FlatPAC Family 50 to 600 Watt AC-DC Switchers

FlatPAC Family
50 to 600 Watt
AC-DC Switchers
Application Notes
Functional and Mechanical Layout
Installation and Operation Guidelines
U-Series
Product Description
The FlatPAC family of user-definable offline power supplies provides a complete
power solution that incorporates one, two, or three standard Vicor DC-DC
converters and a front-end subassembly in a modular package. FlatPAC is available
with one, two, or three outputs and total output ratings of 50–600 W. These power
supplies feature an autoranging input, which automatically senses the input line
voltage and sets the power supply’s input range accordingly. FlatPAC’s unique
modular design accommodates over 10,000 different configurations.
FlatPAC power supplies that contain BatMod current source modules instead of
VI-200 converters are indicated by the suffix -BM following the FlatPAC part
number. BatMod converters provide a programmable output current, rather than a
regulated output voltage. Consequently, the output supervisory terminal functions
differ on FlatPACs with BatMod modules.
2
Application Notes
AC Mains and Supervisory Connections
MOD DIS –
MOD DIS +
AC OK –
AC OK +
BUS OK –
BUS OK +
AC Mains
Earth Ground
Internal
Supervisory
Circuits
(Optocouplers)
L1
2-Up
and
3-Up
1-Up
L2/N
GND
Product is internally fused
External Supervisory Functions (2-up and 3-up models only)
30mA max.
FlatPAC
MOD DIS Input. Apply a current of
1–30 mA to disable output. Forward
voltage drop of internal opto diode is
1.65 V max. at 30 mA max.
V
+
MOD DIS
+
AC OK and BUS OK Status Outputs.
Outputs low when OK.
Vce sat. = < 0.4 V @ 1.5m A. Maximum
external pullup is 70 Vdc. AC OK and
BUS OK signals are isolated and can
have different reference levels.
Disable
+
V
1.5mA
max.
r
+
AC OK
–
1.5mA
max.
+
V
–
r
+
BUS OK
–
3
Timing Diagram—Status Signals (2-up and 3-up models only)
VLINE > 90 (180)Vac
AC
Line
AC Line
Interrupted
AC OK
BUS OK
T0 T1
T2
T3
T4
Conditions: Full Load 90 (180)Vac, AC Line
Time Interval
T1-T0
T3-T2
T4-T2
T4-T3
Min
0
0
5
5
Typ
0.1
–
–
–
Max
1.0
–
–
–
Units
ms
ms
ms
ms
Notes
Ride-through time
Hold-up time
AC fail warning time
Output Sense and Trim (All models with VI-200s)
+ VOUT
+Out
+Sense
Trim
–Sense
R1
10K
VOUT RTN
–Out
R2
+Sense and –Sense must be connected locally or remotely (shown).
RESISTOR VALUES FOR TRIMMING STANDARD OUTPUT VOLTAGES
Nominal
5V
12 V 15 V
24 V 28 V
48 V Trim Range
Output Voltage
R1(KΩ)
.953
15.8
22.1
41.2
48.7
90.9
+10%, -10%
R2(KΩ)
90
90
90
90
90
90
+10%, -10%
Typical Applications (Models with BatMods only)
Battery
Charger
Programmable Current
or Voltage Source
+Out
+Out
+
VTRIM
I TRIM
I MON
External
Control
Functions
12–48V
Battery
+
VTRIM
I TRIM
I MON
–
–Out
–Out
External
Control
Functions
Load
–
4
Functional and Mechanical Layout
LU-Series
Single output
50-200 W
MU-Series
Single output
200-400 W
NU-Series
Single output
300-600 W
PU-Series
Dual output
100-400 W
QU-Series
Dual output
150-600 W
RU-Series
Triple output
150-600 W
FlatPAC units are shipped with pins 11-12
and 14-15 connected via jumper plugs
(Vicor P/N 02589) for local sense. For
remote sense, remove these connections
and connect pins 10-12 and 14-16, as
shown in the Output Sense and Trim
drawing on page 3.
2.540 ±0.030
(64,52 ±0,76)
Inputs
LU-Series
2.156 ±0.010
(54,76 ±0,25)
1.27
(32,26)
7
8
9
0.192 ±0.010
(4,88 ±0,25) 0.18
(4,57)
All FlatPAC models are available
with a conduction cooled flat plate
instead of the top heat sink. Contact
factory for outline drawings.
