FMAB RAIL - 1-Phase Line Filters

FMAB RAIL
1-Phase Line Filters
www.schurter.com/PG84
AC Filter, DIN Rail Mounting
Description
Characteristics
Approvals
Weblinks
-Chassis:
DIN rail mounting
-Line filter in industrial version, 1 stage, high attenuation
-Especially effective against asymmetrical interferences in the frequency
range from 100kHz up to 30MHz
-Protection against interference voltage from the mains
Possible interferences generated in the equipment are strongly attenuated
-Especially designed for electric switch and control cabinets
-Suitable for use in equipment according to IEC/UL 60950
-VDE Certificate Number: 40030734
-UL File Number: E72928
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, e-Shop,
SCHURTER-Stock-Check, Distributor-Stock-Check, Detailed request for
product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Material: Housing
10 - 20 A @ Ta 40 °C / 250 VAC; 50 Hz
10 - 20 A @ Ta 40 °C / 125/250 VAC;
60 Hz
industrial < 2.1 mA (250 V / 50 Hz)
1.7 kVDC between L-N
2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 100 °C
25/100/21 acc. to IEC 60068-1
IP 20 IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Bolts and nuts M4, Quick connect terminal for PE
Metal
Line Filter
MTBF
Industrial Version, IEC 60939, UL 1283,
CSA C22.2 no. 8
Technical Details
> 200'000 h acc. to MIL-HB-217 F
Connectors
1
FMAB RAIL
1-Phase Line Filters
www.schurter.com/PG84
Dimension
max. 61
(6.5)
4)
L
1)
N
(75)
3)
2)
N'
27
max. 48
16
L'
max. 102
EN 60715
35x7.5
24.5
11.5
max. 61
1) Line
2) Load
3) Tightening torque 0.6-0.8 Nm, Screw 4mm²
4) Quick connect terminal 6.3x0.8mm
Diagrams
1)
2)
1) Line
2) Load
Attenuation Loss
. . . . . 0.1/100Ω differential mode
Industrial version
10 A
20 A
2
Connectors
........... 100/0.1Ω differential mode
- - - - differential mode _____ common mode
FMAB RAIL
1-Phase Line Filters
www.schurter.com/PG84
All Variants
Rated Current [A]
Leakage Current [mA] 1)
L [mH]
C1 (X2) [nF]
C2 (Y2) [nF]
Weight
[g]
Screw clamps
[mm2] 2)
10
20
Order Number
2.1
2x1
68
22
358 g
4
5500.2261
2.1
2 x 0.15
68
22
380 g
4
5500.2262
Availability for all products can be searched real-time:http://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
1) Leakage current acc. IEC60950 - 5.2.3 - Annex D (situation when neutral is interrupted)
2) Maximum conductor cross section (wire gauge) to be used; a comparative table for AWG and mm² values can be found in the
general product information www.schurter.com/emc_info
5 Pcs 04.03.2015
Packaging unit The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
Connectors
3