Micro Family Isolated Remote Sense Application Note

Application NOTE | AN:205
Micro DC-DC Converter Family
Isolated Remote Sense
Application Engineering
Vicor Corporation
July 2008
Introduction
Vicor’s Brick Micro DC-DC converters do not have remote sense pins. Nevertheless,
remote sense can be achieved by employing external circuitry. A circuit is proposed that
senses the voltage at the load and adjusts the converter output voltage to compensate
for the voltage drop in the leads / traces. It also provides isolation of the sense leads /
traces that is beneficial in high-noise applications.
Design Considerations
DC Considerations. The Vicor Micro module’s output can be trimmed up to a maximum
of 10% over the nominal output voltage. This limits the amount of lead / trace resistance
the isolated remote sense circuit can correct for. Maximum round trip lead resistance at
full load is governed by the following formula:
Equation 1.
1.1 Vout(nom) - VPOL
Rlead(max) =
0.9 Imax
Vout(nom): Nominal output voltage of the converter
VPOL: Voltage at the point of load
Imax: Converter rated output power ÷ Vout(nom)
Note: As the module output voltage is trimmed up, the output current drawn from
the module must be reduced proportionally. This is why Imax is multiplied by 90%
when the module is trimmed up 10%.
The proposed circuit may cause oscillation with large output capacitance at light loads.
A minimum load of 10% of the maximum is recommended.
AC Considerations. As the load is moved further away from the output of the converter,
lead / trace impedance will increase. Since the Micro module has local sensing at the
output terminals, this impedance causes the voltage that the converter regulates to be
different from the voltage seen by the load.
This remote sense circuit solves this problem by putting the lead / trace impedance
inside the control loop of the converter. Figure 1 shows a very lossy distribution
network between the converter and point-of-load.
AN:205
vicorpower.com Applications Engineering: 800 927.9474
Page 1
Figure 1.
150 mΩ
LEAD RESISTANCE
Example of long leads between
converter and load
(First-order model)
40 µH
LEAD INDUCTANCE
+Out
300 µF
POINT- OF - LOAD
CAPACITANCE
SC
+
4Ω
LOAD
RESISTANCE
–Out
150 mΩ
LEAD RESISTANCE
40 µH
LEAD INDUCTANCE
Figure 2 illustrates the effect of this parasitic network in the time domain. The step
response shows the point-of-load voltage is delayed with respect to the converter
output. This limits how fast the converter can correct for voltage changes at the load.
Figure 2.
Lead / Trace Step Response
Lead / trace step response
Voltage (V)
1.5
1
0.5
0
-0.5
0
0.5
1
1.5
2
2.5
3
t (ms)
Voltage at load
Output voltage of converter
In the frequency domain this delay results in phase shift that increases with frequency.
This is demonstrated by the Bode plot of this network shown in Figure 3.
Figure 3.
0
Magnitude dB
10
0
-60
-10
-20
-30
-120
-40
-50
100
-180
10000
1000
Frequency (Hz)
Magnitude
Phase Degrees
Lead / Trace Bode Plot
Lead / trace model Bode plot
Phase
Whenever phase shift is introduced into a control network, the stability of that loop
will be degraded. This occurs because the control loop is trying to correct for conditions
that have already occurred. As phase shift approaches -180°, the control loop falls so far
behind that the system will begin to oscillate. This consideration will always be an issue
when remote sense is used, regardless of whether it is realized with built-in sense leads
or an external circuit.
To prevent instability the designer must reduce the loop gain below unity before phase
shift becomes significant. This leads to a fundamental trade off in control system design
because reducing the system bandwidth will degrade its transient response.
AN:205
vicorpower.com Applications Engineering: 800 927.9474
Page 2
Figure 4.
Model of the SC pin
+OUT
Error
Amp
SC
1 kΩ
0.033 µF
–OUT
1.23 V
Remote Sense Circuit Functional Description
As shown in Figure 5, an op-amp with a built-in precision reference (U3) maintains
voltage regulation at the point of load. The reference voltage is scaled up from 200 mV
with the external resistive network formed by R7 and R8 to 1.245 V. The reference has a
compensation capacitor (C2) that slows the ramp-up time to control turn-on overshoot.