6.00
(152,4)
MU-, PU-Series
Inputs
1
2
3
4
5
6
7
8
9
MOD DIS–
MOD DIS+
AC OK–
AC OK+
BUS OK–
BUS OK+
AC in L1
AC in L2/N
Chassis Ground
3.83
(97,16)
+Power Out
+Out**
+Sense*
Trim*
–Sense*
–Out**
–Power Out
*On FlatPACs
containing BatMods:
12 VTRIM
13 I TRIM
14 I MON
**For local sense
connection only—
not for load
connection
2.281 ±0.010
(57,94 ±0,25)
1.17
(29,72)
7
8
9
0.199 ±0.010
(5,05 ±0,25) 0.18
(4,57)
Outputs
10
11
12
13
14
15
16
4.562 ±0.010
(115,87 ±0,25)
4.960 ±0.030
(125,98 ±0,76)
6.00
(152,4)
NU-, QU-, and RU-Series
7.380 ±0.030
(187,45 ±0,76)
1
2
3
4
5
6
7.000 ±0.010
(177,8 ±0,25)
4.710 ±0.010
(119,63 ±0,25)
5.48
(139,19)
7
8
9
1.93
(49,02)
2.290 ±0.010
(58,17 ±0,25)
0.190 ±0.010
(4,83 ±0,25) 0.18
(4,57)
6.00
(152,4)
5
All Models
Outputs
1.375 ±0.020
(34,91 ±0,51)
1.11
( 28,19)
0.50
(12,57)
LU-Series
9.245 ±0.030
(234,82 ±0,76)
OUTPUT 1
MOUNTING HOLE
ø 0.15 ±0.01 THRU
4 PLACES
#10 NUT*
#10 LOCK WASHER*
10
11
12
13
14
15
16
#10 WASHER*
USER OUTPUT
TERMINAL
#10 WASHER*
#10 NUT* TORQUED TO
25 in-lbs (2.8 N-m)
AT THE FACTORY
DO NOT LOOSEN
*SUPPLIED WITH FLATPAC
OUTPUT STUD CONNECTIONS
MU-Series
PU-Series
Notes:
+
OUTPUT 2
10
11
12
13
14
15
16
10
11
12
13
14
15
16
OUTPUT 1
MOUNTING HOLE
ø 0.15 ±0.01 THRU
5 PLACES
10
11
12
13
14
15
16
+
–
NU-Series
• Connect paralleled outputs as shown
(MU-, NU-, and QU-Series) for >40 A out.
• All output studs 10-32 UNF.
Torque to 20 in-lbs (2.3 N-m).
• Input supervisory terminals (1–6): use
mating connector Vicor P/N 33100,
AMP P/N 644083-6
• Output supervisory terminals (11–15):
use mating connector Vicor P/N 16385R,
AMP P/N 644083-5
• AMP Termination Tool Pistol Grip
Handle P/N 58074-1; with
interchangeable head P/N 58246-1
• Do not loosen bottom nut.
QU-Series
RU-Series
MOUNTING HOLE
ø 0.15 ±0.01 THRU
6 PLACES
16
16
10
11
12
13
14
15
16
10
11
12
13
14
15
16
–
OUTPUT 3
10
+
10
11
12
13
14
15
16
OUTPUT 2
10
OUTPUT 1
OUTPUT 1
16
10
11
12
13
14
15
16
10
11
12
13
14
15
16
OUTPUT 1
+
OUTPUT 2
10
10
11
12
13
14
15
16
–
+
–
6
Installation and Operation Guidelines
Fusing. The FlatPAC’s internal fuses are not user-replaceable. Please return the
unit to vendor if servicing is necessary.
Grounding. To satisfy IEC 950 Class I grounding requirements, connect a ground
lead to the terminal marked
(GND). For one-up FlatPAC models (max. output
200 W), use 1.5 mm2 / #16 AWG wire; for two-up and three-up models (max. output
400 W and 600 W), use 2.5 mm2 / #14 AWG wire.
Input Voltage Connections. Connect the line voltage to L1 (hot) and L2N (neutral).
For one-up FlatPAC models (max. output 200 W), use #16 AWG input wire; for twoup and three-up models (max. output 400 W and 600 W), use #14 AWG input wire.
Recommended connector screw torque is 5 to 7 in-lbs (0.5 to 0.8 N-m).
Recommended strip length is 8 mm. Use your FlatPAC model only with the
corresponding input voltages and frequencies shown in the table below.
Model
90 –132 Vac
180 – 264 Vac
C– Grade
VI– ■ U– C ■
47– 63 Hz
47– 63 Hz
I– Grade
VI– ■ U– I ■
47– 440 Hz
47– 440 Hz
Output Wire Gauge. Use the output wire gauge that corresponds to the output
current of your FlatPAC unit, below: Do not loosen bottom nut.
