Datasheet - Weidmuller

Datasheet
Varitector
High Density Surge Protection
NEW
All Varitector models include high quality field connections and are grounded via the DIN-rail. A combination
of gas discharge tubes, varistors and suppression
diodes in single or multi-stage configuration are used
to protect nominal voltages between 5 VDC and
230 VAC.
Status monitoring options help ensure continued
protection. VSPC modules feature local and remote
signaling of arrestor status, while many of the VSSC6
models have an option for an integral LED, which
signals when module replacement is required.
The Varitector range complements the Weidmuller’s
SPD II range of surge protectors for low voltage
power distribution applications. Taken together,
these products provide extensive DIN-rail mounted
surge protection capability for industrial installations.
Weidmuller’s Varitector range offers low-cost, highdensity surge protection options for lightning and
other transient protection in industrial control equipment. UL (497B) approved, Varitector is ideally suited
for signaling (I/O) applications such as analog current
and voltage loops, DC and AC status signals and a
wide variety of serial interface and telephone network
installations. Models for hazardous area and SIL
options are available.
The Varitector range includes two construction
formats, VSSC and VSPC. VSSC models feature
4- or 6-pole rugged, compact terminal-sized housings.
VSPC models feature a two part, plug-and-base
format for easy arrestor replacement without re-wiring.
Both formats are DIN-rail mounted, rated for discharge
currents up to 20kA (8/20μs), and provide a combination of wire-to-ground and wire-to-wire protection.
Features:
• T
wo formats – high density terminal (VSSC),
or pluggable, replaceable arrestor (VSPC)
• Imax = 20kA (8/20µs)
• Local or remote indication options for arrestor status
• Grounding via DIN-rail or field connection
• UL497B approval
• Color coded line voltage identification
• A
ccessories include test meter and EMC Set
(easy shield connector)
Weidmuller, Canada
Weidmuller, Mexico
Weidmuller, United States
10 Spy Court
Markham, Ontario L3R 5H6
Telephone: (800) 268-4080
Facsimile: (877) 300-5635
Email: [email protected]
Website: www.weidmuller.ca
Blvd. Hermanos Serdán 698
Col. San Rafael Oriente
Puebla, Puebla, Mexico
C.P. 72029
Telephone: 01 222 2686267
Facsimile: 01 222 2686219
Email: [email protected]
Website: www.weidmuller.com.mx
821 Southlake Blvd.
Richmond, Virginia 23236
Telephone: (800) 849-9343
Facsimile: (804) 379-2593
Email: [email protected]
Website: www.weidmuller.com
Overview
VARITECTOR SPC
VARITECTOR SPC
Pluggable surge protection for the
measurement and control industry
VARITECTOR SPC
Weidmuller's VARITECTOR SPC
pluggable surge protection is remarkable
for its combination of extremely high
protective functionality and compact
dimensions. It is suited for use in
measurement and control circuits.
The size is made possible by the seletion
of INSTA dimensions, with a width of
17.8 mm (1TE).
Two versions are available:
• VSPC: a surge protector with no
monitoring function
• VSPC R: a surge protector with
monitoring function
The base components are plugged in to
form a direct earthing contact via the
mounting rail. Thus you save time during
the connection. The VARITECTOR SPC
series is optimally designed for compact
installation locations in process
automation, industrial automation or
building automation. The two-stage
surge-protection base components are
equipped with gas discharge tubes,
suppressor diodes (TVS) and decoupling
components. Individual protective
components (such as gas-filled spark
gaps, varistors and suppressor diodes)
supplement this product line. IEC 62305
requires that a periodic inspection of
surge protection products be conducted.
The functionality of all VARITECTOR SPC
modules can be tested using testing
equipment (such as the V-TEST Basic)
that is available separately. The
VARITECTOR SPC R modules also
feature an internal monitoring function.
The green LED signals when the
protection function is ready. The red LED
signals an error. VARITECTOR SPC Up to
ten modules can be wired together in
series. The modules alert an evaluative
module (the VSPC CONTROL UNIT) in
the event of an error. VARITECTOR SPCseries surge protection is available with
rated voltages of 5 V, 12 V, 24 V, 48 V
and 60 V. The product's voltage level is
Color-coded on the pluggable arrester.
An earthing contact is established by
snapping onto an earthed TS35 rail.
The TS35 must be earthed in order to
ensure safe power discharging via the
terminals of up to 20 kA (8/20 µs) and
2.5 kA (10/350 µs). The rail must be
screwed onto the earthed mounting plate
for reasons of EMC. In order to optimize
the protective function, a PE-contact
connection should be made over the
VSPC module every 60 cm for
equipotential bonding. The pluggable
protective element can be pulled out
during operations without interrupting the
measurement circuit. A testing
instrument, available as a Weidmuller
accessory, allows you to test the
protective element in compliance with
the IEC 62305-3 directive. The accessory
also includes a simple mechanism for
applying the wire shield.
Overview of model types
A VARITECTOR SPC (VSPC) consists of a
pluggable component and a separate
base component (VSPC BASE).
Explanation of terms:
CL = current loop / analog signals
SL = symmetric loop - for binary signals
VSPC 2CL (CL = current loop) is a twostage protective combination with a gas
discharge tube and a suppressor diode
located between the current paths. This
VSPC 2CL limits the surge voltage within
two analog signal circuits (such as for
current loops). This pluggable component
can be inserted into the base (VSPC
BASE 2CL). The base (VSPC BASE FG
2CL) is used when working with signal
circuits which are not earthed. The VSPC
2CL HF is used in order to avoid
influencing high-frequency signal circuits
(this also includes the VSPC RS485 and
the VSPC UK0). This protective
combination is also inserted into the base
mentioned above.
Monitoring function
The VSPC 2CL R products feature
monitor and alert functions. Despite the
alert function, there are still two channels
2
VARITECTOR SPC
available for current loops in a single
housing. The special VSPC BASE 2CL R
and VSPC BASE 2CL FG R bases
transfer the alert function to a 2-pole
screw/plug-in connection in the bases
and to the VSPC CONTROL UNIT.
The VSPC 1CL is a two-stage protective
combination with a gas discharge tube
and a suppressor diode located between
the current paths. This VSPC 1CL limits
the surge voltage within one analog
signal circuits (such as for current
loops). This pluggable component can be
inserted into the base (VSPC BASE 1CL).
The base (VSPC BASE FG 1CL) is used
when working with signal circuits which
are not earthed.
Monitoring function
The VSPC 1CL R products feature
monitor and alert functions. All channels
remain despite the alert function. The
special VSPC BASE 1CL R and VSPC
BASE 1CL FG R bases transfer the alert
function to a 2-pole screw/plug-in
connection in the bases and to the
VSPC CONTROL UNIT.
The VSPC 4SL is a two-stage protective
combination with a gas discharge tube
and a suppressor diode from the current
3
Overview
path to the PE. This VSPC 4SL limits the
surge voltage within four binary signal
circuits (such as for alert contacts). This
pluggable component can be inserted
into the base (VSPC BASE 4SL). The
base (VSPC BASE FG 4CL) is used when
working with signal circuits which are not
earthed.
VSPC CONTROL UNIT.
Monitoring function
The VSPC 4SL R products feature
monitor and alert functions. Despite the
alert function, there are still channels
available for the four binary signal circuits
in a single housing. The special VSPC
BASE 4SL R base transfers the alert
function to a 2-pole screw/plug-in
connection in the base and to the
VSPC CONTROL UNIT.
The VSPC 3/4WIRE is a two-stage
protective combination with a gas
discharge tube and a suppressor diode
from the current path to the GND. This
VSPC 3/4WIRE limits the surge voltage
within four temperature-measurement
circuits (such as for DMS or PT100/100
sensors). For non-earthed measurement
circuits, we recommend using the base
(VSPC BASE FG 4CL).
The VSPC 2SL is a two-stage protective
combination with a gas discharge tube
and a suppressor diode from the current
path to the PE. This VSPC 2SL limits the
surge voltage within two binary signal
circuits (such as for alert contacts).
This pluggable component can be
inserted into the base (VSPC BASE 2SL).
The base (VSPC BASE 2CL FG) is used
when working with signal circuits which
are not earthed.
VSPC MOV 2CH , VSPC TAZ 2CH und
VSPC GDT 2CH
Four cables can be protected with the
2CH modules. By wiring the connections
differently, either two no-voltage signal
lines or four binary signal lines can be
protected. Two three-pole gas discharge
tubes (GDTs) are used for the VSPC GDT
2CH. This universal protective circuitry
limits the voltage between the signal lines
and also between each signal line and the
PE.
Monitoring function
The VSPC 2SL R products feature
monitor and alert functions. Despite the
alert function, there are still channels
available for the two binary signal circuits
in a single housing. The special VSPC
BASE 2SL R base transfers the alert
function to a 2-pole screw/plug-in
connection in the base and to the
Overview
VARITECTOR SPC
Applications
RS 422/485
The VSPC RS485 is a two-stage
protective combination with a gas
discharge tube and a suppressor diode
located between the current paths. This
VSPC RS485 limits the surge voltage
within two high-frequency signal
circuits. This pluggable component can
be inserted into the base (VSPC BASE
2CL). The base (VSPC BASE FG 2CL) is
used when working with signal circuits
which are not earthed.
The VSPC MOV 2CH and TAZ 2CH offer
one-stage protection with a varistor
(MOV) or suppressor diode (TAZ or TVS)
between the current paths. This makes it
possible to protect a no-voltage (floating)
signal circuit. Two binary signal circuits
can also be protected if terminals 1 and
7 are assigned to GND / PE. These
VSPC pluggable components are
inserted into the base (VSPC BASE
2/4CH). The base (VSPC BASE 2/4CH
FG) is used when working with signal
circuits which are not earthed..
24 V
VSPC 1CL PW (power and signal 1CL)
offers combined protection that is suitable
for the 24 VDC power supply and the
current loops within a device.
This VSPC protects sensors with an
additional 24 VDC.
Monitoring function
The VSPC RS485 R product features
monitoring and alert functions. Despite
the alert function, there are still two
channels available for current loops in a
single housing. The special VSPC BASE
2CL R and VSPC BASE 2CL FG R bases
transfer the alert function to a 2-pole
screw/plug-in connection in the bases
and to the VSPC CONTROL UNIT.
Earthing unit and test plug
The earthing unit can be used during
installation to short out the connected
wires to earth. The earthing unit is swapped
out for a VSPC pluggable component
before the initial commissioning. The test
plug has 2.3 mm sockets. These sockets
can be used by a meter to check the
connected measurement circuit..
The pluggable INSTA housing was
created in compliance with DIN 43880.
It consists of a lower section (the VSPC
BASE) and a pluggable component (the
VSPC). The VSPC BASE is made from
black PA6.6 V0. The pluggable
component is made from red PA6.6 V0.
The temperature range is from -40 °C to
+ 70 °C. The VSPC series has been
tested to comply with IEC 61643-21
04/2008 and EN 61643-21. Modules
were tested with categories C1, C2 and
C3: with quick-rising edges with up to
300 pulses. Category D1 describes high
power testing (10/350 μs), so that the
VSPC can be used according to IEC
62305-4. The base and pluggable
components are Color coded according
to the voltage level. This makes
installation easier.
Color coding
The pluggable components transfer their
coding to the base element when they
are plugged in for the first time. The
voltage levels are also labelled with
Colored Dekafix markers applied to the
VSPC pluggable component. This gives
you a better overview within the electrical
cabinet.
Voltage level
≤ 12 V
Color
green
24 V Binary
24 V Analog
48 V
≥ 60 V
Special function
blue
yellow
red
violet
white
4
VARITECTOR SPC
Remote error diagnostics
Test possibility / V-TEST
Because the modules are pluggable, it is
possible to test the VSPC visually or by
using a V-TEST BASIC testing device.
The VSPC can be easily tested; the user
needs only to insert the VSPC pluggable
component into the V-TEST BASIC. The
result is then shown on the display.
The VSPC R modules also feature an
internal monitoring function for the
arrester. An error is the displayed at the
defective module. The VSPC CONTROL
UNIT can then transfer an alert to the
control room.
Reoccurring tests / V-TEST
Monitoring
The IEC 62305-3 requires testing and
maintenance for lightning protection
systems. This includes the testing of the
arresters used in the system.
Class of
protection
Interval for
complete testing
I
2 years
Interval for
visual
inspection
1 year
II
III/IV
4 years
6 years
2 years
3 years
Caution! These periodic inspections may
be extended with stricter requirements
pertaining to special applications or
regions.
5
Overview
When the VSPC module labelled "R" is
inserted into the corresponding "R" base
component, it is then possible to use the
outage alert function via a two-pole plug.
This screw/plug-in connection has a
clamping range from 0.5 to 1.5 mm².
The wire stripping length is 6 to 6.5 mm.
A screwdriver with a 2 mm blade width
is used to turn the screw. The VSPC Rs
are connected in series to the VSPC
CONTROL UNIT evaluative module.
Up to ten VSPC Rs can be connected in
series to the VSPC CONTROL UNIT.
The evaluative module is supplied with
24 VDC. It is then responsible for the
switching and for the voltage supply to
the VSPC modules. A no-voltage (floating)
CO contact can then be used to alert in
the event of an outage. The error is also
displayed directly on the module when
the LED changes Color from green to
red. An automatic reset is carried out by
the VSPC CONTROL UNIT within one
minute after the failed VSPC pluggable
component is replaced.
Installation
The VSPC series is appropriate for
protecting signal circuits. In order to
achieve a complete protective strategy
for the facility, the power feed must be
protected against Class-II surge voltages
(for example, by using the PU II series).
For existing lightning protection facilities,
Class-I protection must be used (for
example, by using the PU I series).
Class-II protection (for example, the PU II)
is sufficient when there is no lightning
protection facility.
Fusing
The VSPC surge protection modules are
designed so that they are decoupled
between the individual protective stages.
The following must be observed when
providing fuse protection externally:
• Max. rated current
• Deratings curve
• Type of installation
• Application
O v e r v i e w VARITECTOR SPC
Discharge capacity
General technical data
Accessories
Testing is conducted using voltage
and current pulses according to the
IEC 61643-21 standard concerning surge
protection in networks which process
signals.
Storage temperature -40 °C…+80 °C
Operating temperature: -40 °C…+70 °C
Air humidity 5%…96% RH with no
condensation
Material: V0, IP20
Markers
The VSPC BASE lower section can be
labelled with Dekafix-5 markers. The
VSPC pluggable modules are Color
coded with Dekafix-5 markers according
to their rated voltage.
Cate- Testing
gory pulse
C1
Quickrising
edge
Surge
voltage
0.5 - 2 kV
with
1.2/50 µs
Surge
Pulse Type
current
0.25 - 1 kA 300 Surge
mit
voltage
8/20 µs
arrester
C2
Quickrising
edge
2 - 10 kV 1 - 5 kA
with
mit
1.2/50 µs 8/20 µs
C3
Quickrising
edge
≥ 1 kV
with
1 kV/µs
10 - 100 A 300
mit
10/10000 µs
Surge
voltage
arrester
D1
High
power
≥ 1 kV
0.5 - 2.5 kA 2
mit 10/350
µs
Arrester for
lightning
current and
surge voltages
10
Surge
voltage
arrester
Category C reflects the interference
pulses with quick-rising edges and
minimized power. Category D uses
quick-rising edges and high power to
detail the interference pulses. This energy
simulates the high-power load that stems
from coupled partial lightning currents.
Connection: screw connection
screwdriver blade: 0.6 x 3.5 DIN 5264
(for example, 0.6 x 3.5 x 200, Part No.
9010110000)
rated torque: 0.5 Nm
max. torque: 0.8 Nm
stripping length: 7 mm
solid: 0.5…4 mm²
flexible: 0.5…2.5 mm²
wire-end ferrule with plastic collar:
0.5...2.5 mm²
Remote signalling connection:
screw connection
screwdriver blade: 0.4 x 2.0 DIN 5264
(for example, SD 0.4 x 2.0 x 60, Part No.
9037160000)
max. torque: 0.2 Nm
stripping length: 6...6.5 mm
solid: 0.5...1.5 mm²
Shield connection
EMC SET, order number 1067470000
The EMC set consists of a connection
component with shielding and a cable tie
covered with shielding braid. The RT-1
cable tie tool (order number 1296000000)
can be used to fasten the cable ties
professionally.
V-Test
Testing device for functional tests of the
pluggable VSPC, PU II and PU I surge
protection.
Dimensions
length : 90 mm
length with remote signalling contact:
98 mm
height: 69 mm
width: 17.8 mm
6
VARITECTOR SPC
Choice of device depending on the interface
VARITECTOR SPC – Choice of device depending on the interface
Interface
Pluggable arrestor
Pluggable arrestor
with operation message (R)
VSPC 2CL 24Vdc 0,5A R
VSPC 1CL 12Vdc 0,5A R
VSPC 2CL 24Vdc 0,5A R
VSPC 1CL 12Vdc 0,5A R
Part No.
Arrestor
8951480000
8951540000
8951480000
8951540000
Part No.
Base
8951710000
8951730000
8951710000
8951730000
Part No.
Base floating ground (FG)
8951720000
8951740000
8951720000
8951740000
0(4) … 20 mA
0(4) … 20 mA
0 … 10 V
0 … 10 V
ADSL
ADVANT
ARCNET (Plus)
ASI
8951680000
8951670000
8860350000
8860360000
8951470000
8951470000
8951540000
8951690000
8951690000
8951690000
8951690000
8951710000
8951710000
8951720000
8951720000
8924270000
8924270000
8924290000
8924270000
8924270000
8924270000
8924270000
VSPC 2CL HF 5Vdc R
VSPC R485 2ch R
PU III R 48Vdc
PU III R 24Vdc
VSPC 2CL 12Vdc 0,5A R
VSPC 2CL 12Vdc 0,5A R
VSPC 1CL 12Vdc 0,5A R
VSPC 2CL HF 12Vdc R
VSPC 2CL HF 12Vdc R
VSPC 2CL HF 12Vdc R
VSPC 2CL HF 12Vdc R
8951710000
8951710000
8951730000
8951710000
8951710000
8951710000
8951710000
8951720000
8951720000
8951740000
8951720000
8951720000
8951720000
8951720000
8924270000
8924270000
8924270000
8924290000
8924290000
VSPC 2CL HF 12Vdc R
VSPC 2CL HF 12Vdc R
VSPC 2CL HF 12Vdc R
VSPC 1CL 12Vdc 0,5A R
VSPC 1CL 24Vdc 0,5A R
8951690000
8951690000
8951690000
8951540000
8951550000
8951710000
8951710000
8951710000
8951730000
8951730000
8951720000
8951720000
8951720000
8951740000
8951740000
VSPC 1CL 5Vdc 0,5A
8924420000 8924730000 8924290000
VSPC 1CL 5Vdc 0,5A R
8951530000
VSPC Uko
8924660000 8924710000 8924270000
VSPC 2CL HF 5Vdc
8924430000 8924710000 8924270000
VSPC 2CL HF 5Vdc R
8951680000
FIPIO/FIPWAY
VSPC 2CL HF 5Vdc
8924430000 8924710000 8924270000
VSPC 2CL HF 5Vdc R
8951680000
Genius I/O Bus
VSPC 2CL 12Vdc 0,5A
8924440000 8924710000 8924270000
VSPC 2CL 12Vdc 0,5A R
8951470000
Hart
VSPC 1CL 24Vdc 0,5A
892448 0000 8924730000 8924290000
VSPC 1CL 24Vac 0,5A R
8951560000
HDSL
VSPC Uko
8924660000 8924710000 8924270000
IEC-BUS
VSPC 2CL HF 5Vdc
8924430000 8924710000 8924270000
VSPC 2CL HF 5Vdc R
8951680000
8924660000 8924710000 8924270000
ISDN Basic connec- VSPC Uko
tion (Uk0-Bus)
8924570000 8924740000 8924300000
Cathodic corrosion VSPC GDT 2ch 90V20kA
prevention
LON (Works)
VSPC 1CL 48Vac 0,5A
8924520000 8924730000 8924290000
LRE Networks
VSPC 2CL HF 5Vdc
8924430000 8924710000 8924270000
VSPC 2CL HF 5Vdc R
8951680000
LUXMATE-Bus
VSPC 2CL HF 24Vdc
8924510000 8924710000 8924270000
VSPC 2CL HF 24Vdc R
8951700000
VSPC 1CL 24Vac 0,5A
8924500000 8924730000 8924290000
VSPC 1CL 24Vdc 0,5A R
8951550000
M-Bus (Remote
readout of counter)
MODBUS(-PLUS)
VSPC 2CL HF 12Vdc
8924460000 8924710000 8924270000
VSPC 2CL HF 12Vdc R
8951690000
MPI-Bus
VSPC R485 2ch
8924670000 8924710000 8924270000
N1 LAN
VSPC 2CL HF 5Vdc
8924430000 8924710000 8924270000
VSPC 2CL HF 5Vdc R
8951680000
N2 Bus
VSPC 2SL 5Vdc 0,5A
8924210000 8924720000 8924280000
VSPC 2SL 5Vdc 0,5A R
8951610000
P-NET
VSPC 2CL HF 12Vdc
8924460000 8924710000 8924270000
VSPC 2CL HF 12Vdc R
8951690000
VSPC 1CL 12Vdc 0,5A
8924450000 8924730000 8924290000
VSPC 1CL 12Vdc 0,5A R
8951540000
Procontic CS31
VSPC 2CL HF 12Vdc
8924460000 8924710000 8924270000
VSPC 2CL HF 12Vdc R
8951690000
Procontic T200
VSPC 2CL HF 12Vdc
8924460000 8924710000 8924270000
VSPC 2CL HF 12Vdc R
8951690000
8924430000 8924710000 8924270000
VSPC 2CL HF 5Vdc R
8951680000
Profibus DP (FMS) VSPC 2CL HF 5Vdc
VSPC 2CL HF 12Vdc
8924460000 8924710000 8924270000
VSPC 2CL HF 12Vdc R
8951690000
VSPC 2CL HF 12Vdc
8924460000 8924710000 8924270000
VSPC 2CL HF 12Vdc R
8951690000
Process-Bus,
Panel-Bus
8924550000 8924740000 8924300000
PT100
VSPC 3/4WIRE 24VDC
P-Bus
PU III R 24Vdc
8860360000
PU III R 24Vdc
8860360000
PSM-EG-RS422… VSPC 2CL HF 12Vdc
8924460000 8924710000 8924270000
VSPC 2CL HF 12Vdc R
8951690000
PSM-EG-RS485… VSPC 2CL HF 12Vdc
8924460000 8924710000 8924270000
VSPC 2CL HF 12Vdc R
8951690000
RACKBUS
VSPC 2CL HF 5Vdc
8924430000 8924710000 8924270000
VSPC 2CL HF 5Vdc R
8951680000
VSPC 2CL HF 12Vdc
8924460000 8924710000 8924270000
VSPC 2CL HF 12Vdc R
8951690000
RS 422A, V.11,
X.27, RS 423A
RS 449
VSPC 2CL HF 12Vdc
8924460000 8924710000 8924270000
VSPC 2CL HF 12Vdc R
8951690000
RS 485
VSPC R485 2ch
8924670000 8924710000 8924270000
VSPC R485 2ch R
8951670000
RS-232-C/V.24
VSPC 2CL HF 12Vdc
8924460000 8924710000 8924270000
VSPC 2CL HF 12Vdc R
8951690000
SDLC
VSPC 2CL HF 12Vdc
8924460000 8924710000 8924270000
VSPC 2CL HF 12Vdc R
8951690000
SDSL
VSPC Uko
8924660000 8924710000 8924270000
SecuriLan-LON-Bus VSPC 1CL 12Vdc 0,5A
8924450000 8924730000 8924290000
VSPC 1CL 12Vdc 0,5A R
8951540000
SHDSL
VSPC Uko
8924660000 8924710000 8924270000
SINEC L1
VSPC 2CL HF 5Vdc
8924430000 8924710000 8924270000
VSPC 2CL HF 5Vdc R
8951680000
SINEC L2 DP
VSPC 2CL HF 5Vdc
8924430000 8924710000 8924270000
VSPC 2CL HF 5Vdc R
8951680000
Profibus DP
VSPC R485 2ch
8924670000 8924710000 8924270000
VSPC R485 2ch R
8951670000
T-DSL
VSPC Uko
8924660000 8924710000 8924270000
Telephone analog
VSPC Uko
8924660000 8924710000 8924270000
TTY, 0(4) - 20 mA
VSPC 2CL 24Vdc 0,5A
8924470000 8924710000 8924270000
VSPC 2CL 24Vdc 0,5A R
8951480000
U-BUS
VSPC GDT 2ch 90V20kA
8924570000 8924740000 8924300000
VDSL
VSPC Uko
8924660000 8924710000 8924270000
V.35
VSPC 2CL HF 5Vdc
8924430000 8924710000 8924270000
VSPC 2CL HF 5Vdc R
8951680000
X.21/X.24
VSPC 2CL HF 12Vdc
8924460000 8924710000 8924270000
VSPC 2CL HF 12Vdc R
8951690000
X.25/X.31
VSPC 2CL HF 12Vdc
8924460000 8924710000 8924270000
VSPC 2CL HF 12Vdc R
8951690000
This tables contains recommendations for the choice of device. Our technical consultants will be glad to assist you with your individual requirements.