The op-amp compares this reference voltage to the point of load voltage scaled by R9
and R10. The output of the op-amp drives the cathode of an optocoupler (U1). The
optocoupler isolates noise voltages that are present at the negative output lead thereby
keeping them from appearing on the SC pin. The speed at which the external loop can
respond to load transients is determined by the compensation capacitor (C3) and the
parallel combination of the voltage sensing resistors (R9 and R10). R11 allows C3 to fully
discharge when power is removed from the circuit.
The optocoupler is connected to the SC pin via resistors R1 and R2. These resistors
program the maximum output voltage at the converter (R1) and the minimum output
voltage of the converter (R2). Figure 4 shows how the internal connections of the SC pin
form a RC filter that will limit overall system bandwidth.
The op-amp and the optocoupler are both powered from the output of the converter via
a shunt regulator (U2) that is programmed to provide a 2 V rail.
Figure 5.
Circuit schematic
+Out
+S
R7 21.0 k
C3
R4
PS2701
U2
R5
1.00 k TLV431
R6
C1
1.65 k 470 pF
R11
36.5 k
R9
Vcc
+
U1
200 mV
U3
LM10 Gnd
+
R2
R8
4.02 k
–
SC
R3
2.55 k
C2
0.22 µF
R Load
–
R1
R10
1.24 k
–S
–Out
See Component Selection section below.
AN:205
vicorpower.com Applications Engineering: 800 927.9474
Page 3
Component Selection
Table 1 gives resistor values for some common output voltages. For applications that are
not listed formulas for calculating resistor values are also given.
Table 1.
Resistor values
Vout (nom)
(V)
Vout (max)
(V)
Vout (min)
(V)
R4
(kΩ)
R1
(kΩ)
R2
(kΩ)
R9
(kΩ)
3.3
3.63
2.97
0.091
18.7
3.57
2.05
5
5.5
4.5
0.2
34.0
3.57
3.74
8
8.8
7.2
0.39
60.4
3.57
6.65
12
13.2
10.8
0.68, 0.5 W
95.3
3.57
10.7
15
16.5
13.5
0.82, 0.5 W
124
3.57
13.7
24
26.4
21.6
1.5, 0.5 W
205
3.57
22.6
28
30.8
25.2
1.8, 1.0 W
237
3.57
26.7
36
39.6
32.4
2.2, 1.0 W
309
3.57
34.8
48
52.8
43.2
3.0,1.0 W
422
3.57
46.4
All resistors are ¼ W unless otherwise specified.
Vout(nom):
Nominal output voltage of the converter and point-of-load voltage
Vout(max): Maximum output voltage of the converter that supplies the load and lead / trace loss
Vout(min): Minimum output voltage of the converter typically set to 90% of Vout(nom)
Solving for R1
The value of R1 is governed by the following formula:
Equation 2.
R1 = 1 kΩ
Vout(max) - 1.23 V) Vout(nom)
1.23 V (Vout(max) - Vout(nom))
- 1 kΩ
Solving for R2
R2 can be calculated as follows, where VCESAT is the saturation voltage of the
optocoupler given by the manufacturer (0.3 V for the NEC PS2701):
Vout(min)1.23 V
Equation 3.
R2 =
Vout(min)
R1
AN:205
(
Vout(nom)
1-
1.23 V
Vout(nom)
)
+
vicorpower.com -VCESAT
1.23 V
1 kΩ
(
1-
Vout(min)
Vout(nom)
)
Applications Engineering: 800 927.9474
Page 4
Solving for R4
With different module output voltages R4 will need to be changed such that current
being fed into the TLV431 regulator is approximately 15 mA.
The following equations can be used to find the appropriate value for R4 and its power
dissipation PR4:
Equation 4.
Vout(nom) - 2 V
R4 =
15 mΑ
PR4 = (Vout(nom) 2 V) 15 mA
Solving for R9 and R10
The value of R10 should be 1.24 kΩ to obtain a reasonable value for the parallel
combination of R9 and R10. R9 can be calculated as follows:
Equation 5.
