DD12 - Power Entry Modules with Line Filter

DD12
Power Entry Modules with Line Filter
www.schurter.com/PG06
IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole, Line Switch 2-pole
Standard- or Medical-Filter
Order required accessories separately
C14
70° C
Description
-Panel Mount:
Screw-on from front side
-4 Functions:
Appliance Inlet Protection class I, Line Switch 2-pole, Fuseholder for
fuse-links 5 x 20 mm 1‑ or 2‑pole, Line filter in standard and medical
version
-Quick connect terminals 6.3 x 0.8 mm
Approvals
-VDE Certificate Number: 40001522
-UL File Number: E72928
Characteristics
-Ultra-compact design. Ideal for low profile designs
Aluminum case provides good shielding
-All single elements are already wired
-Fuse drawer meets requirements of medical standard IEC/EN 60601-1
-Ideal for application with high transient loads
Designed for standard and medical applications
-Suitable for use in equipment according to IEC/UL 60950
Suitable for use in medical equipment according to IEC/UL 60601-1
Other versions on request
-Solder terminals
-Fuse drawer 1-pole, plus spare fuse case
-Fuse drawer 2-pole, with shorting bar
-Other rocker marking
-Line switch, illuminated
-Line switch 1-pole
-Medical version M80
-Class X1- and Y1-capacitors for enhanced withstand voltage
-Variant with notch for V-Lock mating Cordsets
References
Alternative: version without line filter DD11 Alternative: version for snap-in mounting KMF Alternative: Standard version Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, Mating
Connectors, e-Shop, SCHURTER-Stock-Check, Distributor-StockCheck, CAD-Drawings, Accessories, Wire Harnessing, Detailed request
for product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 8 A @ Ta 40 °C / 250 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (1 min/50 Hz)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw-on mounting: max 8 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
Appliance-Inlet/-Outlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Switch
Line Filter
MTBF
C14 acc. to IEC 60320
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class I
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 2 W (1 pole)/ 1.6 W (2-pole) per
pole
Admissible power acceptance at higher
ambient temperature see derating curves
Rocker switch 2-pole, non-illuminated,
acc. to IEC 61058-1
Technical Details
Standard and Medical Version, IEC
60939, UL 1283, CSA C22.2 no. 8
Technical Details
> 2'000'000 h acc. to MIL-HB-217 F
Connectors
1
DD12
Power Entry Modules with Line Filter
www.schurter.com/PG06
Dimension
Screw version
46.7
56 ±0.15
10.3
9.8
56
3.4
45.3
66
55
5.9
48.5
15.1
1.3
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type
Inductances
L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
R [MΩ]
1
Standard Version
2 x 10
100
2.2
1
2
Standard Version
2x4
100
2.2
1
4
Standard Version
2 x 1.5
100
2.2
1
6
Standard Version
2 x 0.8
100
2.2
1
8
Standard Version
2 x 0.6
100
2.2
1
10
Standard Version
2 x 0.3
100
2.2
1
1
Medical Version (M5)
2 x 10
100
-
1
2
Medical Version (M5)
2x4
100
-
1
4
Medical Version (M5)
2 x 1.5
100
-
1
6
Medical Version (M5)
2 x 0.8
100
-
1
8
Medical Version (M5)
2 x 0.6
100
-
1
10
Medical Version (M5)
2 x 0.3
100
-
1
1
Medical Version (M80)
2 x 10
100
0.47
1
2
Connectors
3.
4
±0
.1
0
4.