8951730000
8951740000
8951710000
8951710000
8951710000
8951730000
8951720000
8951720000
8951720000
8951740000
8951710000
8951720000
8951710000
8951710000
8951730000
8951720000
8951720000
8951740000
8951710000
8951710000
8951710000
8951770000
8951710000
8951730000
8951710000
8951710000
8951710000
8951710000
8951710000
8951720000
8951720000
8951720000
8951780000
8951720000
8951740000
8951720000
8951720000
8951720000
8951720000
8951720000
8951710000
8951710000
8951710000
8951710000
8951720000
8951720000
8951720000
8951720000
8951710000
8951710000
8951710000
8951710000
8951720000
8951720000
8951720000
8951720000
8951730000
8951740000
8951710000
8951710000
8951710000
8951720000
8951720000
8951720000
8951710000
8951720000
8951710000
8951710000
8951710000
8951720000
8951720000
8951720000
BITBUS
BLN (Building
Level Network)
CAN-Bus
C-BUS
CC-LINK
Data Highway
(Plus), DH+
Datex-P
DeviceNet
DIN Detecting Bus System
Dupline/Miniplex
EIB (European
Installation Bus)
ET 200
E1
7
VSPC 2CL 24Vdc 0,5A
VSPC 1CL 24Vdc 0,5A
VSPC 2CL 24Vdc 0,5A
VSPC 1CL 24Vdc 0,5A
VSPC Uko
VSPC 2CL HF 5Vdc
VSPC R485 2ch
PU III R 48Vdc
PU III R 24Vdc
VSPC 2CL HF 12Vdc
VSPC 2CL HF 12Vdc
VSPC 1CL 24Vdc 0,5A
VSPC 2CL HF 12Vdc
VSPC 2CL HF 12Vdc
VSPC 2CL HF 12Vdc
VSPC 2CL HF 12Vdc
Part No.
Arrestor
8924470000
8924480000
8924470000
892448 0000
8924660000
8924430000
8924670000
8860350000
8860360000
8924460000
8924460000
892448 0000
8924460000
8924460000
8924460000
8924460000
Part No.
Base
8924710000
8924730000
8924710000
8924730000
8924710000
8924710000
8924710000
Part No.
Base floating ground (FG)
8924270000
8924290000
8924270000
8924290000
8924270000
8924270000
8924270000
8924710000
8924710000
8924730000
8924710000
8924710000
8924710000
8924710000
VSPC 2CL HF 12Vdc
VSPC 2CL HF 12Vdc
VSPC 2CL HF 12Vdc
VSPC 1CL 12Vdc 0,5A
VSPC 1CL 24Vdc 0,5A
8924460000
8924460000
8924460000
8924450000
892448 0000
8924710000
8924710000
8924710000
8924730000
8924730000
VARITECTOR SPC
8
V
VA
AR
RIIT
TE
EC
CT
TO
OR
RS
SP
PC
C
VSPC 1CL – Protection for one analog
signal
• O
ptional monitoring function with status indicator and
alert function
• Pluggable arrester (plug-in / disconnect interruption-free
and impedance neutral)
• Testable with V-TEST instrument
• Version with non-earthed PE connection for avoiding
potential differences
• Usable in accordance with installations standard
IEC 62305
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
for all VSPC 1CL
Dielectric strength with FG against PE
> 500 V
Volume resistivity per path
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Surge strength C1
Surge strength C2
Surge strength C3
Surge strength D1
2.2 Ω
Mode 2
C1; C2; C3; D1
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
1 kA 10/350 µs
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp. (10/350 μs) wire-wire / wire-PE / GND-PE
Type of connection
Storage temperature
Ambient temperature (operational)
Rel. humidity
2.5 kA / 2.5 kA / 2.5 kA
10 kA / 10 kA / 10 kA
2.5 kA / 2.5 kA / 2.5 kA
Pluggable in VSPC BASE
-40 °C…+80 °C
-40 °C…+70 °C
5 %…96 % RH
Degree of protection
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
IP20
Dimensions of complete module (arrester + base element) Without telecomm. contact With telecomm. contact (R)
Length x width x height
90 x 17.8 x 69 mm
98 x 17.8 x 69 mm
Note
Base elements / base to arresters
Ordering Data for Base
Type
Base element, direct earthing
Base element, indirect earthing via spark gap (FG, floating ground)
Base element, direct earthing with remote alert
Base element, indirect earthing with remote alert
Note: The basis elements are to be ordered separately
9
Qty.
1
Part No.
8924730000
1
1
1
8924290000
8951730000
8951740000
VARITECTOR SPC
VSPC 1CL – Arrester / plug-in elements
Ordering Data
VSPC 1CL 5 V DC
VSPC 1CL 12 V DC
VSPC 1CL 24 V DC
5 V DC
12 V DC
24 V DC
6.4 V DC
15 V DC
28 V DC
450 mA
450 mA
450 mA
UN 250 V AC 0.1 A 1CO at VSPC R
UN 250 V AC 0.1 A 1CO at VSPC R
UN 250 V AC 0.1 A 1CO at VSPC R
with VSPC CONTROL UNIT
green = OK; red = arrester faulty, replace
730 KHz
20 ms
acc. to IEC61643-21
< 650 V
12 V / 450 V / 650 V
with VSPC CONTROL UNIT
green = OK; red = arrester faulty, replace
730 KHz
20 ms
acc. to IEC61643-21
< 650 V
25 V / 450 V / 650 V
with VSPC CONTROL UNIT
green = OK; red = arrester faulty, replace
730 KHz
30 ms
acc. to IEC61643-21
< 650 V
45 V / 450 V / 650 V
< 12 V
< 12 V
< 25 V
< 25 V
< 45 V
< 45 V
< 450 V
< 650 V
< 450 V
< 650 V
< 450 V
< 650 V
VSPC 1CL 5VDC 0.5A
VSPC 1CL 12VDC 0.5A
VSPC 1CL 24VDC 0.5A
8924420000
8924450000
8924480000
VSPC 1CL 5VDC 0.5A R
8951530000
1 piece
VSPC 1CL 12VDC 0.5A R
8951540000
1 piece
VSPC 1CL 24VDC 0.5A R
8951550000
1 piece
VSPC 1CL 24 V AC
VSPC 1CL 48 V AC
VSPC 1CL 60 V AC
Rated voltage (DC)
24 V AC / 34 V DC
48 V AC / 68 V DC
60 V AC / 85 V DC
Max. continuous voltage, Uc (DC)
Alternating-current strength
Rated current
Surge strength
Signaling contact
28 V AC / 39 V DC
60 V AC / 85 V DC
72 V AC / 101 V DC
450 mA
350 mA
250 mA
Rated voltage (DC)
Max. continuous voltage, Uc (DC)
Alternating-current strength
Rated current
Surge strength
Signaling contact
Optical function indicator (VSPC R)
Transmission test (-3dB)
Impulse reset
Tested
Residual voltage Up
wire-wire / wire-PE / GND-PE
Protection level on output side sym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
Protection level on output side unsym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
Ordering data
Without signaling contact/function indicatorType
Part No.
With signaling contact/function indicator Type
Part No.
Qty.
Note
Ordering Data
UN 250 V AC 0.1 A 1CO at VSPC R
Optical function indicator (VSPC R)
Transmission test (-3dB)
Impulse reset
Tested
Residual voltage Up
wire-wire / wire-PE / GND-PE
Protection level on output side sym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
Protection level on output side unsym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
Ordering data
Without signaling contact/function indicatorType
Part No.
with VSPC CONTROL UNIT
green = OK; red = arrester faulty, replace
730 KHz
30 ms
acc. to IEC61643-21
< 650 V
60 V / 450 V / 650 V
no
no
green = OK; red = arrester faulty, replace
730 KHz
100 ms
acc. to IEC61643-21
< 650 V
85 V / 450 V / 650 V
green = OK; red = arrester faulty, replace
730 KHz
100 ms
acc. to IEC61643-21
< 650 V
100 V / 450 V / 650 V
< 60 V
< 85 V
< 100 V
< 60 V
< 85 V
< 100 V
< 450 V
< 450 V
< 450 V
< 650 V
< 650 V
< 650 V
VSPC 1CL 24VAC 0.5A
VSPC 1CL 48VAC 0.5A
VSPC 1CL 60VAC 0.5A
8924500000
8924520000
8924530000
1 piece
1 piece
With signaling contact/function indicator Type
Part No.
VSPC 1CL 24VAC 0.5A R
8951560000
Qty.
Note
1 piece
10
VARITECTOR SPC
VSPC 2CL – Protection for two analog signals
• O
ptional monitoring function with status indicator and
alert function
• Pluggable arrester (plug-in / disconnect interruption-free
and impedance neutral)
• Testable with V-TEST instrument
• Space-saving design for two analog signals with signaling
contact, without additional space requirements
• Version with non-earthed PE connection for avoiding
potential differences
• U
sable in accordance with installations standard IEC 62305
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
for all VSPC 2CL
Dielectric strength with FG against PE
> 500 V
Volume resistivity per path
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Surge strength C1
Surge strength C2
Surge strength C3
Surge strength D1
2.2 Ω
Mode 2
C1; C2; C3; D1
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
1 kA 10/350 µs
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp. (10/350 μs) wire-wire / wire-PE / GND-PE
Degree of protection
Type of connection
Storage temperature
Ambient temperature (operational)
2.5 kA / 2.5 kA / 2.5 kA
10 kA / 2 x 10 kA / 10kA
2.5 kA / 2.5 kA / 2.5 kA
IP20
Pluggable in VSPC BASE
-40 °C…+80 °C
-40 °C…+70 °C
Rel. humidity
5 %…96 % RH
Degree of protection
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
IP20
Dimensions of complete module (arrester + base element) Without telecomm. contact With telecomm. contact (R)
Length x width x height
90 x 17.8 x 69 mm
98 x 17.8 x 69 mm
Note
Base elements / base to arresters
Ordering Data for Base
Type
Base element, direct earthing
Base element, indirect earthing via spark gap (FG, floating ground)
Base element, direct earthing with remote alert
Base element, indirect earthing with remote alert
Note: The basis elements are to be ordered separately
11
Qty.
1
Part No.
8924710000
1
1
1
8924270000
8951710000
8951720000
VARITECTOR SPC
VSPC 2CL – arrester / plug-in elements
Ordering Data
VSPC 2CL 5 V DC
VSPC 2CL 12 V DC
VSPC 2CL 24 V DC
5 V DC
12 V DC
24 V DC
6.4 V DC
15 V DC
28 V DC
450 mA
450 mA
450 mA
UN 250 V AC 0.1 A 1CO at VSPC R
UN 250 V AC 0.1 A 1CO at VSPC R
UN 250 V AC 0.1 A 1CO at VSPC R
with VSPC CONTROL UNIT
green = OK; red = arrester faulty, replace
730 KHz
20 ms
acc. to IEC61643-21
< 800 V
12 V / 450 V / 800 V
with VSPC CONTROL UNIT
green = OK; red = arrester faulty, replace
2.4 MHz
20 ms
acc. to IEC61643-21
< 800 V
25 V / 450 V / 800 V
with VSPC CONTROL UNIT
green = OK; red = arrester faulty, replace
2.2 MHz
30 ms
acc. to IEC61643-21
< 800 V
45 V / 450 V / 800 V
< 12 V
< 12 V
< 25 V
< 25 V
< 45 V
< 45 V
< 450 V
< 800 V
< 450 V
< 800 V
< 450 V
< 800 V
VSPC 2CL 5VDC 0.5A
VSPC 2CL 12VDC 0.5A
VSPC 2CL 24VDC 0.5A
8924400000
VSPC 2CL 5VDC 0.5A R
8951460000
8924440000
VSPC 2CL 12VDC 0.5A R
8951470000
8924470000
VSPC 2CL 24VDC 0.5A R
8951480000
1 piece
1 piece
1 piece
VSPC 2CL 24 V AC
VSPC 2CL 48 V AC
VSPC 2CL 60 V AC
Rated voltage (DC)
24 V AC / 34 V DC
48 V AC / 68 V DC
60 V AC / 85 V DC
Max. continuous voltage, Uc (DC)
Alternating-current strength
Rated current
Surge strength
Signaling contact
28 V AC / 39 V DC
60 V AC / 85 V DC
72 V AC / 101 V DC
450 mA
350 mA
250 mA
Rated voltage (DC)
Max. continuous voltage, Uc (DC)
Alternating-current strength
Rated current
Surge strength
Signaling contact
Optical function indicator (VSPC R)
Transmission test (-3dB)
Impulse reset
Tested
Residual voltage Up
wire-wire / wire-PE / GND-PE
Protection level on output side sym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
Protection level on output side unsym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
Ordering data
Without signaling contact/function indicatorType
Part No.
With signaling contact/function indicator Type
Part No.
Qty.
Note
Ordering Data
UN 250 V AC 0.1 A 1CO at VSPC R
Optical function indicator (VSPC R)
Transmission test (-3dB)
Impulse reset
Tested
Residual voltage Up
wire-wire / wire-PE / GND-PE
Protection level on output side sym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
Protection level on output side unsym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
Ordering data
Without signaling contact/function indicatorType
Part No.
With signaling contact/function indicator Type
Part No.
Qty.
Note
with VSPC CONTROL UNIT
green = OK; red = arrester faulty, replace
3 MHz
450 ms
acc. to IEC61643-21
< 650 V
60 V / 450 V / 800 V
no
no
green = OK; red = arrester faulty, replace
3 MHz
500 ms
acc. to IEC61643-21
< 650 V
85 V / 450 V / 650 V
green = OK; red = arrester faulty, replace
7 MHz
500 ms
acc. to IEC61643-21
< 650 V
100 V / 450 V / 650 V
< 60 V
< 60 V
500 ms
< 85 V
< 85 V
500 ms
< 100 V
< 100 V
< 450 V
< 800 V
< 450 V
< 650 V
< 450 V
< 650 V
VSPC 2CL 24VAC 0.5A
VSPC 2CL 48VAC 0.5A
VSPC 2CL 60VAC 0.5A
8924490000
VSPC 2CL 24VAC 0.5A R
1093400000
8951490000
8951500000
1 piece
1 piece
1 piece
12
V A R I T E C T O R S P C VSPC 2CL HF – For high transmission rates
without signal delays
• O
ptional monitoring function with status indicator and
alert function
• Pluggable arrester (plug-in / disconnect interruption-free
and impedance neutral)
• Testable with V-TEST instrument
• Space-saving design with optional signaling contact,
without additional space requirements
• High transmission rates with low attenuation values
• Usable in accordance with installations standard IEC 62305
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
for all VSPC 2CL HF
Dielectric strength with FG against PE
> 500 V
Rated current
Volume resistivity per path
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Surge strength C1
Surge strength C2
Surge strength C3
450 mA
2.2 Ω
Mode 2
C1; C2; C3; D1
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
Surge strength D1
1 kA 10/350 µs
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp. (10/350 μs) wire-wire / wire-PE / GND-PE
Degree of protection
Type of connection
Storage temperature
Ambient temperature (operational)
Rel. humidity
2.5 kA / 2.5 kA / 2.5 kA
10 kA / 2 x 10 kA / 10kA
2.5 kA / 2.5 kA / 2.5 kA
IP20
Pluggable in VSPC BASE
-40 °C…+80 °C
-40 °C…+70 °C
5 %…96 % RH
Degree of protection
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
IP20
Dimensions of complete module (arrester + base element) Without telecomm. contact With telecomm. contact (R)
Length x width x height
90 x 17.8 x 69 mm
98 x 17.8 x 69 mm
Note
Base elements / base to arresters
Ordering Data for Base
Type
Base element, direct earthing
Base element, indirect earthing via spark gap (FG, floating ground)
Base element, direct earthing with remote alert
Base element, indirect earthing with remote alert
Note: The basis elements are to be ordered separately
13
Qty.
1
Part No.
8924710000
1
1
1
8924270000
8951710000
8951720000
VARITECTOR SPC
VSPC 2CL HF – Arrester / plug-in elements
Ordering Data
VSPC 2CL HF 5 V DC
VSPC 2CL HF 12 V DC
VSPC 2CL HF 24 V DC
5 V DC
12 V DC
24 V DC
6.4 V DC
15 V DC
28 V DC
UN 250 V AC 0.1 A 1CO at VSPC R
UN 250 V AC 0.1 A 1CO at VSPC R
UN 250 V AC 0.1 A 1CO at VSPC R
with VSPC CONTROL UNIT
green = OK; red = arrester faulty, replace
1.5 MHz
20 ms
acc. to IEC61643-21
< 800 V
12 V / 450 V / 800 V
with VSPC CONTROL UNIT
green = OK; red = arrester faulty, replace
1.5 MHz
20 ms
acc. to IEC61643-21
< 800 V
25 V / 450 V / 800 V
with VSPC CONTROL UNIT
green = OK; red = arrester faulty, replace
1.5 MHz
40 ms
acc. to IEC61643-21
< 800 V
45 V / 450 V / 800 V
Protection level on output side sym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
< 12 V
< 12 V
< 25 V
< 25 V
< 45 V
< 45 V
Protection level on output side unsym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
< 450 V
< 800 V
< 450 V
< 800 V
< 450 V
< 800 V
VSPC 2CL HF 5VDC
VSPC 2CL HF 12VDC
VSPC 2CL HF 24VDC
8924430000
VSPC 2CL HF 5VDC R
8951680000
8924460000
VSPC 2CL HF 12VDC R
8951690000
8924510000
VSPC 2CLHF 24VDC R
8951700000
1 piece
1 piece
1 piece
Rated voltage (DC)
Max. continuous voltage, Uc (DC)
Alternating-current strength
Surge strength
Signaling contact
Optical function indicator (VSPC R)
Transmission test (-3dB)
Impulse reset
Tested
Residual voltage Up
wire-wire / wire-PE / GND-PE
Ordering data
Without signaling contact/function indicatorType
Part No.
