KMF - Power Entry Modules with Line Filter

KMF
Power Entry Modules with Line Filter
www.schurter.com/PG06
IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole, Line Switch 2-pole
Plug removal necessary for fuse
replacement
KMF: With shield and line filter
Order required accessories separately
C14
70° C
Description
-Panel Mount:
Snap-in version from front side
-4 Functions:
Appliance Inlet Protection class I, Line Switch 2-pole, Fuseholder for
fuse-links 5 x 20 mm 1‑ or 2‑pole, Line filter in standard and medical
version
-Quick connect terminals 4.8 x 0.8 mm
Approvals
-VDE Certificate Number: 40035743
-UL File Number: E72928
-CCC File Number: 2009010204326571
Characteristics
-Ultra-compact design. Small dimensions in front of and behind the panel
-All single elements are already wired
-For added safety "Extra-Safe" fuse drawers are available
-Innovative EMC-shielding with flexible steel segments for an excellent
contact
-Suitable for use in equipment according to IEC/UL 60950
Suitable for use in medical equipment according to IEC/UL 60601-1
Other versions on request
-Fuse drawer 1-pole, plus spare fuse case
-Fuse drawer 2-pole, with shorting bar
-Other rocker marking
References
Alternative: version without line filter KM Alternative: version for screw mounting DD12 Alternative: Standard version Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, Mating
Connectors, e-Shop, SCHURTER-Stock-Check, Distributor-StockCheck, CAD-Drawings, Accessories, Wire Harnessing, Detailed request
for product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 4.8 x 0.8 mm
Snap-in: 1/1.5/2/2.5 mm
(all steps with one variant)
Thermoplastic, black, UL 94V-0
Appliance-Inlet/-Outlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Switch
Line Filter
MTBF
C14 acc. to IEC 60320,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class I
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 2 W (1 pole)/ 1.4 W (2-pole) per
pole
Admissible power acceptance at higher
ambient temperature see derating curves
2-pole, non-illuminated, acc. to IEC
61058-1
Technical Details
Standard and Medical Version, IEC
60939, UL 1283, CSA C22.2 no. 8
Technical Details
> 1'800'000 h acc. to MIL-HB-217 F
Connectors
1
KMF
Power Entry Modules with Line Filter
www.schurter.com/PG06
Dimension
30.4
.5
R1
25.7
L
3
m
10.7
ax
.R
32
50
47.5
+0.10
47.8 -0.05
N
0.
0
S ± 0.05
40.4
30.5
+0.10
28.5
2.5
28.8 -0.05
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type
Inductances
L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
R [MΩ]
1
Standard Version
2 x 11
47
2.2
-
2
Standard Version
2x4
47
2.2
-
4
Standard Version
2 x 1.6
47
2.2
-
6
Standard Version
2 x 0.7
47
2.2
-
10
Standard Version
2 x 0.4
47
2.2
-
1
Medical Version (M5)
2 x 11
47
-
1
2
Medical Version (M5)
2x4
47
-
1
4
Medical Version (M5)
2 x 1.6
47
-
1
6
Medical Version (M5)
2 x 0.7
47
-
1
10
Medical Version (M5)
2 x 0.4
47
-
1
Diagrams
Standard version
Medical version (M5)
L
L
L’
L1
1)
F1
Cy
PE
Cx
N
L2
F2
Cy
1) Line
2) Load
2
2)
PE’
N’
PE
N
1) Line
2) Load
Connectors
L’
L1
1)
F1
2)
R
Cx
L2
PE’
F2
N’
KMF
Power Entry Modules with Line Filter
www.schurter.com/PG06
Derating Curves
2-pole
2.0
1.5
I = 1.0 In
I = 0.7 In
1.0
I = << In
0.5
0.0
0
20
40
60
80
100
Admissible power
acceptance in Watt
