FKH - Power Entry Modules with Line Filter

FKH
Power Entry Modules with Line Filter
www.schurter.com/PG06
IEC Appliance Inlet C14 with Filter, Fuseholder 1-pole, Line Switch 2-pole
Aluminum
Standard- or Medical-Filter
Nickel plated steel
C14
70° C
Description
Characteristics
Approvals
Other versions on request
-Panel Mount:
Screw-on mounting from front side
-4 Functions:
Appliance Inlet Protection class I, Line Switch 2-pole, Fuseholder for
fuse-links 5 x 20 mm 1‑pole, Line-filter in standard version
-Quick connect terminals 6.3 x 0.8 mm
-VDE Certificate Number: 40004665
-UL File Number: E72928
-Compact design with optimal shielding
-All single elements are already wired
-Plug removal necessary for fuse-link replacement
-With EMC-shield
-Suitable for use in equipment according to IEC/UL 60950
Suitable for use in medical equipment according to IEC/UL 60601-1
-Medical version M80
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, Mating
Connectors, e-Shop, SCHURTER-Stock-Check, Distributor-StockCheck, CAD-Drawings, Accessories, Detailed request for product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz
standard < 0.25 mA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
Appliance-Inlet/-Outlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Switch
Line Filter
MTBF
C14 acc. to IEC 60320,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class I
1-pole, Shocksafe category PC2 acc. to
IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 1.6 W (1 pole)
Admissible power acceptance at higher
ambient temperature see derating curves
2-pole, non-illuminated, acc. to IEC
61058-1
Technical Details
Standard Version, IEC 60939, UL 1283,
CSA C22.2 no. 8
Technical Details
> 1'700'000 h acc. to MIL-HB-217 F
Connectors
1
FKH
Power Entry Modules with Line Filter
www.schurter.com/PG06
Dimension
Case 45
40 ±0.15
+0.5
61–0.2
R1
60.4
6.3x0.8
ø 6.3x90°
49
ø 3.2
63
65 ±0.5
40
M3
3.5
28
R4
50 ±0.5
29.5±0.5
14
5.5
61.3
28.7
67
Case 50
49.5
+0.5
61–0.2
ø 6.3x90°
60.4
6.3x0.8
40 ±0.15
ø 3.2
63
65 ±0.5
40
M3
3.5
28
R4
50 ±0.5
15
5.5
40.5
28.7
55
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type
Inductances
L [mH]
Capacitance
CX [nF]
Capacitance
CY [nF]
R [MΩ]
1
Standard Version
2 x 10
68
2.2
1
2
Standard Version
2x4
68
2.2
1
4
Standard Version
2 x 1.5
68
2.2
1
6
Standard Version
2 x 0.8
68
2.2
1
10
Standard Version
2 x 0.3
68
2.2
1
1
Medical Version (M5)
2 x 10
68
-
1
2
Medical Version (M5)
2x4
68
-
1
4
Medical Version (M5)
2 x 1.5
68
-
1
6
Medical Version (M5)
2 x 0.8
68
-
1
10
Medical Version (M5)
2 x 0.3
68
-
1
2
Connectors
29.5±0.5
FKH
Power Entry Modules with Line Filter
www.schurter.com/PG06
Diagrams
Standard version
N
F2
1) PE
Medical version (M5)
Cy
R
Cx
F1
L
N’
L1
2)
L2
Cx
Cy
PE’ 3)
N
1) PE
L’
L
R = 1MΩ
1) Line
2) only FKI
3) Load
N’
F2
L1
R
F1
Cx
L2
Cx
PE’
2)
L’
1) Line
2) Load
Derating Curves
Admissible power
acceptance in Watt
1-pole
1.6
1.4
1.2
I = 1.0 In
1.0
0.8
I = 0.7 In
0.6
I = << In
0.4
0.2
0.0
0
20
40
60
80
100
Ambient air temperature Ta °C
Attenuation Loss
- - - - differential mode _____ common mode
Standard version
1A
2A
4A
6A
10 A
Connectors
3
FKH
Power Entry Modules with Line Filter
www.schurter.com/PG06
Medical version (M5)
1A
2A
4A
6A
10 A
All Variants
Type
Rated Current
[A]
FKH
1
FKH
2
FKH
Filter-Type
Fuseholder
Line Switch
Housing
Material: Housing
Order Number
Standard Version
1-pole
2-pole
Standard Version
1-pole
2-pole
45
Aluminum
4304.4041
45
Aluminum
4
Standard Version
1-pole
4304.4042
2-pole
45
Aluminum
4304.4043
FKH
6
Standard Version
1-pole
2-pole
45
Aluminum
4304.4044
FKH
10
FKH
1
Standard Version
1-pole
2-pole
45
Aluminum
4304.4045
Medical Version (M5)
1-pole
2-pole
45
Aluminum
FKH
4304.4046
2
Medical Version (M5)
1-pole
2-pole
45
Aluminum
4304.4047
FKH
4
Medical Version (M5)
1-pole
2-pole
45
Aluminum
4304.4048
FKH
6
Medical Version (M5)
1-pole
2-pole
45
Aluminum
4304.4049
FKH
10
Medical Version (M5)
1-pole
2-pole
45
Aluminum
4304.4050
FKH
1
Standard Version
1-pole
2-pole
50
Nickel plated steel
4304.4001
█
FKH
2
Standard Version
1-pole
2-pole
50
Nickel plated steel
4304.4002
█
FKH
4
Standard Version
1-pole
2-pole
50
Nickel plated steel
4304.4003
█
FKH
6
Standard Version
1-pole
2-pole
50
Nickel plated steel
4304.4004
█
FKH
10
Standard Version
1-pole
2-pole
50
Nickel plated steel
4304.4005
█
█ Most Popular.
Availability for all products can be searched real-time:http://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
Packaging unit 10 Pcs Accessories
Description
Assorted Covers
Rear Cover
0859.0074
4
Connectors
█
FKH
Power Entry Modules with Line Filter
www.schurter.com/PG06
Mating Outlets/Connectors
Category / Description
Appliance Outlet Overview complete
IEC Appliance Outlet F, Screw-on Mounting, Front Side, Solder Terminal
4787
IEC Appliance Outlet F, Snap-in Mounting, Front Side, Solder or Quick-connect Terminal
4788
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder, PCB or Quick-connect Terminal
5091
Appliance Outlet further types to FKH
Connector Overview complete
4782
4022 Mounting: Power Supply Cord, 3 x 1.5 mm², Screw clamps, Connector: IEC C13
4022
4785 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4785
4300-06 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
4300-06
4012 Mounting: Power Supply Cord, 3 x 1.5 mm², Screw clamps, Connector: IEC C13
4012
Connector further types to FKH
...
24.08.2015
4782 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.