With signaling contact/function indicator Type
Part No.
Qty.
Note
14
VARITECTOR SPC
VSPC 1CL PW – Combinations of current loop
signal and circuit breaker
• O
ptional monitoring function with status indicator
• Pluggable arrester (plug-in / disconnect interruption-free
and impedance neutral)
• U
sable in accordance with installations standard IEC 62305
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
for all VSPC 1CL PW
C&I protection data
Rated voltage (DC)
Max. continuous voltage, Uc (DC)
Dielectric strength with FG against PE
Rated current
Volume resistivity per path
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Optical function indicator
Rated voltage (AC/DC)
Surge strength C1
Surge strength C2
Surge strength C3
Surge strength D1
Transmission test (-3dB)
Impulse reset
Tested
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp. (10/350 μs) wire-wire / wire-PE / GND-PE
Residual voltage Up
Residual voltage Up wire-wire / wire-PE / GND-PE
Protection level on output side sym., input 1 kV/μs, typ.
Protection level on output side sym., input 8/20 μs, typ.
Protection level on output side unsym., input 1 kV/μs, typ.
Protection level on output side unsym., input 8/20 μs, typ.
Protection of the device
Rated voltage (DC)
Max. continuous voltage, Uc (DC)
Combined pulse
Residual voltage Up
Rated current
General data
Type of connection
Storage temperature
Requirement category acc. to IEC 61643-1
Ambient temperature (operational)
Rel. humidity
Degree of protection
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
24 V AC / 34 V DC
27 V AC / 38 V DC
> 500 V
450 mA
2.2 Ω
Mode 2
C1; C2; C3; D1
green = OK; red = arrester faulty, replace
24 V AC / 33 V DC
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
2.5 kA 10/350 µs
730 KHz
10 ms
acc. to IEC61643-21, IEC61643-1
2.5 kA / 2.5 kA / 2.5 kA
10 kA / 10 kA / 10 kA
2.5 kA / 2.5 kA / 2.5 kA
800 V
60 V / 450 V / 800 V
< 60 V
< 60 V
< 450 V
< 800 V
24 V AC / 34 V DC
27 V AC / 38 V DC
6 kV
900 V
10 A
Pluggable in VSPC BASE
-40 °C…+80 °C
Class III
-40 °C…+70 °C
5 %…96 % RH
IP20
Dimensions of complete module (arrester + base element) Without telecomm. contact With telecomm. contact (R)
Length x width x height
90 x 17.8 x 69 mm
98 x 17.8 x 69 mm
Base elements / base to arresters
Ordering Data for Base
Type
Base element, direct earthing
Base element, indirect earthing via spark gap (FG, floating ground)
Note: The basis elements are to be ordered separately
15
Qty.
1
Part No.
1070230000
1
1105700000
VARITECTOR SPC
VSPC 1CL PW – Arrester / plug-in elements
Ordering Data
VSPC 1CL PW 24 V
Without signaling contact/function indicatorType
Part No.
Qty.
Note
VSPC 1CL PW 24V 0.5A
8951510000
1 piece
16
VARITECTOR SPC
VSPC 2SL – Protection for two binary signals
• O
ptional monitoring function with status indicator and
alert function
• Pluggable arrester (plug-in / disconnect interruption-free
and impedance neutral)
• Testable with V-TEST instrument
• Version with non-earthed PE connection for avoiding
potential differences
• U
sable in accordance with installations standard IEC 62305
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
for all VSPC 2SL
Dielectric strength with FG against PE
> 500 V
Volume resistivity per path
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Surge strength C1
Surge strength C2
Surge strength C3
Surge strength D1
4.7 Ω
Mode 2
C1; C2; C3; D1
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
2.5 kA 10/350 µs
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp. (10/350 μs) wire-wire / wire-PE / GND-PE
Type of connection
Storage temperature
Ambient temperature (operational)
Rel. humidity
2.5 kA / 2.5 kA / 2.5 kA
10 kA / 10 kA / 10kA
2.5 kA / 2.5 kA / 2.5 kA
Pluggable in VSPC BASE
-40 °C…+80 °C
-40 °C…+70 °C
5 %…96 % RH
Degree of protection
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
IP20
Dimensions of complete module (arrester + base element) Without telecomm. contact With telecomm. contact (R)
Length x width x height
90 x 17.8 x 69 mm
98 x 17.8 x 69 mm
Note
Base elements / base to arresters
Ordering Data for Base
Type
Base element, direct earthing
Base element, indirect earthing via spark gap (FG, floating ground)
Base element, direct earthing with remote alert
Base element, indirect earthing with remote alert
Note: The basis elements are to be ordered separately
17
Qty.
1
Part No.
8924720000
1
1
1
8924280000
8951770000
8951780000
VARITECTOR SPC
VSPC 2SL – Arrester / plug-in elements
Ordering Data
Rated voltage UN
VSPC 2SL 5 V DC
VSPC 2SL 12 V DC
VSPC 2SL 12 V AC
VSPC 2SL 24 V DC
24 V DC
5 V DC
12 V DC
12 V AC / 16 V DC
6.4 V DC
15 V DC
13,2 V AC / 18 V DC
UN 250 V AC 0.1 A 1CO at VSPC R
with VSPC CONTROL UNIT
green = OK; red = arrester faulty,
replace
750 KHz
20 ms
acc. to IEC61643-21
< 25 V
25 V / 25 V / 25 V
UN 250 V AC 0.1 A 1CO at VSPC R
with VSPC CONTROL UNIT
green = OK; red = arrester faulty,
replace
750 KHz
20 ms
acc. to IEC61643-21
< 50 V
45 V / 50 V / 50 V
green = OK; red = arrester faulty,
replace
750 KHz
20 ms
acc. to IEC61643-21
< 50 V
55 V / 50 V / 50 V
UN 250 V AC 0.1 A 1CO at VSPC R
with VSPC CONTROL UNIT
green = OK; red = arrester faulty,
replace
750 KHz
30 ms
acc. to IEC61643-21
< 60 V
80 V / 60 V / 60 V
Protection level on output side sym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
< 25 V
< 25 V
< 45 V
< 45 V
< 55 V
< 55 V
< 80 V
< 80 V
Protection level on output side unsym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
< 12 V
< 25 V
< 25 V
< 50 V
< 30 V
< 50 V
< 40 V
< 60 V
300 mA
300 mA
300 mA
300 mA
VSPC 2SL 5VDC 0.5A
VSPC 2SL 12VDC 0.5A
VSPC 2SL 12VAC 0.5A
VSPC 2SL 24VDC 0.5A
8924210000
VSPC 2SL 5VDC 0.5A R
8951610000
8924230000
VSPC 2SL 12VDC 0.5A R
8951620000
8924250000
8924330000
VSPC 2SL 24VDC 0.5A R
8951630000
1 piece
1 piece
1 piece
1 piece
VSPC 2SL 24 V AC
VSPC 2SL 48 V AC
VSPC 2SL 60 V AC
Rated voltage UN
24 V AC / 34 V DC
48 V AC / 68 V DC
60 V AC / 85 V DC
Max. continuous voltage UC
Signaling contact
28 V AC / 39 V DC
60 V AC / 85 V DC
72 V AC / 101 V DC
Max. continuous voltage UC
Signaling contact
Optical function indicator (VSPC R)
Transmission test (-3dB)
Impulse reset
Tested
Residual voltage Up
wire-wire / wire-PE / GND-PE
Rated current
Ordering data
Without signaling contact/function indicatorType
Part No.
With signaling contact/function indicator Type
Part No.
Qty.
Note
Ordering Data
no
UN 250 V AC 0,1 A 1CO at VSPC R
with VSPC CONTROL UNIT
green = OK; red = arrester faulty,
replace
750 KHz
60 ms
acc. to IEC61643-21
< 60 V
80 V / 60 V / 60 V
no
no
green = OK; red = arrester faulty,
replace
750 KHz
60 ms
acc. to IEC61643-21
< 125 V
80 V / 125 V / 125 V
green = OK; red = arrester faulty,
replace
750 KHz
60 ms
acc. to IEC61643-21
< 165 V
80 V / 165 V / 165 V
Protection level on output side sym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
< 110 V
< 80 V
< 210 V
< 80 V
< 280 V
< 80 V
Protection level on output side unsym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
< 60 V
< 60 V
< 85 V
< 125 V
< 100 V
< 165 V
300 mA
250 mA
200 mA
VSPC 2SL 24VAC 0.5A
VSPC 2SL 48VAC 0.5A
VSPC 2SL 60VAC 0.5A
8924350000
VSPC 2SL 24VAC 0.5A R
8951640000
8924370000
8924390000
1 piece
1 piece
1 piece
Optical function indicator (VSPC R)
Transmission test (-3dB)
Impulse reset
Tested
Residual voltage Up
wire-wire / wire-PE / GND-PE
Rated current
Ordering data
Without signaling contact/function indicatorType
Part No.
With signaling contact/function indicator Type
Part No.
Qty.
Note
28 V DC
18
VARITECTOR SPC
VSPC 4SL – Protection for four binary signals
• O
ptional monitoring function with status indicator and
alert function
• Pluggable arrester (plug-in / disconnect interruption-free
and impedance neutral)
• Testable with V-TEST instrument
• Space-saving design for four binary signals with signaling
contact, without additional space requirements
• Version with non-earthed PE connection for avoiding
potential differences
• U
sable in accordance with installations standard IEC 62305
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
for all VSPC 4SL
Volume resistivity per path
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Surge strength C1
Surge strength C2
Surge strength C3
Surge strength D1
4.7 Ω
Mode 2
C1; C2; C3; D1
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
2.5 kA 10/350 µs
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE 2.5 kA / 2.5 kA / 2.5 kA
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp. (10/350 μs) wire-wire / wire-PE / GND-PE
Type of connection
Storage temperature
Ambient temperature (operational)
Rel. humidity
10 kA / 10 kA / 10 kA
2.5 kA / 2.5 kA / 2.5 kA
Pluggable in VSPC BASE
-40 °C … +80 °C
-40 °C … +70 °C
5 % … 96 % RH
Degree of protection
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
IP20
Dimensions of complete module (arrester + base element) Without telecomm. contact With telecomm. contact (R)
Length x width x height
90 x 17.8 x 69 mm
98 x 17.8 x 69 mm
Note
Base elements / base to arresters
Ordering Data for Base
Type
Base element, direct earthing
Base element, indirect earthing via spark gap (FG, floating ground)
Base element, direct earthing with remote alert
Base element, indirect earthing with remote alert
Note: The basis elements are to be ordered separately
19
Qty.
1
Part No.
8924700000
1
1
1
8924260000
8951750000
8951760000
VARITECTOR SPC
VSPC 4SL – Arrester / plug-in elements
Ordering Data
Rated voltage UN
VSPC 4SL 5 V DC
VSPC 4SL 12 V DC
VSPC 4SL 12 V AC
VSPC 4SL 24 V DC
24 V DC
5 V DC
12 V DC
12 V AC / 16 V DC
6.4 V DC
15 V DC
13.2 V AC / 18 V DC
UN 250 V AC 0.1 A 1CO at VSPC R
with VSPC CONTROL UNIT
green = OK; red = arrester faulty,
replace
730 KHz
20 ms
acc. to IEC61643-21
< 25 V
25 V / 25 V / 25 V
UN 250 V AC 0.1 A 1CO at VSPC R
with VSPC CONTROL UNIT
green = OK; red = arrester faulty,
replace
750 KHz
20 ms
acc. to IEC61643-21
< 35 V
45 V / 20 V / 450 V
green = OK; red = arrester faulty,
replace
750 KHz
20 ms
acc. to IEC61643-21
< 50 V
55 V / 50 V / 50 V
UN 250 V AC 0.1 A 1CO at VSPC R
with VSPC CONTROL UNIT
green = OK; red = arrester faulty,
replace
750 KHz
30 ms
acc. to IEC61643-21
< 60 V
80 V / 60 V / 60 V
Protection level on output side sym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
< 25 V
< 25 V
< 45 V
< 45 V
< 55 V
< 55 V
< 80 V
< 80 V
Protection level on output side unsym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
< 12 V
< 25 V
< 25 V
< 50 V
< 30 V
< 50 V
< 40 V
< 60 V
350 mA
300 mA
300 mA
300 mA
VSPC 4SL 5VDC 0.5A
VSPC 4SL 12VDC 0.5A
VSPC 4SL 12VAC 0.5A
VSPC 4SL 24VDC 0.5A
8924200000
VSPC 4SL 5VDC 0.5A R
8951570000
8924220000
VSPC 4SL 12VDC 0.5A R
8951580000
8924240000
8924320000
VSPC 4SL 24VDC 0.5A R
8951590000
1 piece
1 piece
1 piece
1 piece
VSPC 4SL 24 V AC
VSPC 4SL 48 V AC
VSPC 4SL 60 V AC
Rated voltage UN
24 V AC / 34 V DC
48 V AC / 68 V DC
60 V AC / 85 V DC
Max. continuous voltage UC
Signaling contact
28 V AC / 39 V DC
60 V AC / 85 V DC
72 V AC / 101 V DC
Max. continuous voltage UC
Signaling contact
Optical function indicator (VSPC R)
Transmission test (-3dB)
Impulse reset
Tested
Residual voltage Up
wire-wire / wire-PE / GND-PE
Rated current
Ordering data
Without signaling contact/function indicatorType
Part No.
With signaling contact/function indicator Type
Part No.
Qty.
Note
no
UN 250 V AC 0.1 A 1CO at VSPC R
with VSPC CONTROL UNIT
green = OK; red = arrester faulty,
replace
750 KHz
40 ms
acc. to IEC61643-21
< 60 V
80 V / 60 V / 60 V
no
no
green = OK; red = arrester faulty,
replace
750 KHz
60 ms
acc. to IEC61643-21
< 125 V
80 V / 125 V / 125 V
green = OK; red = arrester faulty,
replace
750 KHz
60 ms
acc. to IEC61643-21
< 165 V
80 V / 165 V / 165 V
Protection level on output side sym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
< 110 V
< 80 V
< 210 V
< 80 V
< 280 V
< 80 V
Protection level on output side unsym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
< 60 V
< 60 V
< 85 V
< 125 V
< 100 V
< 165 V
Rated current
300 mA
250 mA
200 mA
VSPC 4SL 24VAC 0.5A
VSPC 4SL 48VAC 0.5A
VSPC 4SL 60VAC 0.5A
Optical function indicator (VSPC R)
Transmission test (-3dB)
Impulse reset
Tested
Residual voltage Up
wire-wire / wire-PE / GND-PE
Without signaling contact/function indicatorType
With signaling contact/function indicator Type
Part No.
8924340000
VSPC 4SL 24VAC 0.5A R
8951600000
Qty.
1 piece
Part No.
28 V DC
8924380000
1 piece
1 piece
20
VARITECTOR SPC
VSPC 4SL WIRE – 3/4 conductor, measurement
• P
luggable arrester (plug-in / disconnect interruption-free
and impedance neutral)
• Protection of measuring bridge signals
• Testable with V-TEST instrument
• U
sable in accordance with installations standard IEC 62305
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
for all VSPC 4SL WIRE
Rated current
450 mA
Volume resistivity per path
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Surge strength C1
Surge strength C2
Surge strength C3
Surge strength D1
0.2 Ω
Mode 2
C1; C2; C3; D1
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
2.5 kA 10/350 µs
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp. (10/350 μs) wire-wire / wire-PE / GND-PE
Type of connection
Storage temperature
Ambient temperature (operational)
Rel. humidity
2.5 kA / 2.5 kA / 2.5 kA
10 kA / 10 kA / 10 kA
2.5 kA / 2.5 kA / 2.5 kA
Pluggable in VSPC BASE
-40 °C…+80 °C
-40 °C...+70 °C
5 %...96 % RH
Degree of protection
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
IP20
Dimensions of complete module (arrester + base element) Without telecomm. contact With telecomm. contact (R)
Length x width x height
90 x 17.8 x 69 mm
98 x 17.8 x 69 mm
Note
Base elements / base to arresters
Ordering Data for Base
Type
Base element, direct earthing
Base element, indirect earthing via spark gap (FG, floating ground)
Note: The basis elements are to be ordered separately
21
Qty.
1
Part No.
8924740000
1
8924300000
VARITECTOR SPC
VSPC 4SL WIRE – Arrester / plug-in elements
Ordering Data
Rated voltage (DC)
VSPC 3/4WIRE 5 V DC
VSPC 3/4WIRE 24 V DC
3 V DC
24 V DC
6.4 V DC
< 800 V
730 KHz
28 V DC
< 800 V
730 KHz
< 20 ms
acc. to IEC61643-21
< 800 V
35 V / 800 V / 500 V
< 30 ms
acc. to IEC61643-21
< 800 V
50 V / 800 V / 800 V
Protection level on output side sym., input 1 kV/μs, typ.
input 8/20 μs, typ.
< 35 V
< 35 V
< 50 V
< 50 V
Protection level on output side unsym., input 1 kV/μs, typ.
input 8/20 μs, typ.
< 250 V
< 800 V
< 270 V
< 800 V
VSPC 3/4WIRE 5VDC
VSPC 3/4WIRE 24VDC
8924540000
8924550000
1 piece
1 piece
Max. continuous voltage, Uc (DC)
Residual voltage Up
Transmission test (-3dB)
Impulse reset
Tested
Residual voltage Up
wire-wire / wire-PE / GND-PE
Ordering data
Without signaling contact /
Function indicator
Type
Part No.
Qty.
Note
22
VARITECTOR SPC
VSPC GDT – with components
Pluggable arrester with components: GDT
• Pluggable arrester (plug-in / disconnect interruption-free
and impedance neutral)
• Testable with V-TEST instrument
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
for all VSPC GDT
Dielectric strength with FG against PE
> 500 V
Volume resistivity per path
Overstressed fault mode
Surge strength C1
Surge strength C2
Surge strength C3
Surge strength D1
Type of connection
< 0.2 Ω
Mode 2
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
2.5 kA 10/350 µs
Pluggable in VSPC BASE
Storage temperature
Ambient temperature (operational)
Rel. humidity
-40 °C…+80 °C
-40 °C…+70 °C
5 %…96 % RH
Degree of protection
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
IP20
Dimensions of complete module (arrester + base element) Without telecomm. contact With telecomm. contact (R)
Length x width x height
90 x 17.8 x 69 mm
98 x 17.8 x 69 mm
Note
Base elements / base to arresters
Ordering Data for Base
Type
Base element, direct earthing
Base element, indirect earthing via spark gap (FG, floating ground)
Note: The basis elements are to be ordered separately
23
Qty.
1
Part No.
8924740000
1
8924300000
VARITECTOR SPC
VSPC GDT – Arrester / plug-in elements
Ordering Data
VSPC GDT 2CH 90 V
VSPC GDT 2CH 150 V AC/230 V DC
Rated voltage (DC)
48 V AC / 68 V DC
110 V AC / 150 V DC
Max. continuous voltage, Uc (DC)
Signaling contact
Rated current
Transmission test (-3dB)
Impulse reset
Tested
Rated discharge current IN (8/20 µs)
50 V AC / 72 V DC
no
2000 mA
125 V AC / 180 V DC
no
2000 mA
3 MHz
3 MHz
in accordance with IEC61643-21
in accordance with IEC61643-21
wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 µs)
2 x 2.5 kA / - / 2.5 kA
2 x 2.5 kA / - / 2.5 kA
wire-wire / wire-PE / GND-PE
Rated discharge current, Iimp. (10/350 µs)
wire-wire / wire-PE / GND-PE
Residual voltage Up
wire-wire / wire-PE / GND-PE
2 x 10 kA / - / 10 kA
2 x 10 kA / - / 10 kA
2 x 0.2 kA / - / 0.2 kA
< 1000 V
650 V / 1000 V / -
2 x 0.2 kA / - / 0.2 kA
< 800 V
800 V / 800 V / -
< 650 V
< 1000 V
< 450 V
< 800 V
C1; C2; C3; D1
C1; C2; C3; D1
VSPC GDT 2ch 90V20kA
VSPC GDT 2CH 150Vac/230Vdc
8924570000
8924590000
1 piece
1 piece
Protection level on output side sym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
Requirement category acc. to IEC 61643-21
Ordering data
Without signaling contact/function indicatorType
Part No.
With signaling contact/function indicator
Type
Part No.
Qty.
Note
24
VARITECTOR SPC
VSPC MOV – with components
Pluggable arrester with components: MOV
• Optional monitoring function with status display and alert
function for MOV components
• Pluggable arrester (plug-in / disconnect interruption-free
and impedance neutral)
• Testable with V-TEST instrument
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
for all VSPC MOV
Dielectric strength with FG against PE
> 500 V
Volume resistivity per path
Overstressed fault mode
Surge strength C1
Surge strength C2
Surge strength D1
Type of connection
Storage temperature
< 0.2 Ω
Mode 1
< 1 kA / 8/20 µs
1.5 kA / 8/20 µs; 1 kA / 8/20 μs at VSPC R
0.5 kA 10/350 μs
Pluggable in VSPC BASE
-40 °C…+80 °C
Ambient temperature (operational)
Rel. humidity
-40 °C…+70 °C
5 %…96 % RH
Degree of protection
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
IP20
Dimensions of complete module (arrester + base element) Without telecomm. contact With telecomm. contact (R)
Length x width x height
90 x 17.8 x 69 mm
98 x 17.8 x 69 mm
Note
Base elements / base to arresters
Ordering Data for Base
Type
Base element, direct earthing
Base element, indirect earthing via spark gap (FG, floating ground)
Base element, direct earthing with remote alert
Base element, indirect earthing with remote alert
Note: The basis elements are to be ordered separately
25
Qty.