100 A–160 A : #2 AWG
30 A–50 A : #8 AWG
10 A–15 A : #14 AWG
75 A–100 A : #4 AWG
20 A–30 A : #10 AWG
6 A–10 A : #16 AWG
50 A–75 A : #6 AWG
15 A–20 A : #12 AWG
0 A–6 A : #18 AWG
Output Voltage Trimming. Do not trim the outputs higher than 110% of their
nominal output voltage. When an output is trimmed up, do not exceed its maximum
rated output power.
Operating Temperature. Do not allow the FlatPAC to exceed its maximum
operating temperature, which is reached when the heat sink is 85°C. (Full power can
be delivered up to this temperature.) Heat sink temperature is a function of the
output power and voltage of the supply, ambient temperature, and airflow across the
heat sink. Refer to the Vicor Applications Manual to determine the maximum ambient
temperature for your application. Always use worst-case conditions when
calculating operating temperature. Note 1: To ensure proper heat transfer from the
internal module(s) to the heat sink, the mounting holes through the heat sink (2, 3,
and 4 holes on one-, two-, and three-up models, respectively) must contain torqued
screws at all times during operation, whether or not the unit is mounted. If the unit is
operated unmounted, insert a #6 or metric panhead screw through each hole from
below and secure with a nut on top, torqued to 6 in-lbs (0.7 N-m). Note 2: All
FlatPAC models are available with a conduction cooled flat plate instead of the top
heat sink. Contact factory for outline drawings.
7
Input/Output Retrofit Connections. A hardware kit available from Vicor allows
the input and output supervisory terminals to be connected in the same manner as
for the earlier style FlatPAC (two-up model only). The retrofit output terminals are
sized to accept AMP Faston® insulated receptacle #2-520184-2.
Input Retrofit Kit
Part Number: 14136
Output Retrofit Kit
Part Number: 14137
For More Information
The Vicor Applications Manual and product data sheet contain complete information
about FlatPAC AC-DC power supplies. To receive literature or to consult an
applications engineer about installation or operation of this product, contact your
nearest Vicor office or visit the Vicor Website. (See back panel.)
(Bitte lesen Sie die Sicherheits-Vorschriften auf Seite 8.)
“AMP” and “Faston” are registered trademarks of AMP, Incorporated, Harrisburg, PA.
8
Sicherheits-Vorschriften
Sicherungen. Die internen Sicherungen im FlatPAC können nicht vom Anwender
ausgetauscht werden. Für Servicearbeiten schicken Sie das Teil bitte an den Händler
zurück.
Erdung. Um den IEC 950 Klasse I Erdungsforderungen zu entsprechen, muß ein
Erdungskabel an den Anschluß
(GND) angeschlossen werden. Für FlatPAC
Modelle mit einem Modul (max. Leistung 200 W) benutzen Sie bitte 1.5 mm2 AWG
16- und für Modelle mit 2 und 3 Modulen (max. Leistung 400 W und 600 W) bitte 2.5
mm2 AWG 14-Kabel.
Betriebstemperatur. Die maximale Betriebstemperatur des FlatPAC-Gerätes darf
nicht überschritten werden. Dies ist gegeben, wenn der Kühlkörper eine Temperatur
von 85 Grad Celsius erreicht hat. Die Kühlkörpertemperatur ist eine Größe, die sich
aus der Ausgangsleistung und Spannung der Stromversorgung, der
Umgebungstemperatur und der Luftzirkulation über dem Kühlkörper ergibt. Bitte
bestimmen Sie mit Hilfe des Vicor Applikationshandbuches die maximale
Umgebungstemperatur Ihrer Applikation.
Weitere Informationen. Das Vicor Applications Manual und Produkt-Datenblätter
enthalten ausführliche Informationen über FlatPAC AC-DC Wandler. Fordern Sie
bitte Unterlagen bei Vicor oder Ihrer nächsten Vicor Vertretung an.
Visit Vicor’s Website at:
vicorpower.com
Vicor Corporation
Andover, MA, U.S.A
Tel: 800-735-6200
Fax: 978-475-6715
Chicago, IL
Tel: 630-769-8780
Fax: 630-769-8782
Sunnyvale, CA
Tel: 408-522-5280
Fax: 408-774-5555
Vicor France
Tel: +33-1-3452-1830
Fax: +33-1-3452-2830
Vicor Italy
Tel: +39-02-2247-2326
Fax: +39-02-2247-3166
Vicor Hong Kong
Tel: +852-2956-1782
Fax: +852-2956-0782
Vicor Germany
Tel: +49-89-962-439-0
Fax: +49-89-962-439-39
Vicor U.K.
Tel: +44-1276-678-222
Fax: +44-1276-681-269
Vicor Japan Co., Ltd.
Tel: +81-3-5487-3880
Fax: +81-3-5487-3885
Printed in U.S.A.
Pt. No. 24436
Rev 6.2