FMBB - 1-Phase Line Filters

FMBB
1-Phase Line Filters
www.schurter.com/PG84
AC Filter 2-Stage, Broad Band Attenuation
Description
-Chassis:
Screw-on mounting, from top
-Line-filter in standard version, 2 positions, very high attenuation
-High symmetrical and asymmetrical attenuation in the frequency range
from 10kHz up to 30MHz
Approvals
-VDE Certificate Number: 40004673
-UL File Number: E72928
Characteristics
-Designed for high current applications
-Protection against interference voltage from the mains
Possible interferences generated in the equipment are strongly attenuated
-Especially designed for industrial applications such as: Frequency Converters, Stepper Motor Drives, UPS-Systems, Inverters
-Suitable for use in equipment according to IEC/UL 60950
Other versions on request
-Version with wire connection
References
Alternative: Standard version Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, e-Shop,
SCHURTER-Stock-Check, Distributor-Stock-Check, Detailed request for
product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Protection Class
Terminal
Material: Housing
8 - 25 A @ Ta 40 °C / 250 VAC; 50 Hz
8 - 25 A @ Ta 40 °C / 125 VAC; 60 Hz
industrial < 3.5 mA ( V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 100 °C
25/100/21 acc. to IEC 60068-1
Suitable for appliances with protection
class I acc. to IEC 61140
Screw
Metal
Line Filter
MTBF
Standard and Industrial Version, IEC
60939, UL 1283, CSA C22.2 no. 8
Technical Details
> 200'000 h acc. to MIL-HB-217 F
Connectors
1
FMBB
1-Phase Line Filters
www.schurter.com/PG84
Dimension
Case 24-2
Case 16-2
max. 58
max. 47
(9)
max. 87.5 ±0.5
1)
(20)
(27)
max. 54
M4
4)
max. 86
2)
4)
max. 100
3)
5.3 ±0.2
(7)
(29.5)
+0
1)
95 -1
max. 106
max. 137
max. 100
2)
M6
3)
51 ±0.3
(15)
(17)
1) Line
2) Load
3) Nut torque 3...4 Nm
4) I/O Connections torque 0.6...0.8
1) Line
2) Load
3) Nut torque 3...4 Nm
4) Do not unscrew lock-nut
Case 31-2
Case 31-6
(7)
6.5 ±0.3
M6
115
3)
1) Line
2) Load
3) Nut torque 3...4 Nm
1)
6.5 ±0.3
(17)
2)
(30)
+0
100 -1
max. 116
max. 86
2)
±0.3
max. 61
(1)
max. 181
(30)
100 -1
+0
max. 116
1)
max. 217
max. 61
max. 217
max. 181
(12)
max. 78
max. 86
5.3 ±0.3
M6
115
±0.3
3)
(17)
1) Line
2) Load
3) Nut torque 3...4 Nm
Diagrams
S1 standard version
S2 standard version
2) 1)
1)
1) Line
2) Load
2
1) Line
2) Load
Connectors
2)
FMBB
1-Phase Line Filters
www.schurter.com/PG84
Attenuation Loss
- - - - differential mode _____ common mode
Standard version
8A
Industrial version
12 A
16 A
25 A
All Variants
Rated Current Filter-Type
[A]
Leakage Current [mA]
L [mH]
C1
(X2)
[μF]
C2
(X2)
[µF]
C3
(X2)
[µF]
C4
(Y2)
[nF]
C5
(Y2)
[nF]
R1, R2
[MΩ]
Diagram
Clamps
[mm2]
Weight
[g]
Housing Order
Number
8
Standard Version
0.25
2x7
0.1
0.15
0.47
2.2
-
1
S1
4
410 g
16-2
5500.2068
12
Industrial Version
3.5
2x5
2.2
2.2
2.2
33
2.2
0.5
S2
4
1000 g
24-2
5500.2069
16
Industrial Version
3.5
2 x 3.5
2.2
2.2
2.2
33
2.2
0.5
S2
4
2400 g
31-2
5500.2070
25
Industrial Version
3.5
2 x 3.5
2.2
2.2
2.2
33
2.2
0.5
S2
6
2500 g
31-6
5500.2071
█
█ Most Popular.
Availability for all products can be searched real-time:http://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
5 Pcs 04.03.2015
Packaging unit The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
Connectors
3