1
Part No.
8924740000
1
1
1
8924300000
8951790000
8951800000
VARITECTOR SPC
VSPC MOV – Arrester / plug-in elements
Ordering Data
VSPC MOV 2CH 24 V
Rated voltage (DC)
Max. continuous voltage, Uc (DC)
Rated current
Transmission test
Tested
Surge strength C3
Rated discharge current, limp (10/350 μs)
wire-wire / wire-PE / GND-PE
Rated discharge current IN (8/20 µs)
wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 µs)
wire-wire / wire-PE / GND-PE
Residual voltage Up
wire-wire / wire-PE / GND-PE
Protection level on output side sym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
Requirement category acc. to IEC 61643-21
Ordering data
Without signaling contact/function indicator
Type
Part No.
Qty.
Note
Ordering Data
Rated voltage (DC)
Max. continuous voltage, Uc (DC)
Signaling contact
Optical function indicator (VSPC R)
Rated current
Transmission test
Tested
Surge strength C3
Rated discharge current, limp (10/350 μs)
wire-wire / wire-PE / GND-PE
Rated discharge current IN (8/20 µs)
wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 µs)
wire-wire / wire-PE / GND-PE
Residual voltage Up
wire-wire / wire-PE / GND-PE
Protection level on output side sym.,
input 1 kV/μs, typ.
input 8/20 μs, typ.
Requirement category acc. to IEC 61643-21
Ordering data
With signaling contact/function indicator
Type
Part No.
Qty.
Note
VSPC MOV 2CH 230 V
24 V AC
230 V AC
30 V AC / 42 V DC
10 A
1 MHz
275 V AC / 385 V DC
10 A
1 MHz
acc. to IEC61643-21
100 A / 10/1000 μs
acc. to IEC61643-21
50 A / 10/1000 μs
0.2 kA / - / 0.5 kA
0.2 kA / - / 0.5 kA
1.5 kA / - / 1.5 kA
1.5 kA / - / 1.5 kA
1.5 kA / - / 1.5 kA
< 95 V
80 V / - / -
1.5 kA / - / 1.5 kA
< 850 V
850 V / - / -
< 80 V
< 95 V
< 600 V
< 700 V
C1; C2; C3; D1
C1; C2; C3; D1
VSPC MOV 2CH 24V 8kA
VSPC MOV 2ch 230V8kA
8924600000
8924610000
1 piece
1 piece
VSPC MOV 2CH 24 V R
VSPC MOV 2CH 230 V R
24 V AC
230 V AC
30 V AC / 42 V DC
275 V AC / 385 V DC
UN 250 V AC 0.1 A 1CO at VSPC R
UN 250 V AC 0.1 A 1CO at VSPC R
with VSPC CONTROL UNIT
green = OK; red = arrester faulty, replace
10 A
1 MHz
acc. to IEC61643-21
100 A / 10/1000 μs
with VSPC CONTROL UNIT
green = OK; red = arrester faulty, replace
10 A
1 MHz
acc. to IEC61643-21
50 A / 10/1000 μs
0.2 kA / - / 0.5 kA
0.2 kA / - / 0.5 kA
1 kA / - / 1 kA
1 kA / - / 1 kA
1 kA / - / 1 kA
< 200 V
200 V / - / -
1 kA / - / 1 kA
< 850 V
850 V / - / -
< 80 V
< 95 V
< 600 V
< 700 V
C1; C2; C3; D1
C1; C2; C3; D1
VSPC MOV 2CH 24V R
VSPC MOV 2ch 230V R
8951650000
8951660000
1 piece
1 piece
26
VARITECTOR SPC
VSPC TAZ – components
Pluggable arrester with components: TAZ
• Pluggable arrester (plug-in / disconnect interruption-free
and impedance neutral)
• Testable with V-TEST instrument
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
for all VSPC TAZ
Dielectric strength with FG against PE
> 500 V
Rated current
Volume resistivity per path
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Surge strength C3
Type of connection
Storage temperature
10 A
< 0.2 Ω
Mode 2
C3
20 A / 10/1000 µs
Pluggable in VSPC BASE
-40 °C…+80 °C
Ambient temperature (operational)
Rel. humidity
-40 °C…+70 °C
5 %…96 % RH
Degree of protection
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
IP20
Dimensions of complete module (arrester + base element) Without telecomm. contact With telecomm. contact (R)
Length x width x height
90 x 17.8 x 69 mm
98 x 17.8 x 69 mm
Note
Base elements / base to arresters
Ordering Data for Base
Type
Base element, direct earthing
Base element, indirect earthing via spark gap (FG, floating ground)
Note: The basis elements are to be ordered separately
27
Qty.
1
Part No.
8924740000
1
8924300000
VARITECTOR SPC
VSPC TAZ – Arrester / plug-in elements
Ordering Data
VSPC TAZ 2 CH 24 V AC
VSPC TAZ 4 CH 24 V
Rated voltage (DC)
24 V AC / 34 V DC
24 V AC / 34 V DC
Max. continuous voltage, Uc (DC)
28 V AC / 39 V DC
1 MHz
28 V AC / 39 V DC
1 MHz
in accordance with IEC61643-21
55 V / - / -
in accordance with IEC61643-21
- / 55 V / -
< 50 V
< 55 V
< 50 V
< 55 V
VSPC TAZ 2ch24Vac 0.1kA
VSPC TAZ 4ch24V 0.1kA
8924640000
8924650000
1 piece
1 piece
Transmission test (-3dB)
Impulse reset
Tested
Residual voltage Up wire-wire / wire-PE / GND-PE
Protection level on output side sym., input 1 kV/μs, typ.
input 8/20 μs, typ.
Ordering data
Without signaling contact /
Function indicator
Type
Part No.
Qty.
Note
28
VARITECTOR SPC
VSPC TELE UK0
for the Uk0/S0 interface in telecommunication
• Pluggable arrester (plug-in / disconnect interruption-free
and impedance neutral)
• Low residual voltage
• 2-wire input interface – Uk0
• Testable with V-TEST instrument
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
for all VSPC TELE UK0
Dielectric strength with FG against PE
> 500 V
Rated current
Volume resistivity per path
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Surge strength C1
Surge strength C2
Surge strength C3
450 mA
2.2 Ω
Mode 2
C1; C2; C3; D1
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
Surge strength D1
2.5 kA 10/350 µs
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp. (10/350 μs) wire-wire / wire-PE / GND-PE
Type of connection
Storage temperature
Ambient temperature (operational)
Rel. humidity
2.5 kA / 2.5 kA / 2.5 kA
10 kA / 2 x 10 kA / 10 kA
0.2 kA / 2 x 0.2 kA / 0.2 kA
Pluggable in VSPC BASE
-40 °C…+80 °C
-40 °C…+70 °C
5 %…96 % RH
Degree of protection
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
IP20
Dimensions of complete module (arrester + base element) Without telecomm. contact With telecomm. contact (R)
Length x width x height
90 x 17.8 x 69 mm
98 x 17.8 x 69 mm
Note
Base elements / base to arresters
Ordering Data for Base
Type
Base element, direct earthing
Base element, indirect earthing via spark gap (FG, floating ground)
Note: The basis elements are to be ordered separately
29
Qty.
1
Part No.
8924710000
1
8924270000
VARITECTOR SPC
VSPC TELE UK0 / VSPC RS485 – Arrester / plug-in elements
Ordering Data
VSPC TELE UK0 2WIRE
Rated voltage (DC)
127 V AC
Max. continuous voltage, Uc (DC)
180 V DC
1 MHz
60 ms
Transmission test (-3dB)
Impulse reset
Tested
Residual voltage Up
wire-wire / wire-PE / GND-PE
in accordance with IEC61643-21
800 V
250 V / 450 V / 650 V
Protection level on output side sym., input 1 kV/μs, typ.
input 8/20 μs, typ.
< 250 V
< 300 V
Protection level on output side unsym.,input 1 kV/μs, typ.
input 8/20 μs, typ.
< 450 V
< 800 V
Ordering data
Without signaling contact /
Function indicator
Type
Part No.
Qty.
Note
VSPC TELE UK0 2WIRE
8924660000
1 piece
30
VARITECTOR SPC
VSPC RS485
For serial data transmission
• Optional monitoring function with status indicator and alert
function
• Pluggable arrester (plug-in / disconnect interruption-free
and impedance neutral)
• Low residual voltage
• Protection for conducted serial data transmission – RS485
• Testable with V-TEST instrument
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
for all VSPC RS485
Dielectric strength with FG against PE
> 500 V
Rated current
Volume resistivity per path
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Surge strength C1
Surge strength C2
Surge strength C3
450 mA
2.2 Ω
Mode 2
C1; C2; C3; D1
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
Surge strength D1
2.5 kA 10/350 µs
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp. (10/350 μs) wire-wire / wire-PE / GND-PE
Type of connection
Storage temperature
Ambient temperature (operational)
Rel. humidity
2.5 kA / 2.5 kA / 2.5 kA
10 kA / 2 x 10 kA / 10 kA
0.2 kA / 2 x 0.2 kA / 0.2 kA
Pluggable in VSPC BASE
-40 °C…+80 °C
-40 °C…+70 °C
5 %…96 % RH
Degree of protection
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
IP20
0.5
0.45
Current [mA]
0.4
0.35
0.3
0.25
0.2
0.15
0.1
0.05
0
0
10
20
30
40
50
60
70
80
90
100
Temperature [°C]
Dimensions of complete module (arrester + base element) Without telecomm. contact With telecomm. contact (R)
Length x width x height
90 x 17.8 x 69 mm
98 x 17.8 x 69 mm
Note
Base elements / base to arresters
Ordering Data for Base
Type
Base element, direct earthing
Base element, indirect earthing via spark gap (FG, floating ground)
Base element, direct earthing with remote alert
Base element, indirect earthing with remote alert
Note: The basis elements are to be ordered separately
31
Qty.
1
Part No.
8924710000
1
1
1
8924270000
8951790000
8951800000
VARITECTOR SPC
VSPC RS485 – Arrester / plug-in elements
Ordering Data
VSPC RS485 2CH
Rated voltage (DC)
5 V DC
Max. continuous voltage, Uc (DC)
6,4 V DC
UN 250 V AC 0,1 A 1CO at VSPC R
Signaling contact
Optical function indicator (VSPC R)
Transmission test (-3dB)
Impulse reset
Tested
Residual voltage Up
wire-wire / wire-PE / GND-PE
Protection level on output side sym., input 1 kV/μs, typ.
input 8/20 μs, typ.
Protection level on output side unsym., input 1 kV/μs, typ.
input 8/20 μs, typ.
Ordering data
Without signaling contact /
Function indicator
With signaling contact /
Function indicator
Type
Part No.
Type
Part No.
Qty.
Note
with VSPC CONTROL UNIT
green = OK; red = arrester faulty, replace
4 MHz
20 ms
acc. to IEC61643-21
35 V
15 V / 35 V / 500 V
< 10 V
< 15 V
< 10 V
< 35 V
VSPC RS485 2CH
8924670000
VSPC RS485 2CH R
8951670000
1 piece
32
VARITECTOR SPC
VSPC CONTROL UNIT 24 V DC
•
•
•
•
•
•
For monitoring up to 10 protective modules
Signaling module for all VSPCs with status indicator
Signaling of cable breaks / signal interruptions
Voltage supply from 18...31 V DC
Potential-free changeover contact
Function indicator (red/green LED)
Technical Data
24 V
0V
Input
Rated voltage (DC)
18 V…24 V DC…31 V DC
X2
Rated current
max. 50 mA
X1
Power rating
Output
Current loop
1.5 W
Monitoring option
Signal output
Type
1…10 VSPC modules
Max. switching voltage / continuous current
Diagnostics
Operating status
250 V / 1 A
Defect at current loop
Red LED (control unit and defective module)
Wire breakage
General data
Terminal rail
Red/green LED, flashing
Design, Protection class
Type of connection
Storage temperature
Ambient temperature (operational)
Rel. humidity
Insta-enclosure, IP20
BL / SL
-40 °C…+80 °C
-40 °C…+70 °C
5 %…96 % RH
Start-up time after fault correction
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
60 s
12
11
VSPC CONTROL UNIT
X2
X1
X2
X1
14
X2
X1
nmax = 10
n=2
n=1
VSPC...R
VSPC...R
VSPC...R
8 mA bei < 51 V
1 CO contact
Green LED
TS35
Dimensions
Dimensions incl. enclosure L x W x H Note
Applikation
102 x 18 x 71.5 mm
Ordering Data
VSPC CONTROL UNIT 24 V DC
Type
Part No.
Qty.
Note
33
VSPC CONTROL UNIT 24Vdc
8972270000
1 piece
Accessories
VARITECTOR SPC
VSPC Accessories
V-Test
• Instrument for testing the protective functions of series:
PU I, PU II and VSPC
• Device for realizing standard IEC 62305 (periodic testing)
• Handy device with integrated battery set for local
measurements
• Result display via LCD display
• Bilingual menu
• Including protective bag and power supply
• Intuitive user navigation in German and English
The V-Test is a compact, portable instrument for the
Varitector SPC pluggable surge protection (VSPC series) and
surge protection for power distribution, PUI and II series.
With this instrument, the Weidmuller surge protection can be
tested for protective function in accordance with the required
test periods as stipulated by IEC62305 (DIN VDE 185 Part 3).
In a backlit display, the measurement result is indicated with
"ok" or "not ok" for each component.
Technical Data
Rated voltage
100...240 V AC
Accumulator set
Storage temperature
Ambient temperature (operational)
Degree of protection
Measuring range
UL94 flammability class
8 NiMH with 2600 mA
0 °C ... 40 °C
0 °C ... 40 °C
IP20
U < 1000 V / I = 1 mA
V0
General tolerances of measurement range
Gas discharge tube
+/- 10%
Varistor
+/- 5%
TVS-diode
+/- 5%
Note
Ordering Data
V-Test
Dimensions
Length x width x height Ordering data
Type
Part No.
Qty.
Note
230 x 122 x 65 mm
V-Test
8951860000
1
34
VARITECTOR SPC
Accessories
VSPC Accessories
V-Ground
• Can be applied to unassigned wires
• Usable during start-up and maintenance
• Earthing of all sensor cables
• Can be plugged into standard base sockets
V-Test-Connector
• Usable during start-up and maintenance
• For circuit voltage measurements using a standard
2.3-mm test socket
• Can be plugged into standard base sockets
Technical Data
Rated voltage (DC)
230 V AC
Max. continuous voltage, Uc (DC)
255 V AC
< 0.5 A
< 0.2 Ω
Pluggable in VSPC BASE
-40 °C…+80 °C
-40 °C…+70 °C
5 %…96 % RH
Rated current
Volume resistivity per path
Type of connection
Storage temperature
Ambient temperature (operational)
Rel. humidity
Degree of protection
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
IP20
Note
Ordering Data
Arrester / plug-in elements
VSPC TEST Connector 24 DC
VSPC GROUND
VSPC TEST Connector 24DC
VSPC GROUND
8924690000
8924680000
1
1
Type
Part No.
Qty.
Note
Ordering Data
Shield connection:
Complete set - cable ties and shield connection
Cable ties
Shield connection
Cable tie tool
35
Type
EMC set
Qty.
1
Part No.
1067470000
EMC tie
EMC connector
Cable tie tool RT-1
100
50
1
1067490000
1067520000
1296000000
VARITECTOR SPC
36
VARITECTOR SPC
VSPC 1CL EX – Protection for an analog
signal in intrinsically safe circuits
• P
luggable arrester (impedance neutral plugging/
unplugging without interruption)
• Can be tested with the V-TEST testing device
• Space-saving design for 1 analog signal
• Version with floating ground PE connection used to avoid
differences in voltage potential
• Can be used in compliance with the IEC 62305 installation
standard
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
• Can be used in zone 2, 1 and 0
• Certified for IEC 61643-21:08 D1, C1, C2, C3
Technical Data Arresters / Plugs
General data
Dielectric strength at FG against PE
> 500 V
Volume resistivity
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Surge strength C1
Surge strength C2
Surge strength C3
Surge strength D1
2.2 Ω
Mode 2
C1; C2; C3; D1
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
2.5 kA 10/350 µs
Rated discharge current IN (8/20 µs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 µs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp. (10/350 µs) wire-wire / wire-PE / GND-PE
Connection
Storage temperature
Ambient temperature (operational)
Rel. humidity
Degree of protection
2.5 kA / 2.5 kA / 2.5 kA
10 kA / 10 kA / 10 kA
2.5 kA / 2.5 kA / 2.5 kA
Pluggable in VSPC BASE
-40 °C…+80 °C
-40 °C…+70 °C
5 %…96 % RH
IP20
Flammability class EX protection data
Inner capacitance, max. Ci V0
Inner inductance, max. Li
Temperature class T6/85 °C ( -40 °C…+60 °C) Ii
Temperature class T5/100 °C ( -40 °C…+75 °C) Ii
Temperature class T4/135 °C ( -40 °C…+85 °C) Ii
0 µH
250 mA
250 mA
350 mA
Input power, max. Pi
Failure probability
λges
3W
MTTF
2537 years
ATEX Approval:
T II 1 G EX ia IIC T4…T6 Ga
T II 1 D Ex ia IIIC T135°C…T85°C Da
EU-type examination certificate No.: KEMA 10ATEX0148 X
37
Note
< 4 nF
45
VARITECTOR SPC
VSPC 1CL EX
Arresters / plugs
Bases and arresters should be ordered separately
Arrester / Plug
Arrester / plug
Base / socket
VSPC 1CL 5 V DC EX
VSPC 1CL 12 V DC EX
VSPC 1CL 24 V DC EX
Technical data
Rated voltage (DC)
Max. continuous voltage Uc (DC)
Input voltage, max. Ui
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage Up
wire-wire / wire-PE / GND-PE
5 V DC
12 V DC
24 V DC
6,4 V DC
6V
730 KHz
15 V DC
14 V
730 KHz
28 V DC
26 V
730 KHz
20 ms
< 650 V
12 V / 450 V / 650 V
20 ms
< 650 V
25 V / 450 V / 650 V
30 ms
< 650 V
45 V / 450 V / 650 V
< 12 V
< 12 V
< 25 V
< 25 V
< 45 V
< 45 V
< 450 V
< 650 V
< 450 V
< 650 V
< 450 V
< 650 V
IEC61643-21, IEC 62305, EN 60079-0.2009,
EN 60079-11:2007, EN 60079-26:2007,
EN 61241-11:2006
IEC61643-21, IEC 62305, EN 60079-0.2009,
EN 60079-11:2007, EN 60079-26:2007,
EN 61241-11:2006
IEC61643-21, IEC 62305, EN 60079-0.2009,
EN 60079-11:2007, EN 60079-26:2007,
EN 61241-11:2006
VSPC 1CL 5VDC ATEX
VSPC 1CL 12VDC ATEX
VSPC 1CL 24VDC ATEX
8953660000
8953590000
8953600000
1
1
1
VSPC BASE 1CL FG EX
VSPC BASE 1CL FG EX
VSPC BASE 1CL FG EX
0.5 mm² / 4 mm²
0.5 mm² / 4 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
7 mm
0.5...0.8 Nm
7 mm
0.5...0.8 Nm
7 mm
0.5...0.8 Nm
VSPC BASE 1CL FG EX
VSPC BASE 1CL FG EX
VSPC BASE 1CL FG EX
8951810000
8951810000
8951810000
1
1
1
Protection level on output side sym.
Input 1 kV/µs, typ.
Input 8/20 µs, typ.
Protection level on output side unsym.,
Input 1 kV/µs, typ.
Input 8/20 µs, typ.
Standards
Note
Ordering Data
Arrester / plug
Type
Part No.
Qty.
Note
Base / Socket
Technical data
Clamping range,
Rated connection, min./max.
Conductor cross section,
flexible, min./max.
solid, min./max.
stranded, min./max.
Stripping length
Tightening torque
Note
Ordering Data
Base / socket
Indirect earthing via gas dischargedType
tube FG, floating ground
Part No.
Qty.