Admissible power
acceptance in Watt
1-pole
Ambient air temperature Ta °C
1.4
1.2
1.0
I = 1.0 In
0.8
I = 0.7 In
0.6
I = << In
0.4
0.2
0.0
0
20
40
60
80
100
Ambient air temperature Ta °C
Attenuation Loss
- - - - differential mode _____ common mode
Standard version
1A
2A
4A
6A
2A
4A
6A
10 A
Medical version (M5)
1A
10 A
Connectors
3
KMF
Power Entry Modules with Line Filter
www.schurter.com/PG06
All Variants
Rated Current
[A]
Filter-Type
Fuseholder
Line Switch
Illumination
Order Number
1
Standard Version
1-pole
2-pole
non-illuminated
KMF1.1211.11
█
2
Standard Version
1-pole
2-pole
non-illuminated
KMF1.1221.11
█
4
Standard Version
1-pole
2-pole
non-illuminated
KMF1.1241.11
█
6
Standard Version
1-pole
2-pole
non-illuminated
KMF1.1261.11
█
10
Standard Version
1-pole
2-pole
non-illuminated
KMF1.1291.11
█
1
Standard Version
2-pole
2-pole
non-illuminated
KMF1.1111.11
█
2
Standard Version
2-pole
2-pole
non-illuminated
KMF1.1121.11
█
4
Standard Version
2-pole
2-pole
non-illuminated
KMF1.1141.11
█
6
Standard Version
2-pole
2-pole
non-illuminated
KMF1.1161.11
█
10
Standard Version
2-pole
2-pole
non-illuminated
KMF1.1191.11
█
1
Medical Version (M5)
1-pole
2-pole
non-illuminated
KMF1.1213.11
2
Medical Version (M5)
1-pole
2-pole
non-illuminated
KMF1.1223.11
4
Medical Version (M5)
1-pole
2-pole
non-illuminated
KMF1.1243.11
6
Medical Version (M5)
1-pole
2-pole
non-illuminated
KMF1.1263.11
10
Medical Version (M5)
1-pole
2-pole
non-illuminated
KMF1.1293.11
1
Medical Version (M5)
2-pole
2-pole
non-illuminated
KMF1.1113.11
█
2
Medical Version (M5)
2-pole
2-pole
non-illuminated
KMF1.1123.11
█
4
Medical Version (M5)
2-pole
2-pole
non-illuminated
KMF1.1143.11
█
6
Medical Version (M5)
2-pole
2-pole
non-illuminated
KMF1.1163.11
█
10
Medical Version (M5)
2-pole
2-pole
non-illuminated
KMF1.1193.11
█
█ Most Popular.
Availability for all products can be searched real-time:http://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
Packaging unit 20 Pcs Required Accessory
Description
Fusedrawer 2
Fusedrawer für Fuse Links 5x20 mm, with or without Voltage Selector Insert
Fingergrip, 2-pole
4301.1401
Extra-Safe, 2-pole
4301.1403
Fingergrip, 1-pole
4301.1405
Extra-Safe, 1-pole
4301.1407
...
Accessories
Wire Harness
Wire harness for SCHURTER products
Assorted Covers
Rear Cover
0859.0076
4
Connectors
KMF
Power Entry Modules with Line Filter
www.schurter.com/PG06
Cord retaining kits
Cord retaining strain relief
Flat head, A
4700.0001
Mating Outlets/Connectors
Category / Description
Appliance Outlet Overview complete
IEC Appliance Outlet F, Screw-on Mounting, Front Side, Solder Terminal
4787
IEC Appliance Outlet F, Snap-in Mounting, Front Side, Solder or Quick-connect Terminal
4788
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder, PCB or Quick-connect Terminal
5091
Appliance Outlet further types to KMF
Connector Overview complete
4782
4022 Mounting: Power Supply Cord, 3 x 1.5 mm², Screw clamps, Connector: IEC C13
4022
4785 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4785
4300-06 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4300-06
4012 Mounting: Power Supply Cord, 3 x 1.5 mm², Screw clamps, Connector: IEC C13
4012
Connector further types to KMF
...
24.08.2015
4782 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
Connectors
5