6
R
29.8
90˚
L
PE
N
12
27.7
31.5
5
3.2
±0.10
49.3 ±0.10
DD12
Power Entry Modules with Line Filter
www.schurter.com/PG06
Diagrams
Standard version
non illuminated
L
Medical version M5
non illuminated
L’
F1
1)
PE
S
R
F2
N
L
L1
2)
Cy
Cx
L2
PE’
Cy
1)
PE
N’
1) Line
2) Load
N
L’
F1
L1
S
R
Cx
F2
2)
PE’
L2
Cy
N’
1) Line
2) Load
Derating Curves
2-pole
2.0
1.5
I = 1.0 In
I = 0.7 In
1.0
I = << In
0.5
0.0
0
20
40
60
80
100
Admissible power
acceptance in Watt
Admissible power
acceptance in Watt
1-pole
Ambient air temperature Ta °C
1.6
1.4
1.2
I = 1.0 In
1.0
0.8
I = 0.7 In
0.6
I = << In
0.4
0.2
0.0
0
20
40
60
80
100
Ambient air temperature Ta °C
Attenuation Loss
- - - - differential mode _____ common mode
Standard version
1A
2A
8A
10 A
4A
6A
Connectors
3
DD12
Power Entry Modules with Line Filter
www.schurter.com/PG06
Medical version (M5)
1A
2A
8A
10 A
4A
6A
All Variants
Rated Current
[A]
Filter-Type
Fuseholder
Line Switch
Illumination
Order Number
1
Standard Version
1-pole
2-pole
non-illuminated
DD12.1111.111
█
2
Standard Version
1-pole
2-pole
non-illuminated
DD12.2111.111
█
4
Standard Version
1-pole
2-pole
non-illuminated
DD12.4111.111
█
6
Standard Version
1-pole
2-pole
non-illuminated
DD12.6111.111
█
8
Standard Version
1-pole
2-pole
non-illuminated
DD12.8111.111
█
10
Standard Version
1-pole
2-pole
non-illuminated
DD12.9111.111
█
1
Standard Version
2-pole
2-pole
non-illuminated
DD12.1121.111
█
2
Standard Version
2-pole
2-pole
non-illuminated
DD12.2121.111
█
2
Standard Version
2-pole
2-pole
illuminated, green
DD12.2124.111
█
4
Standard Version
2-pole
2-pole
non-illuminated
DD12.4121.111
█
6
Standard Version
2-pole
2-pole
non-illuminated
DD12.6121.111
█
6
Standard Version
2-pole
2-pole
illuminated red
DD12.6123.111
█
8
Standard Version
2-pole
2-pole
non-illuminated
DD12.8121.111
█
10
Standard Version
2-pole
2-pole
non-illuminated
DD12.9121.111
█
1
Medical Version (M5)
2-pole
2-pole
non-illuminated
DD12.1321.111
█
2
Medical Version (M5)
2-pole
2-pole
non-illuminated
DD12.2321.111
█
4
Medical Version (M5)
2-pole
2-pole
non-illuminated
DD12.4321.111
█
6
Medical Version (M5)
2-pole
2-pole
non-illuminated
DD12.6321.111
█
8
Medical Version (M5)
2-pole
2-pole
non-illuminated
DD12.8321.111
█
10
Medical Version (M5)
2-pole
2-pole
non-illuminated
DD12.9321.111
█
1
Medical Version (M80)
2-pole
2-pole
non-illuminated
DD12.1621.111
█
█ Most Popular.
Availability for all products can be searched real-time:http://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
10 A version only IEC approval.
Packaging unit 4
20 Pcs Connectors
DD12
Power Entry Modules with Line Filter
www.schurter.com/PG06
Required Accessory
Description
Fusedrawer 2
Fusedrawer für Fuse Links 5x20 mm, with or without Voltage Selector Insert
Fingergrip, 2-pole
4301.1401
Extra-Safe, 2-pole
4301.1403
Fingergrip, 1-pole
4301.1405
Extra-Safe, 1-pole
4301.1407
...
Accessories
Wire Harness
Wire harness for SCHURTER products
Assorted Covers
Rear Cover
0859.0076
Cord retaining kits
Cord retaining strain relief
Flat head, A
4700.0001
Mating Outlets/Connectors
Category / Description
Appliance Outlet Overview complete
IEC Appliance Outlet F, Screw-on Mounting, Front Side, Solder Terminal
4787
IEC Appliance Outlet F, Snap-in Mounting, Front Side, Solder or Quick-connect Terminal
4788
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder, PCB or Quick-connect Terminal
5091
Appliance Outlet further types to DD12
Connector Overview complete
4782 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4782
4022 Mounting: Power Supply Cord, 3 x 1.5 mm², Screw clamps, Connector: IEC C13
4022
4785 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4785
4300-06 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4300-06
4012 Mounting: Power Supply Cord, 3 x 1.5 mm², Screw clamps, Connector: IEC C13
4012
Connector further types to DD12
...
Connectors
5
DD12
Power Entry Modules with Line Filter
www.schurter.com/PG06
Mating Outlets/Connectors shuttered
Power Cord Overview complete
VAC17KS, North America, 2.0 m, Connector C17, cord end:
6051.2801
VAC17KS, Europlug, 2.0 m, Connector IEC C17, cord end:
6051.2803
VAC17KS, Europlug, 2.0 m, Connector IEC C17, cord end:
6051.2813
VAC13KS, Overview, diverse Connector IEC C13, cord end:
VAC13KS
Power Cord further types to DD12
24.08.2015
6
Connectors
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.