Size of complete module
(arrester + base)
Length x width x height
Note:
90 x 17.8 x 69 mm
90 x 17.8 x 69 mm
90 x 17.8 x 69 mm
Accessories: Screwdrivers
SD 0.6x3.5x200 Part No.: 9010110000
Accessories: Screwdrivers
SD 0.6x3.5x200 Part No.: 9010110000
Accessories: Screwdrivers
SD 0.6x3.5x200 Part No.: 9010110000
38
VARITECTOR SPC
VSPC 2CL EX – Protection for an analog
signal in intrinsically safe circuits
• P
luggable arrester (impedance-neutral plugging/
unplugging without interruption)
• Can be tested with the V-TEST testing device
• Space-saving design for 2 analog signals
• Version with floating ground PE connection used to avoid
differences in voltage potential
• Can be used in compliance with the IEC 62305 installation
standard
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
• Can be used in zone 2, 1 and 0
• Certified for IEC 61643-21:08 D1, C1, C2, C3
Technical Data Arresters / Plugs
General data
Dielectric strength at FG against PE
> 500 V
Volume resistivity
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Surge strength C1
Surge strength C2
Surge strength C3
Surge strength D1
2.2 Ω
Mode 2
C1; C2; C3; D1
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
2.5 kA 10/350 µs
Rated discharge current IN (8/20 µs) wire-wire / wire-PE / GND-PE 2.5 kA / 2.5 kA / 2.5 kA
Rated discharge current Imax (8/20 µs) wire-wire / wire-PE / GND-PE 10 kA / 2 x 10 kA / 10 kA
Lightning test current, Iimp. (10/350 µs) wire-wire / wire-PE / GND-PE 2.5 kA / 2.5 kA / 2.5 kA
Connection
Pluggable in VSPC BASE
Storage temperature
-40 °C…+80 °C
Ambient temperature (operational)
-40 °C…+70 °C
Rel. humidity
5 %…96 % RH
Degree of protection
IP20
Flammability class EX protection data
Inner capacitance, max. Ci V0
Inner inductance, max. Li
Temperature class T6/85 °C ( -40 °C…+60 °C) Ii
Temperature class T5/100 °C ( -40 °C…+75 °C) Ii
Temperature class T4/135 °C ( -40 °C…+85 °C) Ii
0 µH
250 mA
250 mA
350 mA
Input power, max. Pi
Failure probability
λges
3W
45
MTTF
2537 years
ATEX Approval:
T II 1 G EX ia IIC T4…T6 Ga
T II 1 D Ex ia IIIC T135°C…T85°C Da
EU-type examination certificate No.: KEMA 10ATEX0148 X
39
Note
< 4 nF
VARITECTOR SPC
VSPC 2CL EX
Arresters / plugs
Bases and arresters should be ordered separately
Arrester / plug
Arrester / Plug
Base / socket
VSPC 2CL 24 V DC EX
Technical data
Rated voltage (DC)
24 V DC
Max. continuous voltage Uc (DC)
Input voltage, max. Ui
28 V DC
26 V
2.2 MHz
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage Up
wire-wire / wire-PE / GND-PE
30 ms
< 800 V
45 V / 450 V / 800 V
Protection level on output side sym.
< 45 V
< 45 V
Input 1 kV/µs, typ.
Input 8/20 µs, typ.
Protection level on output side unsym.,
Input 1 kV/µs, typ.
Input 8/20 µs, typ.
< 450 V
< 800 V
IEC61643-21, IEC 62305, EN 60079-0.2009,
EN 60079-11:2007, EN 60079-26:2007,
EN 61241-11:2009
Standards
Note
Ordering Data
Arrester / plug
Type
Part No.
Qty.
Note
VSPC 2CL 24VDC ATEX
8953720000
1
VSPC BASE 2CL FG EX
Base / Socket
Technical data
Clamping range,
Rated connection, min./max.
0.5 mm² / 4 mm²
Conductor cross section,
flexible, min./max.
solid, min./max.
stranded, min./max.
0.5 mm² / 2.5 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
7 mm
0.5...0.8 Nm
Stripping length
Tightening torque
Note
Ordering Data
Base / socket
Indirect earthing via gas dischargedType
tube FG, floating ground
Part No.
Qty.
Size of complete module
(arrester + base)
Length x width x height
Note:
VSPC BASE 2CL FG EX
8951820000
1
90 x 17.8 x 69 mm
Accessories: Screwdrivers
SD 0.6x3.5x200 Part No.: 9010110000
40
VARITECTOR SPC
VSPC 1CL PW EX – Combinations of
current-loop signal and device protection
in intrinsically safe circuits
• P
luggable arrester (impedance neutral plugging/
unplugging without interruption)
• Can be used to comply with the IEC 62305 installation
standard
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
• Can be used in zone 2, 1 and 0
• Certified for IEC 61643-21:08 D1, C1, C2, C3
• Certified for IEC 61643-11:09 class III
Technical Data Arresters / Plugs
Protection for the current loop
Rated voltage (DC)
Max. continuous voltage Uc (DC)
Dielectric strength at FG against PE
Volume resistivity
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Rated voltage (AC/DC)
Surge strength C1
Surge strength C2
Surge strength C3
Surge strength D1
Signal transmission properties (-3 dB)
Pulse reset capacity
27 V AC / 38 V DC
> 500 V
2.2 Ω
Mode 2
C1; C2; C3; D1
24 V AC / 33 V DC
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
2.5 kA 10/350 µs
730 KHz
10 ms
Rated discharge current IN (8/20 µs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 µs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp. (10/350 µs) wire-wire / wire-PE / GND-PE
Residual voltage Up
Residual voltage Up wire-wire / wire-PE / GND-PE
Protection level on output side sym. input 1 kV/µs, typ.
Protection level on output side sym., input 8/20 µs, typ.
Protection level on output side unsym., input 1 kV/µs, typ.
Protection level on output side unsym., input 8/20 µs, typ.
2.5 kA / 2.5 kA / 2.5 kA
10 kA / 10 kA / 10 kA
2.5 kA / 2.5 kA / 2.5 kA
800 V
60 V / 450 V / 800 V
< 60 V
< 60 V
< 450 V
< 800 V
Standards
IEC 61643-21, IEC 61643-1, IEC 62305, EN 600790.2009, EN 60079-11:2007, EN 60079-26:2007,
EN 61241-11:2009
Protection for Energy line III
Rated voltage (DC)
Max. continuous voltage UC (AC) / (DC)
EU-type examination certificate No.: KEMA 10ATEX0148 X
41
24 V AC / 34 V DC
Combined pulse
Residual voltage Up
27 V AC / 38 V DC
6 kV
900 V
Nominal current
0.35 A
ATEX Approval:
T II 1 G EX ia IIC T4…T6 Ga
T II 1 D Ex ia IIIC T135°C…T85°C Da
24 V AC / 34 V DC
Note
VARITECTOR SPC
VSPC 1CL PW EX
Arresters / plugs
Bases and arresters should be ordered separately
Arrester / plug
Arrester / Plug
Base / socket
VSPC 1CL PW 24 V EX
Technical data
Pluggable in VSPC BASE
Type of connection
Ambient temperature (operational)
Storage temperature
Requirement category acc. to IEC 61643-1 -40 °C…+70 °C
-40 °C…+80 °C
Class III
5 %…96 % RH
Rel. humidity
EX protection data
Degree of protection
IP20
Flammability class
Inner capacitance, max. Ci
Inner inductance, max. Li
Temperature class T6/85°C (-40°C…+60°C) Ii
Temperature class T5/100°C (-40°C…+75°C) Ii
Temperature class T4/135°C (-40°C…+85°C) Ii
Input power, max. Pi
V0
< 4 nF
0 µH
250 mA
250 mA
350 mA
3W
20 V
Input voltage, max. Ui
Failure probability
λges
45
2537 years
MTTF
Note
Ordering Data
Arrester / plug
Type
Part No.
Qty.
Note
VSPC 1CL PW 24V 0,5A
8951510000
1
VSPC BASE 1CL PW FG EX
Base / Socket
Technical data
Clamping range,
Rated connection, min./max.
0.5 mm² / 4 mm²
Conductor cross section,
flexible, min./max.
solid, min./max.
stranded, min./max.
0.5 mm² / 2.5 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
7 mm
Stripping length
0.5...0.8 Nm
Tightening torque
Note
Ordering Data
Base / socket
Indirect earthing via gas dischargedType
tube FG, floating ground
Part No.
Qty.
Size of complete module
(arrester + base)
Length x width x height
Note:
VSPC BASE 1CL PW FG EX
1070470000
1
90 x 17.8 x 69 mm
Accessories: Screwdrivers
SD 0.6x3.5x200 Part No.: 9010110000
42
VARITECTOR SPC
VSPC 2SL EX – Protection for two binary
signals in intrinsically safe circuits
• P
luggable arrester (impedance neutral plugging/
unplugging without interruption)
• Can be tested with the V-TEST testing device
• Space saving design for 2 binary signals
• Version with floating ground PE connection used to avoid
differences in voltage potential
• Can be used to comply with the IEC 62305 installation
standard
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
• Can be used in zone 2, 1 and 0
• Certified for IEC 61643-21:08 D1, C1, C2, C3
Technical Data Arresters / Plugs
General data
Dielectric strength at FG against PE
> 500 V
Volume resistivity
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Surge strength C1
Surge strength C2
Surge strength C3
Surge strength D1
4.7 Ω
Mode 2
C1; C2; C3; D1
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
2.5 kA 10/350 µs
Rated discharge current IN (8/20 µs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 µs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp. (10/350 µs) wire-wire / wire-PE / GND-PE
Type of connection
Storage temperature
Ambient temperature (operational)
Rel. humidity
Degree of protection
2.5 kA / 2.5 kA / 2.5 kA
10 kA / 10 kA / 10kA
2.5 kA / 2.5 kA / 2.5 kA
Pluggable in VSPC BASE
-40 °C…+80 °C
-40 °C…+70 °C
5 %…96 % RH
IP20
Flammability class EX protection data
Inner capacitance, max. Ci V0
Inner inductance, max. Li
Temperature class T6/85 °C ( -40 °C…+60 °C) Ii
Temperature class T5/100 °C ( -40 °C…+75 °C) Ii
0 µH
250 mA
250 mA
Input power, max. Pi
Failure probability
λges
3W
43
MTTF
2655 years
ATEX Approval:
T II 1 G EX ia IIC T4…T6 Ga
T II 1 D Ex ia IIIC T135°C…T85°C Da
EU-type examination certificate No.: KEMA 10ATEX0148 X
43
Note
< 4 nF
VARITECTOR SPC
VSPC 2SL EX
Arresters / plugs
Bases and arresters should be ordered separately
Arrester / plug
Arrester / Plug
VSPC 2SL 12 V DC EX
Base / socket
VSPC 2SL 12 V AC EX
VSPC 2SL 24 V DC EX
VSPC 2SL 48 V AC EX
12 V DC
12 V AC / 16 V DC
24 V DC
48 V AC / 68 V DC
15 V DC
14 V
300 mA
13.2 V AC / 18 V DC
19 V
300 mA
28 V DC
26 V
300 mA
60 V AC / 85 V DC
75 V
250 mA
750 KHz
20 ms
IEC 61643-21, IEC 62305,
EN 60079-0.2009, EN 6007911:2007, EN 60079-26:2007,
EN 61241-11:2009
< 50 V
45 V / 50 V / 50 V
750 KHz
20 ms
IEC 61643-21, IEC 62305,
EN 60079-0.2009, EN 6007911:2007, EN 60079-26:2007,
EN 61241-11:2009
< 50 V
55 V / 50 V / 50 V
750 KHz
30 ms
IEC 61643-21, IEC 62305,
EN 60079-0.2009, EN 6007911:2007, EN 60079-26:2007,
EN 61241-11:2009
< 60 V
80 V / 60 V / 60 V
750 KHz
60 ms
IEC 61643-21, IEC 62305,
EN 60079-0.2009, EN 6007911:2007, EN 60079-26:2007,
EN 61241-11:2009
< 125 V
80 V / 125 V / 125 V
Protection level on output side sym.
Input 1 kV/µs, typ.
Input 8/20 µs, typ.
< 45 V
< 45 V
< 55 V
< 55 V
< 80 V
< 80 V
< 210 V
< 80 V
Protection level on output side unsym.,
Input 1 kV/µs, typ.
Input 8/20 µs, typ.
< 25 V
< 50 V
< 30 V
< 50 V
< 40 V
< 60 V
< 85 V
< 125 V
300 mA
300 mA
300 mA
250 mA
VSPC 2SL 12VDC 0.5A ATEX
VSPC 2SL 12VAC 0.5A ATEX
VSPC 2SL 24VDC 0.5A ATEX
VSPC 2SL 48VAC 0.5A ATEX
8953620000
8953630000
8953670000
8953640000
1
1
1
1
VSPC BASE 2SL FG EX
VSPC BASE 2SL FG EX
VSPC BASE 2SL FG EX
VSPC BASE 2SL FG EX
0.5 mm² / 4 mm²
0.5 mm² / 4 mm²
0.5 mm² / 4 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
7 mm
0.5...0.8 Nm
7 mm
0.5...0.8 Nm
7 mm
0.5...0.8 Nm
7 mm
0.5...0.8 Nm
VSPC BASE 2SL FG EX
VSPC BASE 2SL FG EX
VSPC BASE 2SL FG EX
VSPC BASE 2SL FG EX
8951830000
8951830000
8951830000
8951830000
1
1
1
1
Technical data
Rated voltage UN
Max. continuous voltage UC (AC) / (DC)
Input voltage, max. Ui
Temperature class T4/135°C (-40°C…+85°C) Ii
Signal transmission properties (-3 dB)
Pulse reset capacity
Standards
Residual voltage Up
wire-wire / wire-PE / GND-PE
Nominal current
Note
Ordering Data
Arrester / plug
Type
Part No.
Qty.
Note
Base / Socket
Technical data
Clamping range,
Rated connection, min./max.
Conductor cross section,
flexible, min./max.
solid, min./max.
stranded, min./max.
Stripping length
Tightening torque
Note
Ordering Data
Base / socket
Indirect earthing via gas dischargedType
tube FG, floating ground
Part No.
Qty.
Size of complete module
(arrester + base)
Length x width x height
Note:
90 x 17.8 x 69 mm
90 x 17.8 x 69 mm
90 x 17.8 x 69 mm
90 x 17.8 x 69 mm
Accessories: Screwdrivers
SD 0.6x3.5x200 Part No.: 9010110000
Accessories: Screwdrivers
SD 0.6x3.5x200 Part No.: 9010110000
Accessories: Screwdrivers
SD 0.6x3.5x200 Part No.: 9010110000
Accessories: Screwdrivers
SD 0.6x3.5x200 Part No.: 9010110000
44
VARITECTOR SPC
VSPC 4SL EX – Protection for four binary
signals in intrinsically safe circuits
• P
luggable arrester (impedance neutral plugging/
unplugging without interruption)
• Can be tested with the V-TEST testing device
• Space saving design for 4 binary signals
• Version with floating ground PE connection used to avoid
differences in voltage potential
• Can be used to comply with the IEC 62305 installation
standard
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
• Can be used in zone 2, 1 and 0
• Certified for IEC 61643-21:08 D1, C1, C2, C3
Technical Data Arresters / Plugs
General data
Volume resistivity
4.7 Ω
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Surge strength C1
Surge strength C2
Surge strength C3
Surge strength D1
Mode 2
C1; C2; C3; D1
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
2.5 kA 10/350 µs
Rated discharge current IN (8/20 µs) wire-wire / wire-PE / GND-PE
2.5 kA / 2.5 kA / 2.5 kA
Rated discharge current Imax (8/20 µs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp. (10/350 µs) wire-wire / wire-PE / GND-PE
Type of connection
Storage temperature
Ambient temperature (operational)
Rel. humidity
Degree of protection
10 kA / 10 kA / 10 kA
2.5 kA / 2.5 kA / 2.5 kA
Pluggable in VSPC BASE
-40 °C … +80 °C
-40 °C … +70 °C
5 % … 96 % RH
IP20
Flammability class EX protection data
Inner capacitance, max. Ci V0
Inner inductance, max. Li
Temperature class T6/85 °C ( -40 °C…+60 °C) Ii
Temperature class T5/100 °C ( -40 °C…+75 °C) Ii
Temperature class T4/135 °C ( -40 °C…+85 °C) Ii
0 µH
250 mA
250 mA
300 mA
Input power, max. Pi
Failure probability
λges
3W
43
MTTF
2655 years
ATEX Approval:
T II 1 G EX ia IIC T4…T6 Ga
T II 1 D Ex ia IIIC T135°C…T85°C Da
EU-type examination certificate No.: KEMA 10ATEX0148 X
45
Note
< 4 nF
VARITECTOR SPC
VSPC 4SL EX
Arresters / plugs
Bases and arresters should be ordered separately
Arrester / plug
Arrester / Plug
VSPC 4SL 12 V DC EX
Technical data
Rated voltage UN
Max. continuous voltage UC (AC) / (DC)
Input voltage, max. Ui
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage Up
wire-wire / wire-PE / GND-PE
Base / socket
VSPC 4SL 12 V AC EX
VSPC 4SL 24 V DC EX
VSPC 4SL 24 V AC EX
12 V DC
12 V AC / 16 V DC
24 V DC
24 V AC / 34 V DC
15 V DC
14 V
750 KHz
13.2 V AC / 18 V DC
19 V
750 KHz
28 V DC
26 V
750 KHz
28 V AC / 39 V DC
38 V
750 KHz
20 ms
< 35 V
45 V / 20 V / 450 V
20 ms
< 50 V
55 V / 50 V / 50 V
30 ms
< 60 V
80 V / 60 V / 60 V
40 ms
< 60 V
80 V / 60 V / 60 V
< 45 V
< 45 V
< 55 V
< 55 V
< 80 V
< 80 V
< 110 V
< 80 V
< 25 V
< 50 V
300 mA
< 30 V
< 50 V
300 mA
< 40 V
< 60 V
300 mA
< 60 V
< 60 V
300 mA
IEC 61643-21, IEC 62305,
EN 60079-0.2009, EN 6007911:2007, EN 60079-26:2007,
EN 61241-11:2009
IEC 61643-21, IEC 62305,
EN 60079-0.2009, EN 6007911:2007, EN 60079-26:2007,
EN 61241-11:2009
IEC 61643-21, IEC 62305,
EN 60079-0.2009, EN 6007911:2007, EN 60079-26:2007,
EN 61241-11:2009
IEC 61643-21, IEC 62305,
EN 60079-0.2009, EN 6007911:2007, EN 60079-26:2007,
EN 61241-11:2009
VSPC 4SL 12VDC 0.5A ATEX
VSPC 4SL 12VAC 0.5A ATEX
VSPC 4SL 24VDC 0.5A ATEX
VSPC 4SL 24VAC 0.5A ATEX
1161170000
1161150000
1161190000
1161180000
1
1
1
1
VSPC BASE 4SL FG EX
VSPC BASE 4SL FG EX
VSPC BASE 4SL FG EX
VSPC BASE 4SL FG EX
0.5 mm² / 4 mm²
0.5 mm² / 4 mm²
0.5 mm² / 4 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 2.5 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
7 mm
0.5...0.8 Nm
7 mm
0.5...0.8 Nm
7 mm
0.5...0.8 Nm
7 mm
0.5...0.8 Nm
VSPC BASE 4SL FG EX
VSPC BASE 4SL FG EX
VSPC BASE 4SL FG EX
VSPC BASE 4SL FG EX
8951840000
8951840000
8951840000
8951840000
1
1
1
1
Protection level on output side sym.
Input 1 kV/µs, typ.
Input 8/20 µs, typ.
Protection level on output side unsym.,
Input 1 kV/µs, typ.
Input 8/20 µs, typ.
Nominal current
Standards
Note
Ordering Data
Arrester / plug
Type
Part No.
Qty.
Note
Base / Socket
Technical data
Clamping range,
Rated connection, min./max.
Conductor cross section,
flexible, min./max.
solid, min./max.
stranded, min./max.
Stripping length
Tightening torque
Note
Ordering Data
Base / socket
Indirect earthing via gas dischargedType
tube FG, floating ground
Part No.
Qty.
Size of complete module
(arrester + base)
Length x width x height
Note:
90 x 17.8 x 69 mm
90 x 17.8 x 69 mm
90 x 17.8 x 69 mm
90 x 17.8 x 69 mm
Accessories: Screwdrivers
SD 0.6x3.5x200 Part No.: 9010110000
Accessories: Screwdrivers
SD 0.6x3.5x200 Part No.: 9010110000
Accessories: Screwdrivers
SD 0.6x3.5x200 Part No.: 9010110000
Accessories: Screwdrivers
SD 0.6x3.5x200 Part No.: 9010110000
46
VARITECTOR SPC
VSPC 3/4 WIRE EX – 3/4 wire measurements
in intrinsically safe circuits
• P
luggable arrester (impedance neutral plugging/
unplugging without interruption)
• Protection for measuring bridge signals
• Can be tested with the V-TEST testing device
• Can be used to comply with the IEC 62305 installation
standard
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
• Can be used in zone 2, 1 and 0
• Certified for IEC 61643-21:08 D1, C1, C2, C3
Technical Data Arresters / Plugs
General data
Input voltage,max. Ui
6V
Volume resistivity
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Surge strength C1
Surge strength C2
Surge strength C3
Surge strength D1
0.2 Ω
Mode 2
C1; C2; C3; D1
< 1 kA / 8/20 µs
5 kA / 8/20 µs
100 A / 10/1000 µs
2.5 kA 10/350 µs
Rated discharge current IN (8/20 µs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 µs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp. (10/350 µs) wire-wire / wire-PE / GND-PE
Type of connection
Storage temperature
Ambient temperature (operational)
Rel. humidity
Degree of protection
2.5 kA / 2.5 kA / 2.5 kA
10 kA / 10 kA / 10 kA
2.5 kA / 2.5 kA / 2.5 kA
Pluggable in VSPC BASE
-40 °C…+80 °C
-40 °C...+70 °C
5 %...96 % RH
IP20
Flammability class EX protection data
Inner capacitance, max. Ci V0
Inner inductance, max. Li
Temperature class T6/85 °C ( -40 °C…+60 °C) Ii
Temperature class T5/100 °C ( -40 °C…+75 °C) Ii
Temperature class T4/135 °C ( -40 °C…+85 °C) Ii
0 µH
250 mA
250 mA
300 mA
Input power, max. Pi
Failure probability
λges
3W
43
MTTF
2655 years
ATEX Approval:
T II 1 G EX ia IIC T4…T6 Ga
T II 1 D Ex ia IIIC T135°C…T85°C Da
EU-type examination certificate No.: KEMA 10ATEX0148 X
47
Note
< 4 nF
VARITECTOR SPC
VSPC 3/4 WIRE EX
Arresters / plugs
Bases and arresters should be ordered separately
Arrester / plug
Arrester / Plug
Base / socket
VSPC 3/4WIRE 5 V DC EX
Technical data
3 V DC
Rated voltage (DC)
Max. continuous voltage Uc (DC)
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage Up
wire-wire / wire-PE / GND-PE
6.4 V DC
730 KHz
20 ms
< 800 V
35 V / 800 V / 500 V
Protection level on output side sym.
