connector: IEC C13
4012
Connector further types to FKHD
...
Connectors
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
24.08.2015
Connector Overview complete