(
Vout(nom)
-1
R9
=
R10
1.245 V
)
Solving for C3
For good stability the bandwidth of a remote sense circuit must be lower than the
frequency where phase shift from the leads / traces becomes ­significant. The appropriate
integrator crossover frequency can be estimated with a first-order model of the leads /
traces. For many applications 200 Hz makes a good starting value (C3 = 0.68 µF). The
optimal value will depend on design requirements. Figure 6 can be used to find C3 once
the desired crossover frequency is known.
Figure 6.
Selecting Capacitor C3
Crossover frequency vs.
capacitance
100
C3 (uF)
10
1
0.1
0.01
10
100
1000
10000
fc (Hz)
AN:205
vicorpower.com Applications Engineering: 800 927.9474
Page 5
Solving for C2
C2 programs the ramp-up time of the remote sense circuit’s reference. To minimize
overshoot this should be longer than the 4 ms start up ramp of the converter (C2 = 0.22 µF). The effect of changing C2 is shown in the waveforms section.
The following table gives component values for a circuit configured for a point-of-load
voltage of 3.3 V.
Table 2.
Parts list for 3.3 V module
Ref Des
Part Description
Rating
R1
18.7 kΩ
¼W
R2
3.57 kΩ
¼W
R3
2.55 kΩ
¼W
R4
91 Ω
¼W
R5
1.0 kΩ
¼W
R6
1.65 kΩ
¼W
R7
21 kΩ
¼W
R8
4.02 kΩ
¼W
R9
2.05 kΩ
¼W
R10
1.24 kΩ
¼W
R11
36.5 kΩ
¼W
C1
470 pF
100 V
C2
0.22 µF
16 V
C3
0.68 µF
16 V
U1
NEC PS2701 (Digi-Key #PS2701-1-ND)
NA
U2
TI TLV431 (Digi-Key #296-10727-5-ND)
NA
U3
National LM10 (Digi-Key #LM10CWM-ND)
NA
Circuit Waveforms
Transient Response. Figures 7, 8, and 9 show the response to a load current step. C3 is
sized for a 200 Hz crossover frequency giving a clean transient response with no oscillation.
Figure 7.
Load step 0.5 A to 5 A to 0.5 A,
C3 = 0.64 µF, 300 µF at
point of load (V48C3V3E75B)
AN:205
vicorpower.com Applications Engineering: 800 927.9474
Page 6
Figure 8.
Load step 0.5 A to 5 A,
C3 = 0.64 µF, 300 µF at
point of load (V48C3V3E75B)
Figure 9.
Load step 5 A to 0.5 A,
C3 = 0.64 µF, 300 µF at
point of load (V48C3V3E75B)
Transient Response Improperly Sized C3. Figures 10 and 11 show the response to a load
step with C3 undersized. They illustrate how both C3 and the point-of-load capacitance
contribute to the circuit’s closed loop response.
Figure 10.
Load step 0.5 A to 5 A to 0.5 A,
C3 = 0.033 µF, 300 µF ­­­at
point of load (V48C3V3E75B)
AN:205
vicorpower.com Applications Engineering: 800 927.9474
Page 7
Figure 11.
Load step 0.5 A to 5 A to 0.5 A,
C3 = 0.033 µF, no point-of-load
capacitance (V48C3V3E75B)
Effect of C2 on Start up. Figure 12 shows a good intermediate value for C2 which
results in a reasonable start up time and eliminates overshoot. Depending on the
application C2 may need to be resized. In Figure 13, C2 is intentionally undersized
causing the reference to come up too fast and the point-of-load voltage to overshoot.
Figure 14 shows start up with C2 oversized resulting in a long delay before the nominal
voltage is reached.
Figure 12.
Start up C2 = 0.21 µF
(V48C3V3E75B)
Figure 13.
Start up C2 = 0.047 µF
(V48C3V3E75B)
AN:205
vicorpower.com Applications Engineering: 800 927.9474
Page 8
Figure 14.
Start up C2 = 1.0 µF
(V48C3V3E75B)
For more information on remote sense capabilities, please contact Vicor’s Applications
Engineers at 1-800-927-9474 or vicorpower.com/support for worldwide assistance.
The Power Behind Performance
Rev 2.1
12/13
vicorpower.com Applications Engineering: 800 927.9474
Page 9