Input 1 kV/µs, typ.
Input 8/20 µs, typ.
< 35 V
< 35 V
Protection level on output side unsym.,
Input 1 kV/µs, typ.
Input 8/20 µs, typ.
< 250 V
< 800 V
IEC 61643-21, IEC 62305,
EN 60079-0.2009, EN 60079-11:2007,
EN 60079-26:2007, EN 61241-11:2009
Standards
Note
Ordering Data
Arrester / plug
Type
Part No.
Qty.
Note
VSPC 3/4WIRE 5VDC ATEX
8953650000
1
VSPC BASE 4SL FG EX
Base / Socket
Technical data
Clamping range,
Rated connection, min./max.
0.5 mm² / 4 mm²
Conductor cross section,
flexible, min./max.
solid, min./max.
stranded, min./max.
0.5 mm² / 2.5 mm²
0.5 mm² / 4 mm²
0.5 mm² / 2.5 mm²
7 mm
0.5...0.8 Nm
Stripping length
Tightening torque
Note
Ordering Data
Base / socket
Indirect earthing via gas dischargedType
tube FG, floating ground
Part No.
Qty.
Size of complete module
(arrester + base)
Length x width x height
Note:
VSPC BASE 4SL FG EX
8951840000
1
90 x 17.8 x 69 mm
Accessories: Screwdrivers
SD 0.6x3.5x200 Part No.: 9010110000
48
VARITECTOR SSC
VSSC 6AN CL and TR CL – Protection for
analog signals (CL) with and without
disconnect lever (TR)
Two stage surge protection with screw connection for
instrumentation, control and automation technology
• Surge protection in terminal block format
• Modular width of just 6.2 mm
• Space saving design: 1 analog signal
• Torx® slotted screw connection
• Can be used to comply with the IEC 62305 installation
standard and the IEC 61643-1/-22 standards
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
General data
Nominal current
500 mA (see derating curve)
Dielectric strength at FG against PE
Volume resistivity
Overstressed fault mode
Requirement category IEC 61643-21
Standards
Surge strength C2
Surge strength C3
–
1.8 Ω ± 10 %
Mode 2
C2; C3; D1
IEC 61643-21
2.5 kA
50 A
Surge strength D1
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp (10/350 μs) wire-wire / wire-PE / GND-PE
Storage temperature
Ambient temperature (operational)
Humidity
Degree of protection
0.5 kA
2.5 kA / 2.5 kA / –
5 kA / 5 kA / –
– / 0.5 kA / –
-40 °C...+80 °C
-40 °C...+70 °C
5...96 % RH
IP20
Flammability class
Connection data
Connection
V0
Tightening torque
Conductor cross section, flexible, ferrule (DIN 46228-1), max.
Conductor cross section, flexible, ferrule (DIN 46228-1), min.
Conductor cross section, solid, max.
Conductor cross section, solid, min.
Conductor cross section, stranded, Rated connection, max.
Conductor cross section, stranded, Rated connection, min.
Stripping length
0.5 Nm
4 mm²
0.5 mm²
6 mm²
0.5 mm²
4 mm²
0.5 mm²
10 mm
Mounting rail
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
TS35
Dimensions
Length x width x height
Torx® T15 / slot 0.8 x 4
88.5 x 6.2 x 81 mm
Accessories: Screwdriver: Torx® 9009170000, slotted 9008340000; test plug: PS 2.3 0180400000; EMC SET: 1067470000;
marker: WS 10/6 1818400000, DEK 6 0468560000, SNAPMARK 1805880000; end plate: 1063110000
49
VARITECTOR SSC
VSSC CL and TR CL
Technical Data
CL 12 V DC
CL 24 V UC
CL 48 V UC
Rated voltage AC/DC
12 V DC
24 V AC / 34 V DC
48 V AC / 68 V DC
60 V AC / 85 V DC
15 V DC
≤ 700 kHz
≤ 20 ms
30 V AC / 42 V DC
≤ 700 kHz
≤ 170 ms
60 V AC / 85 V DC
≤ 700 kHz
≤ 150 ms
75 V AC / 106 V DC
≤ 700 kHz
≤ 20 ms
≤ 1600 V
35 V / 900 V / -
≤ 1650 V
90 V / 900 V / -
≤ 1510 V
200 V / 770 V / -
≤ 1520 V
260 V / 780 V / -
Protection level on output side sym.,
input 1 kV/µs, typ.
30 V
70 V
70 V
200 V
Protection level on output side unsym.,
input 1 kV/µs, typ.
900 V
900 V
770 V
780 V
VSSC6 CL 12Vdc 0.5A
VSSC6 CL 24Vuc 0.5A
1064170000
VSSC6 CL 48Vuc 0.5A
VSSC6 CL 60Vuc 0.5A
1064150000
1064190000
1064210000
10 pieces
10 pieces
10 pieces
10 pieces
Technical Data
TR CL 12 V DC
TR CL 24 V UC
TR CL 48 V UC
TR CL 60 V UC
Rated voltage AC/DC
12 V DC
24 V AC/ 34 V DC
48 V AC / 68 V DC
60 V AC / 85 V DC
15 V DC
≤ 700 kHz
≤ 20 ms
≤ 1600 V
35 V / 900 V / -
30 V AC/ 42 V DC
≤ 700 kHz
≤ 170 ms
≤ 1650 V
90 V / 900 V / -
60 V AC / 85 V DC
≤ 700 kHz
≤ 150 ms
≤ 1510 V
200 V / 770 V / -
75 V AC / 106 V DC
≤ 700 kHz
≤ 20 ms
≤ 1520 V
260 V / 780 V / -
Protection level on output side sym.,
input 1 kV/µs, typ.
30 V
70 V
150 V
200 V
Protection level on output side unsym.,
input 1 kV/µs, typ.
900 V
900 V
770 V
780 V
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage UP
wire-wire / wire-PE / GND-PE
Ordering data
Type
Part No.
Qty.
CL 60 V UC
Note
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage UP
wire-wire / wire-PE / GND-PE
Yes
Disconnect lever
Testing option
Ordering data
Type
Part No.
Qty.
Yes
Yes
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
Functional screw with test plug
receptacle connection 1, 2, 4, 5
Functional screw with test plug
receptacle connection 1, 2, 4, 5
Functional screw with test plug
receptacle connection 1, 2, 4, 5
VSSC6 TR CL 12Vdc 0.5A
VSSC6 TR CL 24Vuc 0.5A
VSSC6 TR CL 48Vuc 0.5A
VSSC6 TR CL 60Vuc 0.5A
1064220000
1064230000
1064240000
1064250000
10 pieces
10 pieces
10 pieces
10 pieces
Note
50
VARITECTOR SSC
VSSC 6AN CLFG and TR CLFG – Protection for
analog signals (CL) with floating ground (FG)
with and without disconnect lever (TR)
Two stage surge protection with screw connection for
instrumentation, control and automation technology
• Surge protection in terminal-block format
• Modular width of just 6.2 mm
• Space saving design: 1 analog signal
• Torx® slotted screw connection
• Can be used to comply with the IEC 62305 installation
standard and the IEC 61643-1/-22 applications standards.
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
• Version with floating ground PE connection used to avoid
differences in voltage potential
Technical Data
General data
Nominal current
500 mA (see derating curve)
Dielectric strength at FG against PE
Volume resistivity
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Standards
Surge strength C2
Surge strength C3
≥ 500 V
1.8 Ω ± 10 %
Mode 2
C2; C3; D1
IEC 61643-21
2.5 kA
50 A
Surge strength D1
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp (10/350 μs) wire-wire / wire-PE / GND-PE
Storage temperature
Ambient temperature (operational)
Humidity
Degree of protection
0.5 kA
2.5 kA / 2.5 kA / –
5 kA / 5 kA / –
– / 0.5 kA / –
-40 °C...+80 °C
-40 °C...+70 °C
5...96 % RH
IP20
Flammability class
Connection data
Connection
V0
Tightening torque
Conductor cross section, flexible, ferrule (DIN 46228-1), max.
Conductor cross section, flexible, ferrule (DIN 46228-1), min.
Conductor cross section, solid, max.
Conductor cross section, solid, min.
Conductor cross section, stranded, Rated connection, max.
Conductor cross section, stranded, Rated connection, min.
Stripping length
0.5 Nm
4 mm²
0.5 mm²
6 mm²
0.5 mm²
4 mm²
0.5 mm²
10 mm
Mounting rail
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
TS35
Dimensions
Length x width x height
Torx® screw T15 / slot 0.8 x 4
88.5 x 6.2 x 81 mm
Accessories: Screwdriver: Torx® 9009170000, slotted 9008340000; test plug: PS 2.3 0180400000; EMC SET: 1067470000;
marker: WS 10/6 1818400000, DEK 6 0468560000, SNAPMARK 1805880000; end plate: 1063110000
51
VARITECTOR SSC
VSSC 6AN CLFG and TR CLFG
Technical Data
CLFG 12 V DC
CLFG 24 V UC
CLFG 48 V UC
CLFG 60 V UC
Rated voltage AC/DC
12 V DC
24 V AC/ 34 V DC
48 V AC / 68 V DC
15 V DC
≤ 700 kHz
≤ 20 ms
30 V AC / 42 V DC
≤ 700 kHz
≤ 20 ms
60 V AC / 85 V DC
≤ 700 kHz
≤ 20 ms
60 V AC / 85 V DC
75 V AC / 106 V DC
≤ 35 V
35 V / 1600 V / 800 V
≤ 85 V
90 V / 1632 V / 800 V
≤ 90 V
200 V / 1510 V / 800 V
≤ 700 kHz
≤ 20 ms
≤ 300 V
260 V / 1510 V / 800 V
30 V
70 V
150 V
200 V
1600 V
1632 V
1510 V
1510 V
VSSC6 CLFG 12VDC 0.5A
VSSC6 CL FG24VUC 0.5A
VSSC6 CLFG 48VUC 0.5A
VSSC6 CLFG 60VUC 0.5A
1064260000
1064270000
1064280000
1064290000
10 pieces
10 pieces
10 pieces
10 pieces
Technical Data
TR CLFG 12 V DC
TR CLFG 24 V UC
TR CLFG 48 V UC
TR CLFG 60 V UC
Rated voltage AC/DC
12 V DC
24 V AC / 34 V DC
48 V AC / 68 V DC
60 V AC / 85 V DC
15 V DC
≤ 700 kHz
≤ 20 ms
≤ 35 V
35 V / 1600 V / 800 V
30 V AC / 42 V DC
≤ 700 kHz
≤ 20 ms
≤ 85 V
90 V / 1632 V / 800 V
60 V AC / 85 V dc
≤ 700 kHz
≤ 20 ms
≤ 90 V
200 V / 1510 V / 800 V
75 V AC / 106 V DC
≤ 700 kHz
≤ 20 ms
≤ 300 V
260 V / 1510 V / 800 V
30 V
70 V
150 V
200 V
1600 V
1632 V
1510 V
1510 V
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage UP
wire-wire / wire-PE / GND-PE
Protection level on output side sym.
Input 1 kV/µs, typ.
Protection level on output side unsym.,
Input 1 kV/µs, typ.
Ordering data
Type
Part No.
Qty.
Note
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage UP
wire-wire / wire-PE / GND-PE
Protection level on output side sym.
Input 1 kV/µs, typ.
Protection level on output side unsym.,
Input 1 kV/µs, typ.
Disconnect lever
Testing option
Ordering data
Type
Part No.
Qty.
Note
yes
yes
yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
Functional screw with test plug
receptacle connection 1, 2, 4, 5
Functional screw with test plug
receptacle connection 1, 2, 4, 5
VSSC6 TR CLFG 12Vdc0.5
VSSC6TR CLFG 24VUC 0.5A
VSSC6 TR CLFG 48VUC 0.5A
VSSC6 TR CLFG 60VUC 0.5A
1064300000
1064310000
1064320000
1064330000
10 pieces
10 pieces
10 pieces
10 pieces
52
VARITECTOR SSC
VSSC 6AN SL and TR SL – Protection for
binary signals (SL) with and without
disconnect lever (TR) and indicator (LD)
Two-stage surge protection with screw connection for
instrumentation, control and automation technology
• Surge protection in terminal-block format
• Modular width of just 6.2 mm
• Space saving design: 2 binary signals
• Torx® slotted screw connection
• Can be used to comply with the IEC 62305 installation
standard and the IEC 61643-1/-22 applications standards
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
General data
Nominal current
500 mA (see derating curve)
Dielectric strength at FG against PE
Volume resistivity
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Standards
Surge strength C2
Surge strength D1
–
1.8 Ω ± 10 %
Mode 2
C2; C3; D1
IEC 61643-21
2.5 kA
1 kA
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp (10/350 μs) wire-wire / wire-PE / GND-PE
Storage temperature
Ambient temperature (operational)
Humidity
Degree of protection
– / 2.5 kA / –
– / 10 kA / –
– / 1 kA / –
-40 °C...+80 °C
-40 °C...+70 °C
5...96 % RH
IP20
Flammability class
Connection data
Connection
V0
Tightening torque
Conductor cross section, flexible, ferrule (DIN 46228-1), max.
Conductor cross section, flexible, ferrule (DIN 46228-1), min.
Conductor cross section, solid, max.
Conductor cross section, solid, min.
Conductor cross section, stranded, Rated connection, max.
Conductor cross section, stranded, Rated connection, min.
Stripping length
0.5 Nm
4 mm²
0.5 mm²
6 mm²
0.5 mm²
4 mm²
0.5 mm²
10 mm
TS35
Mounting rail
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
Dimensions
Length x width x height
Torx® screw T15 / slot 0.8 x 4
88.5 x 6.1 x 81 mm
Accessories: Screwdriver: Torx® 9009170000, slotted 9008340000; test plug: PS 2.3 0180400000; EMC SET: 1067470000;
marker: WS 10/6 1818400000, DEK 6 0468560000, SNAPMARK 1805880000; end plate: 1063110000
53
VARITECTOR SSC
VSSC 6AN SL and TR SL
Technical Data
SL LD 12 V DC
SL LD 24 V UC
Rated voltage AC/DC
12 V DC
24 V AC / 34 V DC
48 V AC/ 68 V DC
60 V AC / 85 V DC
15 V DC
≤ 700 kHz
≤ 30 ms
30 V AC / 42 V DC
≤ 700 kHz
≤ 30 ms
60 V AC / 85 V DC
≤ 700 kHz
≤ 30 ms
75 V AC / 106 V DC
≤ 700 kHz
≤ 30 ms
≤ 40 V
- / 74 V / -
≤ 100 V
- / 110 V / -
≤ 220 V
- / 175 V / -
≤ 330 V
- / 230 V / -
-
-
-
-
Protection level on output side unsym.,
Input 1 kV/µs, typ.
74 V
110 V
175 V
230 V
Surge strength C3
10 A
50 A
50 A
50 A
Status indicator
Ordering data
Type
Yes
Yes
Yes
Yes
VSSC6 SL LD 12VDC 0.5A
VSSC6 SL LD 24VUC 0.5A
VSSC6 SL LD 48VUC 0.5A
VSSC6 SL LD 60VUC 0.5A
1064340000
1064350000
10 pieces
10 pieces
10 pieces
10 pieces
Technical Data
TR SL LD 12 V DC
TR SL LD 24 V UC
TR SL LD 48 V UC
TR SL LD 60 V UC
Rated voltage AC/DC
12 V DC
24 V AC / 34 V DC
48 V AC/ 68 V DC
60 V AC / 85 V DC
15 V DC
≤ 700 kHz
≤ 30 ms
≤ 40 V
- / 74 V / -
30 V AC / 42 V DC
≤ 700 kHz
≤ 30 ms
≤ 100 V
- / 110 V / -
60 V AC / 85 V DC
≤ 700 kHz
≤ 30 ms
≤ 220 V
- / 175 V / -
75 V AC / 106 V DC
≤ 700 kHz
≤ 30 ms
≤ 330 V
- / 230 V / -
-
-
-
-
74 V
110 V
175 V
230 V
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage UP
wire-wire / wire-PE / GND-PE
Protection level on output side sym.
Input 1 kV/µs, typ.
Part No.
Qty.
SL LD 4w8 V UC
1064360000
SL LD 60 V UC
1064370000
Note
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage UP
wire-wire / wire-PE / GND-PE
Protection level on output side sym.
Input 1 kV/µs, typ.
Protection level on output side unsym.,
Input 1 kV/µs, typ.
Surge strength C3
Disconnect lever
Testing option
10 A
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
Status indicator
Ordering data
Type
Part No.
Qty.
50 A
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
50 A
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
50 A
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
Yes
Yes
Yes
Yes
VSSC6 TR SL LD12Vdc0.5A
VSSC6 TR SL LD 24VUC 0.5A
VSSC6 TR SL LD 48VUC 0.5A
VSSC6 TR SL LD 60VUC 0.5A
1064380000
1064390000
1064400000
1064410000
10 pieces
10 pieces
10 pieces
10 pieces
Note
54
VARITECTOR SPC
VSSC 6AN SLFG and TR SLFG – Protection for
binary signals (SL) with floating ground (FG), with
and without disconnect lever (TR) and indicator (LD)
Two stage surge protection with screw connection for
instrumentation, control and automation technology
• Surge protection in terminal block format
• Modular width of just 6.2 mm
• Space saving design: 2 binary signals
• Torx® slotted screw connection
• Can be used to comply with the IEC 62305 installation
standard and the IEC 61643-1/-22 applications standards
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
• Version with floating ground PE connection used to avoid
differences in voltage potential
Technical Data
General data
Dielectric strength at FG against PE
≥ 500 V
Volume resistivity
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Standards
Surge strength C2
Surge strength C3
Surge strength D1
1.8 Ω ± 10 %
Mode 2
C2; C3; D1
IEC 61643-21
2.5 kA
10 A; 50 A @ 60 V
1 kA
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp (10/350 μs) wire-wire / wire-PE / GND-PE
Storage temperature
Ambient temperature (operational)
Humidity
Degree of protection
– / 2.5 kA / 2.5 kA
– / 10 kA / 10 kA
– / 10 kA / –
-40 °C...+80 °C
-40 °C...+70 °C
5...96 % RH
IP20
Flammability class
Connection data
Connection
V0
Tightening torque
Conductor cross section, flexible, ferrule (DIN 46228-1), max.
Conductor cross section, flexible, ferrule (DIN 46228-1), min.
Conductor cross section, solid, max.
Conductor cross section, solid, min.
Conductor cross section, stranded, Rated connection, max.
Conductor cross section, stranded, Rated connection, min.
Stripping length
0.5 Nm
4 mm²
0.5 mm²
6 mm²
0.5 mm²
4 mm²
0.5 mm²
10 mm
Mounting rail
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
TS35
Dimensions
Length x width x height
Torx® screw T15 / slot 0.8 x 4
88.5 x 6.2 x 81 mm
Accessories: Screwdriver: Torx® 9009170000, slotted 9008340000; test plug: PS 2.3 0180400000; EMC SET: 1067470000;
marker: WS 10/6 1818400000, DEK 6 0468560000, SNAPMARK 1805880000; end plate: 1063110000
55
VARITECTOR SSC
VSSC 6AN SLFG and TR SLFG
Technical Data
SLFG LD 12 V DC
SLFG LD 24 V UC
SLFG LD 48 V UC
Rated voltage AC/DC
12 V DC
24 V AC / 34 V DC
48 V AC / 68 V DC
60 V AC / 85 V DC
15 V DC
≤ 700 kHz
≤ 20 ms
30 V AC / 42 V DC
≤ 700 kHz
≤ 20 ms
60 V AC / 85 V DC
≤ 700 kHz
≤ 20 ms
75 V AC / 106 V DC
≤ 700 kHz
≤ 20 ms
≤ 1600 V
- / 74 V / 1400 V
≤ 1650 V
- / 110 V / 1400 V
≤ 1550 V
- / 175 V / 1200 V
≤ 1550 V
- / 230 V / 1200 V
30 V
70 V
150 V
200 V
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage UP
wire-wire / wire-PE / GND-PE
SLFG LD 60 V UC
Protection level on output side sym.
Input 1 kV/µs, typ.
Protection level on output side unsym.,
Input 1 kV/µs, typ.
Nominal current
Status indicator
Ordering data
Type
Part No.
Qty.
74 V
110 V
175 V
230 V
500 mA
200 mA (IEC 61643-21)
on request
on request
yes
yes
yes
yes
VSSC6 SLFG 12VDC 0.5A
VSSC6 SLFG 24VUC 0.5A
VSSC6 SLFG 48VUC 0.5A
VSSC6 SLFG 60VUC 0.5A
1064420000
1064430000
1064440000
1064470000
10 pieces
10 pieces
10 pieces
10 pieces
Note
Technical Data
TR SLFG LD 12 V DC TR SLFG LD 24 V UC TR SLFG LD 48 V UC TR SLFG LD 60 V UC
Rated voltage AC/DC
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage UP
wire-wire / wire-PE / GND-PE
12 V DC
24 V AC / 34 V DC
48 V AC / 68 V DC
60 V AC / 85 V DC
15 V DC
≤ 700 kHz
≤ 20 ms
≤ 1600 V
- / 74 V / 1400 V
30 V AC / 42 V DC
≤ 700 kHz
≤ 20 ms
≤ 1650 V
- / 110 V / 1400 V
60 V AC / 85 V DC
≤ 700 kHz
≤ 20 ms
≤ 1550 V
- / 175 V / 1200 V
75 V AC / 106 V DC
≤ 700 kHz
≤ 20 ms
≤ 1550 V
- / 230 V / 1200 V
30 V
70 V
150 V
200 V
Protection level on output side sym.
Input 1 kV/µs, typ.
Protection level on output side unsym.,
Input 1 kV/µs, typ.
Nominal current
Disconnect lever
Testing option
Status indicator
Ordering data
Type
Part No.
Qty.
74 V
110 V
175 V
230 V
500 mA
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
200 mA (IEC 61643-21)
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
on request
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
on request
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
Yes
Yes
Yes
Yes
VSSC6 TR SLFG LD 12VDC 0.5A
VSSC6 TR SLFG LD 24VUC 0.5A
VSSC6 TR SL FG LD 48VUC 0.5A
VSSC6 TR SLFG LD 60VUC 0.5A
1064490000
10 pieces
1064500000
10 pieces
1064510000
10 pieces
1064520000
10 pieces
Note
56
VARITECTOR SSC
VSSC 6AN MOV and TR LD MOV 12 V DC
and 24 V UC – with varistor, with and without
disconnect lever (TR) and indicator (LD)
Surge protection with screw connection for
instrumentation, control and automation technology
• Surge protection in terminal block format
• Modular width of just 6.2 mm
• Space saving design: 2 analog signals
• Torx® slotted screw connection
• Can be used to comply with the IEC 62305 installation
standard and the IEC 61643-1/-22 applications standards
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
General data
Nominal current
Volume resistivity
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Standards
Surge strength C1
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Storage temperature
Ambient temperature (operational)
Humidity
Degree of protection
12 A (see derating curve)
< 0.1 Ω
Mode 1
C1
IEC 61643-21 (Pending)
0.25 kA
– / 500 A / –
– / 1 kA / –
-40 °C...+80 °C
-40 °C...+70 °C
5...96 % RH
IP20
Flammability class
Connection data
Connection
V0
Tightening torque
Conductor cross section, flexible, ferrule (DIN 46228-1), max.
Conductor cross section, flexible, ferrule (DIN 46228-1), min.
Conductor cross section, solid, max.
Conductor cross section, solid, min.
Conductor cross section, stranded, Rated connection, max.
Conductor cross section, stranded, Rated connection, min.
Stripping length
0.5 Nm
4 mm²
0.5 mm²
6 mm²
0.5 mm²
4 mm²
0.5 mm²
10 mm
Mounting rail
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
TS35
Dimensions
Length x width x height
Torx® screw T15 / slot 0.8 x 4
88.5 x 6.2 x 81 mm
Accessories: Screwdriver: Torx® 9009170000, slotted 9008340000; test plug: PS 2.3 0180400000; EMC SET: 1067470000;
marker: WS 10/6 1818400000, DEK 6 0468560000, SNAPMARK 1805880000; end plate: 1063110000
57
VARITECTOR SSC
VSSC MOV and TR LD MOV
12 V DC and 24 V UC
Technical Data
MOV 12 V DC
MOV 24 V UC
Rated voltage AC/DC
12 V DC
24 V AC / 34 V DC
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Residual voltage UP
15 V DC
≤ 100 kHz
≤ 50 V
30 V AC / 42 V DC
≤ 400 kHz
≤ 100 V
wire-wire / wire-PE / GND-PE
- / 57 V / -
- / 120 V / -
50 V
150 V
VSSC6 MOV 12VDC
VSSC6 MOV 24VUC
1064530000
1064540000
10 pieces
10 pieces
Technical Data
TR LD MOV 12 V DC
TR LD MOV 24 V UC
Rated voltage AC/DC
12 V DC
24 V AC / 34 V DC
15 V DC
≤ 100 kHz
≤ 50 V
- / 57 V / -
30 V AC / 42 V DC
≤ 400 kHz
≤ 100 V
- / 120 V / -
50 V
150 V
Protection level on output side sym.
Input 1 kV/µs, typ.
Ordering data
Type
Part No.
Qty.
Note
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Residual voltage UP
wire-wire / wire-PE / GND-PE
Protection level on output side sym.
Input 1 kV/µs, typ.
Disconnect lever
Testing option
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
Status indicator
Ordering data
Type
Part No.
Qty.
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
Yes
Yes
VSSC6 TR LD MOV 12VDC
VSSC6 TR MOV 24VUC
1064800000
1064810000
10 pieces
10 pieces
Note
58
VARITECTOR SSC
VSSC 6AN MOV and TR LD MOV
48 V UC and 60 V UC – with varistor,
with and without disconnect lever (TR)
and indicator (LD)
Surge protection with screw connection for
instrumentation, control and automation technology
• Surge protection in terminal block format
• Modular width of just 6.2 mm
• Space saving design: 2 analog signals
• Torx® slotted screw connection
• Can be used to comply with the IEC 62305 installation
standard and the IEC 61643-1/-22 applications standards
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
General data
Nominal current
Volume resistivity
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Standards
Surge strength C1
Surge strength C2
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Storage temperature
Ambient temperature (operational)
Humidity
Degree of protection
12 A (see derating curve)
< 0.1 Ω
Mode 1
C1
acc. to IEC 61643-21
0.5 kA
1 kA
– / 1 kA / –
– / 4.5 kA / –
-40 °C...+80 °C
-40 °C...+70 °C
5...96 % RH
IP20
Flammability class
Connection data
Connection
V0
Tightening torque
Conductor cross section, flexible, ferrule (DIN 46228-1), max.
Conductor cross section, flexible, ferrule (DIN 46228-1), min.
Conductor cross section, solid, max.
Conductor cross section, solid, min.
Conductor cross section, stranded, Rated connection, max.
Conductor cross section, stranded, Rated connection, min.
Stripping length
0.5 Nm
4 mm²
0.5 mm²
6 mm²
0.5 mm²
4 mm²
0.5 mm²
10 mm
Mounting rail
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
TS35
Dimensions
Length x width x height
Torx® screw T15 / slot 0.8 x 4
88.5 x 6.2 x 81 mm
Accessories: Screwdriver: Torx® 9009170000, slotted 9008340000; test plug: PS 2.3 0180400000; EMC SET: 1067470000;
marker: WS 10/6 1818400000, DEK 6 0468560000, SNAPMARK 1805880000; end plate: 1063110000
59
VARITECTOR SSC
VSSC MOV and TR LD MOV
48 V UC and 60 V UC
Technical Data
MOV 48VUC
Rated voltage AC/DC
48 V AC / 60 V DC
60 V AC / 85 V DC
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Residual voltage UP
60 V AC / 85 V DC
≤ 400 kHz
≤ 200 V
75 V AC / 106 V DC
≤ 600 kHz
≤ 250 V
- / 213 V / -
- / 269 V / -
200 V
250 V
VSSC6 MOV 48VUC
VSSC6 MOV 60VUC
1064570000
1064600000
10 pieces
10 pieces
Technical Data
TR LD MOV 48VUC
TR LD MOV 60VUC
Rated voltage AC/DC
48 V AC / 60 V DC
60 V AC / 85 V DC
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Residual voltage UP
60 V AC / 85 V DC
≤ 400 kHz
≤ 200 V
- / 213 V / -
75 V AC / 106 V DC
≤ 600 kHz
≤ 250 V
- /269 V / -
200 V
250 V
wire-wire / wire-PE / GND-PE
Protection level on output side sym.
Input 1 kV/µs, typ.
Ordering data
Type
Part No.
Qty.
MOV 60VUC
Note
wire-wire / wire-PE / GND-PE
Protection level on output side sym.
Input 1 kV/µs, typ.
Disconnect lever
Yes
Testing option
Status indicator
Ordering data
Type
Part No.
Qty.
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
Functional screw with test plug
receptacle connection 1, 2, 4, 5
VSSC6 TR LD MOV 48VUC
VSSC6 TR LD MOV 60VUC
1064820000
1064830000
10 pieces
10 pieces
Note
60
VARITECTOR SSC
VSSC 6AN MOV and TR LD MOV
120 V UC, 150 V UC and 240 V UC – with
varistor, with and without disconnect lever (TR)
and indicator (LD)
Surge protection with screw connection for
instrumentation, control and automation technology
• Surge protection in terminal block format
• Modular width of just 6.2 mm
• Space saving design: 2 analog signals
• Torx® slotted screw connection
• Can be used to comply with the IEC 62305 installation
standard and the IEC 61643-1/-22 applications standards
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
General data
Nominal current
Volume resistivity
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Standards
Surge strength C1
Surge strength C2
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Storage temperature
Ambient temperature (operational)
Humidity
Degree of protection
12 A (see derating curve)
< 0.1 Ω
Mode 1
C1. C2
IEC 61643-21 (Pending)
0.5 kA
1.5 kA
– / 500 A / –
– / 1.5 kA / –
-40 °C...+80 °C
-40 °C...+70 °C
5...96 % RH
IP20
Flammability class
Connection data
Connection
V0
Tightening torque
Conductor cross section, flexible, ferrule (DIN 46228-1), max.
Conductor cross section, flexible, ferrule (DIN 46228-1), min.
Conductor cross section, solid, max.
Conductor cross section, solid, min.
Conductor cross section, stranded, Rated connection, max.
Conductor cross section, stranded, Rated connection, min.
Stripping length
0.5 Nm
4 mm²
0.5 mm²
6 mm²
0.5 mm²
4 mm²
0.5 mm²
10 mm
Mounting rail
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
TS35
Dimensions
Length x width x height
Torx® screw T15 / slot 0.8 x 4
88.5 x 12.4 x 81 mm
Accessories: Screwdriver: Torx® 9009170000, slotted 9008340000; test plug: PS 2.3 0180400000; EMC SET: 1067470000;
marker: WS 10/6 1818400000, DEK 6 0468560000, SNAPMARK 1805880000; end plate: 1063110000
61
VARITECTOR SSC
VSSC MOV and TR LD MOV
120 V UC, 150 V UC and 240 V UC
Technical Data
MOV 120VUC
MOV 150VUC
MOV 240VUC
Rated voltage AC/DC
120 V AC / 170 V DC
150 V AC / 212 V DC
240 V AC / 339 V DC
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Residual voltage UP
150 V AC / 212 V DC
≤ 1 MHz
≤ 500 V
188 V AC / 266 V DC
≤ 1 MHz
≤ 600 V
288 V AC / 407 V DC
≤ 1.7 MHz
≤ 900 V
- / 543 V / -
- / 641 V / -
- / 1022 V / -
500 V
600 V
1000 V
VSSC6 MOV 120VUC
VSSC6 MOV 150VUC
VSSC6 MOV 240VUC
1064610000
1064620000
1064630000
10 pieces
10 pieces
10 pieces
Technical Data
TR LD MOV 120VUC
TR LD MOV 150VUC
TR LD MOV 240VUC
Rated voltage AC/DC
120 V AC / 170 V DC
150 V AC / 212 V DC
240 V AC / 339 V DC
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Residual voltage UP
150 V AC / 212 V DC
≤ 1 MHz
≤ 500 V
- / 543 V / -
188 V AC / 266 V DC
≤ 1 MHz
≤ 600 V
- / 641 V / -
288 V AC / 407 V DC
≤ 1.7 MHz
≤ 900 V
- / 1022 V / -
500 V
600 V
1000 V
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
Yes
Yes
Yes
VSSC6 TR LD MOV 120VUC
VSSC6 TR LD MOV 150VUC
VSSC6 TR LD MOV 240VUC
wire-wire / wire-PE / GND-PE
Protection level on output side sym.
Input 1 kV/µs, typ.
Ordering data
Type
Part No.
Qty.
Note
wire-wire / wire-PE / GND-PE
Protection level on output side sym.
Input 1 kV/µs, typ.
Disconnect lever
Testing option
Status indicator
Ordering data
Type
Part No.
Qty.
1064840000
10 pieces
1064850000
10 pieces
1064860000
10 pieces
Note
62
VARITECTOR SSC
VSSC 6AN TAZ and TR TAZ – with suppressor
diode gap, with and without disconnect
lever (TR) and indication (LD)
Surge protection with screw connection for
instrumentation, control and automation technology
• Surge protection in terminal block format
• Modular width of just 6.2 mm
• Space saving design: 2 analog signals
• Torx® slotted screw connection
• Can be used to comply with the IEC 62305 installation
standard and the IEC 61643-1/-22 applications standards
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
General data
Nominal current
12 A (see derating curve)
Volume resistivity
Overstressed fault mode
Storage temperature
Ambient temperature (operational)
Humidity
Degree of protection
< 0.1 Ω
Mode 1
-40 °C...+80 °C
-40 °C...+70 °C
5...96 % RH
IP20
Flammability class
Connection data
Connection
V0
Tightening torque
Conductor cross section, flexible, ferrule (DIN 46228-1), max.
Conductor cross section, flexible, ferrule (DIN 46228-1), min.
Conductor cross section, solid, max.
Conductor cross section, solid, min.
Conductor cross section, stranded, Rated connection, max.
Conductor cross section, stranded, Rated connection, min.
Stripping length
0.5 Nm
4 mm²
0.5 mm²
6 mm²
0.5 mm²
4 mm²
0.5 mm²
10 mm
Mounting rail
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
TS35
Dimensions
Length x width x height
Torx® screw T15 / slot 0.8 x 4
88.5 x 6.2 x 81 mm
Accessories: Screwdriver: Torx® 9009170000, slotted 9008340000; test plug: PS 2.3 0180400000; EMC SET: 1067470000;
marker: WS 10/6 1818400000, DEK 6 0468560000, SNAPMARK 1805880000; end plate: 1063110000
63
VARITECTOR SSC
VSSC TAZ and TR LD TAZ
Technical Data
TAZ 12VDC
TAZ 24VUC
Rated voltage AC/DC
12 V DC
24 V UC / 34 V DC
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage UP
15 V DC
≤ 1 MHz
≤ 30 ms
30 V AC / 42 V DC
≤ 1 MHz
≤ 30 ms
≤ 22 V
- / 26 V / -
≤ 61 V
- / 62 V / -
Protection level on output side sym.
Input 1 kV/µs, typ.
30 V
70 V
Requirement category to IEC 61643-21
Surge strength C3
Rated discharge current IN (8/20 μs) wire-PE
Rated discharge current Imax (8/20 μs) wire-PE
C3
50 A
200 A
500 A
C3
15 A
100 A
200 A
Standards
Ordering data
Type
IEC 61643-21
IEC 61643-21
VSSC6 TAZ 12VDC
VSSC6 TAZ 24VUC
1064730000
1064740000
10 pieces
10 pieces
Technical Data
TR LD TAZ 12VDC
TR LD TAZ 24VUC
Rated voltage AC/DC
12 V DC
24 V UC / 34 V DC
15 V DC
≤ 1 MHz
≤ 30 ms
≤ 22 V
- / 26 V / -
30 V AC / 42 V DC
≤ 1 MHz
≤ 30 ms
≤ 61 V
- / 62 V / -
30 V
70 V
C3
50 A
200 A
500 A
IEC 61643-21
Yes
C3
15 A
100 A
200 A
IEC 61643-21
Yes
Functional screw with test plug
receptacle connection 1, 2, 4, 5
Functional screw with test plug
receptacle connection 1, 2, 4, 5
VSSC6 TR LD TAZ 12VDC
VSSC6 TR LD TAZ 24VUC
1064940000
1064950000
10 pieces
10 pieces
wire-wire / wire-PE / GND-PE
Part No.
Qty.
Note
Max. continuous voltage UC (AC) / (DC)
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage UP
wire-wire / wire-PE / GND-PE
Protection level on output side sym.
Input 1 kV/µs, typ.
Requirement category to IEC 61643-21
Surge strength C3
Rated discharge current IN (8/20 μs) wire-PE
Rated discharge current Imax (8/20 μs) wire-PE
Standards
Disconnect lever
Testing option
Ordering data
Type
Part No.
Qty.
Note
64
VARITECTOR SSC
VSSC 6AN RS485, RS485 DP and RS232 –
for interface signals
Two-stage surge protection with screw connection for
instrumentation, control and automation technology
•
•
•
•
•
Surge protection in terminal block format
Modular width of just 6.2 mm
Space saving design
Torx® slotted screw connection
Can be used to comply with the IEC 62305 installation
standard and the IEC 61643-1/-22 applications standards
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
General data
Nominal current
500 mA (see derating curve)
Volume resistivity
Overstressed fault mode
Requirement category to IEC 61643-21
Standards
Surge strength C2
Surge strength C3
Surge strength D1
1.8 Ω ±10 %
Mode 2
C2, C3, D1
IEC 61643-21
2.5 kA
10 A
0.5 kA
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp (10/350 μs) wire-wire / wire-PE / GND-PE
Storage temperature
Ambient temperature (operational)
Humidity
Degree of protection
2.5 kA / 2.5 kA / –
10 kA / 10 kA / –
1 kA
-40 °C...+80 °C
-40 °C...+70 °C
5...96 % RH
IP20
Flammability class
Connection data
Connection
V0
Tightening torque
Conductor cross section, flexible, ferrule (DIN 46228-1), max.
Conductor cross section, flexible, ferrule (DIN 46228-1), min.
Conductor cross section, solid, max.
Conductor cross section, solid, min.
Conductor cross section, stranded, Rated connection, max.
Conductor cross section, stranded, Rated connection, min.
0.5 Nm
4 mm²
0.5 mm²
6 mm²
0.5 mm²
4 mm²
0.5 mm²
Stripping length
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
10 mm
Dimensions
Length x width x height
Torx® screw T15 / slot 0.8 x 4
88.5 x 6.2 x 81 mm
Accessories: Screwdriver: Torx® 9009170000, slotted 9008340000; test plug: PS 2.3 0180400000; EMC SET: 1067470000;
marker: WS 10/6 1818400000, DEK 6 0468560000, SNAPMARK 1805880000; end plate: 1063110000
65
VARITECTOR SSC
VSSC 6AN RS485, RS485 DP and RS232
Technical Data
RS485
RS485 DP
RS232
Rated voltage AC/DC
12 V DC
12 V DC
12 V DC
Max. continuous voltage UC (DC)
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage UP
15 V DC
≤ 2 MHz
≤ 20 ms
15 V DC
≤ 2 MHz
≤ 20 ms
15 V DC
≤ 2 MHz
≤ 20 ms
≤ 94 V
35 V / 35 V / -
≤ 94 V
35 V / 35 V / -
≤ 80 V
70 V / 35 V / -
Protection level on output side sym.
Input 1 kV/µs, typ.
30 V
30 V
60 V
Protection level on output side unsym.,
Input 1 kV/µs, typ.
94 V
VSSC6 RS485
VSSC6 RS485 DP
VSSC6 RS232
1064980000
1065010000
1064990000
10 pieces
10 pieces
10 pieces
wire-wire / wire-PE / GND-PE
Ordering data
Type
Part No.
Qty.
Note
66
VARITECTOR SSC
VSSC 6AN RTD – for temperature signals
Two-stage surge protection with screw connection for
instrumentation, control and automation technology
•
•
•
•
•
Surge protection in terminal block format
Modular width of just 6.2 mm
Space saving design
Torx® slotted screw connection
Can be used to comply with the IEC 62305 installation
standard and the IEC 61643-1/-22 applications standards
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
General data
Nominal current
300 mA
Dielectric strength at FG against PE
Volume resistivity
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Standards
Surge strength C2
Surge strength C3
–
1.8 Ω ±10 %
Mode 2
C2, C3, D1
IEC 61643-21
2.5 kA 8/20 µs, 5 kV 1,2/50 µs
10 A 10/1000 µs
Surge strength D1
Rated discharge current IN (8/20 μs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 μs) wire-wire / wire-PE / GND-PE
Lightning test current, Iimp (10/350 μs) wire-wire / wire-PE / GND-PE
Storage temperature
Ambient temperature (operational)
Humidity
Degree of protection
0.5 kA 10/350 µs
2.5 kA / 2.5 kA / –
10 kA / 10 kA / –
1 kA
-40 °C...+80 °C
-40 °C...+70 °C
5...96 % RH
IP20
Flammability class
Connection data
Connection
V0
Tightening torque
Conductor cross section, flexible, ferrule (DIN 46228-1), max.
Conductor cross section, flexible, ferrule (DIN 46228-1), min.
Conductor cross section, solid, max.
Conductor cross section, solid, min.
Conductor cross section, stranded, Rated connection, max.
Conductor cross section, stranded, Rated connection, min.
Stripping length
0.5 Nm
4 mm²
0.5 mm²
6 mm²
0.5 mm²
4 mm²
0.5 mm²
10 mm
Mounting rail
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
TS35
Dimensions
Length x width x height
Torx® screw T15 / slot 0.8 x 4
88.5 x 6.2 x 81 mm
Accessories: Screwdriver: Torx® 9009170000, slotted 9008340000; test plug: PS 2.3 0180400000; EMC SET: 1067470000;
marker: WS 10/6 1818400000, DEK 6 0468560000, SNAPMARK 1805880000; end plate: 1063110000
67
VARITECTOR SSC
VSSC 6AN RTD
Technical Data
RTD
Rated voltage AC/DC
1 V DC
Max. continuous voltage UC (DC)
Signal transmission properties (-3 dB)
Pulse reset capacity
Residual voltage UP
5 V DC
≤ 1 MHz
≤ 20 ms
≤ 126 V
15 V / 15 V / -
wire-wire / wire-PE / GND-PE
Protection level on output side sym.
Input 1 kV/µs, typ.
10 V
Protection level on output side unsym.,
Input 1 kV/µs, typ.
10 V
Ordering data
Type
VSSC6 RTD
Part No.
1139710000
Qty.
10 pieces
Note
68
VARITECTOR SSC
VARITECTOR SSC CL and CL FG
Two-stage surge protection with screw connection for
instrumentation, control and automation technology
• Surge protection in terminal-block format
• Modular width of just 6.2 mm
• Space-saving design: 1 analog signal
• Torx slotted screw connection
• Version with non-earthed PE connection for avoiding
potential differences
• U
sable in accordance with installations standard IEC 62305
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
General data
Nominal current IN at 25 °C
Rated discharge current IN (8 / 20 µs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8 / 20 µs) wire-wire / wire-PE / GND-PE
Response time wire-wire / wire-PE / GND-PE
Volume resistivity per path
Discharge current Itotal
Rated discharge current Iimp (10 / 350 µs)
Surge strength
Max. continuous voltage
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Rel. humidity
Degree of protection
Ambient temperature (operational)
Storage temperature
Approvals
Clampable conductor
Connection
UL, CSA pending
Stripping length
Tightening torque range
Solid / stranded
7 mm
0.5 … 0.8 Nm
0.5 … 6 mm² / 0.5 … 4 mm²
Flexible / flexible with ferrule
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
0.5 … 2.5 mm²
Dimensions
Length x width x height Note: end plate AP VSSC4: 1063120000
Applications
69
500 mA
2.5 kA / 2.5 kA / 5 kA / 5 kA / ≤ 1 ns / ≤ 100 ns / 1.8 Ω ± 10%
10 kA
1 kA
4 kV / 2 kA, 10 repetitions
1 A / 1 s, 5 repetitions
Mode 2
C1; C2; C3; D1
5%…96% RH
IP20
-40 °C…+70 °C
-40 °C…+80 °C
Torx screw (T15) / slot (0.8 x 4.0)
76 x 6.2 x 58.5 mm
VARITECTOR SSC
VARITECTOR SSC CL and CL FG
Ordering Data
VSSC4 CL 12 V DC 0.5 A
VSSC4 CL FG 12 V DC 0.5 A
VSSC4 CL 24 V UC 0.5 A
Rated voltage UN
12 V DC
12 V DC
24 V AC / 34 V DC
Max. continuous voltage UC
Voltage GND-PE
Capacitance
Gas discharge tube
Supressor diode
Limiting frequency (-3 dB) at load resistance
15 V DC
4 nF
15 V DC
> 500 V
4 nF
30 V AC / 42 V DC
650 pF
90 V
16 V
250 kHz
90 V
16 V
250 kHz
90 V
43V
1.5 MHz
35 V / 600 V / 30 V / 600 V / -
35 V / 1500 V / 30 V / 1500 V / -
90 V / 600 V / 70 V / 600 V / -
VSSC4 CL 12VDC 0.5A
VSSC4 CL FG 12VDC 0.5A
VSSC4 CL 24VUC 0.5A
1063720000
1063760000
1063730000
10 piece
10 piece
10 piece
VSSC4 CL FG 24 V UC 0.5 A
VSSC4 CL 48 V UC 0.5 A
VSSC4 CL FG 48 V UC 0.5 A
Rated voltage UN
24 V AC / 34 V DC
48 V AC / 68 V DC
48 V AC / 68 V DC
Max. continuous voltage UC
Voltage GND-PE
Capacitance
Gas discharge tube
Supressor diode
Limiting frequency (-3 dB) at load resistance
30 V AC / 42 V DC
> 500 V
650 pF
90 V
43V
1.5 MHz
60 V AC / 85 V DC
450 pF
150 V
91 V
2.2 MHz
60 V AC / 85 V DC
> 500 V
450 pF
150 V
91 V
2.2 MHz
90 V / 1500 V / 70 V / 1500 V / -
200 V / 600 V / 150 V / 600 V / -
200 V / 1500 V / 150 V / 1500 V / -
VSSC4 CL FG 24VUC 0.5A
VSSC4 CL 48VUC 0.5A
VSSC4 CL FG 48VUC 0.5A
1063770000
1063740000
1063780000
10 piece
10 piece
10 piece
VSSC4 CL 60 V UC 0.5 A
VSSC4 CL FG 60 V UC 0.5 A
Protection level at
IN wire-wire / wire-PE / GND-PE
1 kV / µs wire-wire / wire-PE / GND-PE
Ordering data
Type
Part No.
Qty.
Note
Ordering Data
Protection level at
IN wire-wire / wire-PE / GND-PE
1 kV / µs wire-wire / wire-PE / GND-PE
Ordering data
Type
Part No.
Qty.
Note
Ordering Data
Rated voltage UN
60 V AC / 85 V DC
60 V AC / 85 V DC
Max. continuous voltage UC
Voltage GND-PE
Capacitance
Gas discharge tube
Supressor diode
Limiting frequency (-3 dB) at load resistance
75 V AC / 106 V DC
350 pF
230 V
120 V
2.8 MHz
75 V AC / 106 V DC
> 500 V
350 pF
150 V
120 V
2.8 MHz
260 V / 600 V / 200 V / 600 V / -
260 V / 1500 V / 200 V / 1500 V / -
VSSC4 CL 60VUC 0.5A
VSSC4 CL FG 60VUC 0.5A
1063750000
1063790000
10 piece
10 piece
Protection level at
IN wire-wire / wire-PE / GND-PE
1 kV / µs wire-wire / wire-PE / GND-PE
Ordering data
Type
Part No.
Qty.
Note
70
VARITECTOR SSC
VARITECTOR SSC SL and SL FG
Two-stage surge protection with screw connection for
instrumentation, control and automation technology
• Surge protection in terminal-block format
• Modular width of just 6.2 mm
• Space-saving design: 1 binary signal
• Torx slotted screw connection
• Version with non-earthed PE connection for avoiding
potential differences
• U
sable in accordance with installations standard IEC 62305
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
Technical Data
General data
Nominal current IN at 25 °C
Rated discharge current IN (8 / 20 µs) wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8 / 20 µs) wire-wire / wire-PE / GND-PE
Response time wire-wire / wire-PE / GND-PE
Volume resistivity per path
Discharge current Itotal
Rated discharge current Iimp (10 / 350 µs)
Surge strength
Max. continuous voltage
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Rel. humidity
Degree of protection
Ambient temperature (operational)
Storage temperature
Approvals
Clampable conductor
Connection
UL, CSA pending
Stripping length
Tightening torque range
Solid / stranded
7 mm
0.5 … 0.8 Nm
0.5 … 6 mm² / 0.5 … 4 mm²
Flexible / flexible with ferrule
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
0.5 … 2.5 mm²
Dimensions
Length x width x height Note: end plate AP VSSC4: 1063120000
Applications
71
500 mA
- / 2.5 kA / - / 10 kA / - / ≤ 2 ns / ≤ 100 ns
1.8 Ω ± 10%
10 kA
1 kA
4 kV / 2 kA, 10 repetitions
1 A / 1 s, 5 repetitions
Mode 2
C1; C2; C3; D1
5%…96% RH
IP20
-40 °C…+70 °C
-40 °C…+80 °C
Torx screw (T15) / slot (0.8 x 4.0)
76 x 6.2 x 58.5 mm
VARITECTOR SSC
VARITECTOR SSC SL and SL FG
Ordering Data
VSSC4 SL 12 V DC 0.5 A
VSSC4 SL FG 12 V DC 0.5 A
VSSC4 SL 24 V UC 0.5 A
Rated voltage UN
12 V DC
12 V DC
24 V AC / 34 V DC
Max. continuous voltage UC
Voltage GND-PE
Capacitance
Gas discharge tube
Supressor diode
Limiting frequency (-3 dB) at load resistance
15 V DC
4 nF
15 V DC
> 500 V
4 nF
30 V AC / 42 V DC
650 pF
90 V
16 V
250 KHz
90 V
16 V
250 KHz
90 V
43 V
1.5 MHz
- / 35 V / - / 30 V / -
- / 35 V / 1400 V
- / 30 V / 1400 V
- / 90 V / - / 70 V / -
VSSC4 SL 12VDC 0.5A
VSSC4 SL FG 12VDC 0.5A
VSSC4 SL 24VUC 0.5A
1063830000
1063880000
1063840000
10 piece
10 piece
10 piece
VSSC4 SL FG 24 V UC 0.5 A
VSSC4 SL 48 V UC 0.5 A
VSSC4 SL FG 48 V UC 0.5 A
Rated voltage UN
24 V AC / 34 V DC
48 V AC / 68 V DC
48 V AC / 68 V DC
Max. continuous voltage UC
Voltage GND-PE
Capacitance
Gas discharge tube
Supressor diode
Limiting frequency (-3 dB) at load resistance
30 V AC / 42 V DC
> 500 V
650 pF
90 V
43 V
1.5 MHz
60 V AC / 85 V DC
450 pF
150 V
91 V
2.2 MHz
60 V AC / 85 V DC
> 500 V
450 pF
150 V
91 V
2.2 MHz
- / 90 V / 1400 V
- / 70 V / 1400 V
- / 200 V / - / 150 V / -
- / 200 V / 1200 V
- / 150 V / 1200 V
VSSC4 SL FG 24VUC 0.5A
VSSC4 SL 48VUC 0.5A
VSSC4 SL FG 48VUC 0.5A
1063890000
1063860000
1063910000
10 piece
10 piece
10 piece
VSSC4 SL 60 V UC 0.5 A
VSSC4 SL FG 60 V UC 0.5 A
Protection level at
IN wire-wire / wire-PE / GND-PE
1 kV / µs wire-wire / wire-PE / GND-PE
Ordering data
Type
Part No.
Qty.
Note
Ordering Data
Protection level at
IN wire-wire / wire-PE / GND-PE
1 kV / µs wire-wire / wire-PE / GND-PE
Ordering data
Type
Part No.
Qty.
Note
Ordering Data
Rated voltage UN
60 V AC / 85 V DC
60 V AC / 85 V DC
Max. continuous voltage UC
Voltage GND-PE
Capacitance
Gas discharge tube
Supressor diode
Limiting frequency (-3 dB) at load resistance
75 V AC / 106 V DC
350 pF
230 V
120 V
2.8 MHz
75 V AC / 106 V DC
> 500 V
350 pF
150 V
120 V
2.8 MHz
- / 260 V / - / 200 V / -
- / 260 V / 1200 V
- / 200 V / 1200 V
VSSC4 SL 60VUC 0.5A
VSSC4 SL FG 60VUC 0.5A
1063870000
1063920000
10 piece
10 piece
Protection level at
IN wire-wire / wire-PE / GND-PE
1 kV / µs wire-wire / wire-PE / GND-PE
Ordering data
Type
Part No.
Qty.
Note
72
VARITECTOR SSC
VSSC4 MOV – Components
Two-stage surge protection with screw connection for
instrumentation, control and automation technology
• Modular width of just 6.2 mm or 12.4 mm
• Components built-into terminal block, such as GDT,
MOV, TAZ
• Torx slotted screw connection
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
• Accessories: end plate and extension frame
Technical Data
General data
Nominal current IN at 25 °C
Response time wire-wire / wire-PE / GND-PE
Volume resistivity per path
Surge strength
Max. continuous voltage
Combined pulse UOC
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Rel. humidity
Degree of protection
Ambient temperature (operational)
Storage temperature
73
- / 25 ns / < 0.1 Ω
1 kV / 100 A (10 / 1000 µs), 30 repetitions
0.25 A / 1 s, 5 repetitions
5 kV
Mode 1
C1; C2; C3
5%…96% RH
IP20
-40 °C…+70 °C
-40 °C…+80 °C
Approvals
Clampable conductor
Connection
UL, CSA pending
Stripping length
Tightening torque range
Solid / stranded
7 mm
0.5 … 0.8 Nm
0.5 … 6 mm² / 0.5 … 4 mm²
Flexible / flexible with ferrule
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
0.5 … 2.5 mm²
Note: end plate AP VSSC4: 1063120000
Applications
20 A
Torx screw (T15) / slot (0.8 x 4.0)
VARITECTOR SSC
VSSC4 MOV – Components
Ordering Data
VSSC4 MOV 12 V DC
VSSC4 MOV 24 V UC
VSSC4 MOV 48 V UC
Rated voltage UN
12 V DC
24 V AC / 34 V DC
48 V AC / 68 V DC
60 V AC / 85 V DC
Max. continuous voltage UC
Voltage GND-PE
Capacitance
Varistor
Limiting frequency (-3 dB) at load resistance
Rated discharge current IN (8/20 µs)
wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 µs)
15 V DC
12 nF
30 V AC / 42 V DC
5 nF
60 V AC / 85 V DC
1650 pF
75 V AC / 106 V DC
1370 pF
18 V
80 kHz
47 V
200 kHz
100 V
600 kHz
120 V
700 kHz
- / 500 A / -
- / 500 A / -
- / 2 kA / -
- / 2 kA / -
wire-wire / wire-PE / GND-PE
Discharge current Itotal
- / 1 kA / 1 kA
- / 1 kA / 1 kA
- / 4,5 kA / 4,5 kA
- / 4,5 kA / 4,5 kA
Protection level at
IN wire-wire / wire-PE / GND-PE
1 kV / µs wire-wire / wire-PE / GND-PE
- / 65 V / - / 50 V / -
- / 180 V / - / 150 V / -
- / 270 V / - / 200 V / -
- / 320 V / - / 250 V / -
76 x 6.2 x 58.5 mm
76 x 6.2 x 58.5 mm
76 x 6.2 x 58.5 mm
76 x 6.2 x 58.5 mm
VSSC4 MOV 12VDC
VSSC4 MOV 24VUC
VSSC4 MOV 48VUC
VSSC4 MOV 60VUC
1063950000
1063960000
1063970000
1063980000
10 piece
10 piece
10 piece
10 piece
VSSC4 MOV 120 V UC
VSSC4 MOV 150 V UC
VSSC4 MOV 240 V UC
Rated voltage UN
120 V AC / 170 V DC
150 V AC / 212 V DC
120 V AC / 170 V DC
Max. continuous voltage UC
Voltage GND-PE
Capacitance
Varistor
Limiting frequency (-3 dB) at load resistance
Rated discharge current IN (8/20 µs)
wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 µs)
wire-wire / wire-PE / GND-PE
Discharge current Itotal
150 V AC / 212 V DC
2 nF
240 V
500 kHz
188 V AC / 266 V DC
1.5 nF
300 V
650 kHz
150 V AC / 212 V DC
2 nF
240 V
500 kHz
- / 7.5 kA / -
- / 7.5 kA / -
- / 7,5 kA / -
- / 15 kA / 15 kA
- / 15 kA / 15 kA
- / 15 kA / 15 kA
- / 720 V / - / 500 V / -
- / 900 V / - / 600 V / -
- / 720 V / - / 500 V / -
76 x 12.4 x 58.5 mm
76 x 12.4 x 58.5 mm
76 x 12.4 x 58.5 mm
VSSC4 MOV 120VUC
VSSC4 MOV 150VUC
VSSC4 MOV 240VUC
1063990000
1064010000
1064020000
10 piece
10 piece
10 piece
Dimensions
Length x width x height Ordering data
Type
Part No.
Qty.
VSSC4 MOV 60 V UC
Note
Ordering Data
Protection level at
IN wire-wire / wire-PE / GND-PE
1 kV / µs wire-wire / wire-PE / GND-PE
Dimensions
Length x width x height Ordering data
Type
Part No.
Qty.
Note
74
VARITECTOR SSC
VSSC4 TAZ – Components
Single stage surge protection with screw connection for
instrumentation, control and automation technology
• Modular width of just 6.2 mm or 12.4 mm
• Components built-into terminal block, such as GDT,
MOV, TAZ
• Torx slotted screw connection
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
• Accessories: end plate and extension frame
VSSC4 TAZ
Technical Data
General data
Nominal current IN at 25 °C
20 A
Volume resistivity per path
Overstressed fault mode
Rel. humidity
Degree of protection
Ambient temperature (operational)
Storage temperature
< 0.1 Ω
Mode 2
5%…96% RH
IP20
-40 °C…+70 °C
-40 °C…+80 °C
Approvals
Clampable conductor
Connection
UL, CSA
Stripping length
Tightening torque range
Solid / stranded
7 mm
0.5 … 0.8 Nm
0.5 … 6 mm² / 0.5 … 4 mm²
Flexible / flexible with ferrule
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
0.5 … 2.5 mm²
Note: end plate AP VSSC4: 1063120000
Applications
75
Torx screw (T15) / slot (0.8 x 4.0)
VARITECTOR SSC
VSSC4 TAZ – Components
Ordering Data
VSSC4 TAZ 24 V UC
VSSC4 TAZ 48 V UC
24 V AC / 34 V DC
48 V AC / 75 V DC
30 V AC / 42 V DC
0.1 A / 1 s, 5 repetitions
10 A (10 / 1000 µs), 300 repetitions
60 V AC / 85 V DC
0.1 A / 1 s, 5 repetitions
5 A (10 / 1000 µs), 300 repetitions
650 pF
C1; C2; C3
450 pF
C1; C2; C3
51 V
1.5 MHz
100 V
2.2 MHz
- / 100 A / -
- / 50 A / -
- / 200 A / 200 A
- / 100 A / 100 A
Protection level at
IN wire-wire / wire-PE / GND-PE
1 kV / µs wire-wire / wire-PE / GND-PE
- / 90 V / - / 70 V / -
- / 200 V / - / 150 V / -
Response time wire-wire / wire-PE / GND-PE
- / 2 ns / -
- / 2 ns / -
Rated discharge current Iimp (10/350 µs)
Dimensions
Length x width x height Ordering data
Type
76 x 6.2 x 58.5 mm
76 x 6.2 x 58.5 mm
VSSC4 TAZ 24VUC
VSSC4 TAZ 48VUC
1064080000
1064090000
10 piece
10 piece
Rated voltage UN
Max. continuous voltage UC
Alternating-current strength
Surge strength
Capacitance
Requirement category acc. to IEC 61643-21
Gas discharge tube
Supressordiode
Limiting frequency (-3 dB) at load resistance
Rated discharge current IN (8/20 µs)
wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 µs)
wire-wire / wire-PE / GND-PE
Discharge current Itotal
Part No.
Qty.
Note
76
VARITECTOR SSC
VSSC4 RC – Components
Two-stage surge protection with screw connection for
instrumentation, control and automation technology
• Modular width of 12.4 mm
• Torx slotted screw connection
• Integrated PE contact in base element, safely discharges
up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to PE
• Accessories: end plate and extension frame
Technical Data
General data
Nominal current IN at 25 °C
20 A
Response time wire-wire / wire-PE / GND-PE
Volume resistivity per path
Surge strength
Max. continuous voltage
Overstressed fault mode
Requirement category acc. to IEC 61643-21
Capacitance
Limiting frequency (-3 dB) at load resistance
Rel. humidity
Degree of protection
Ambient temperature (operational)
Storage temperature
- / 25 ns / < 0.1 Ω
1 kV / 100A (10 / 1000 µs), 30 repetitions
0.25 A / 1 s, 5 repetitions
Mode 1
C1
220 nF
4 kHz
5%…96% RH
IP20
-40 °C…+70 °C
-40 °C…+80 °C
Approvals
Clampable conductor
Connection
UL, CSA
Stripping length
Tightening torque range
Solid / stranded
7 mm
0.5 … 0.8 Nm
0.5 … 6 mm² / 0.5 … 4 mm²
Flexible / flexible with ferrule
Approvals
UL Listed (USL). Assessed to UL497B. File ref. E 311081
0.5 … 2.5 mm²
Dimensions
Length x width x height Note: end plate AP VSSC4: 1063120000
Applications
77
Torx screw (T15) / slot (0.8 x 4.0)
76 x 12.4 x 58.5 mm
VARITECTOR SSC
VSSC4 RC – Components
Ordering Data
VSSC4 RC 24 V UC
Rated voltage UN
Max. continuous voltage UC
Voltage GND-PE
Alternating-current strength
Varistor
Surge strength C1
Protection level Up
Rated discharge current IN (8/20 µs)
wire-wire / wire-PE / GND-PE
Rated discharge current Imax (8/20 µs)
wire-wire / wire-PE / GND-PE
VSSC4 RC 240 V UC
24 V AC
240 V AC
30 V AC / 42 V DC
0.25 A / 1 s, 30 repetitions
275 V AC / 388 V DC
0.1 A / 1 s, 5 repetitions
43 V
0.25 kA / 8/20 μs
0.5 kV / 1.2/50 μs
< 500 V
430 V
0.25 kA / 8/20 μs
0.5 kV / 1.2/50 μs
< 500 V
- / 500 A / -
- / 1 kA / -
- / 1 kA / -
- / 2.5 kA / -
Discharge current Itotal
IN wire-wire / wire-PE / GND-PE
1 kA
- / 150 V / -
2.5 kA
- / 1500 V / -
Protection level at
1 kV / µs wire-wire / wire-PE / GND-PE
- / 120 V / -
- / 500 V / -
VSSC4 RC 24VUC
VSSC4 RC 240VUC
1064120000
1064130000
5 piece
5 piece
Ordering data
Type
Part No.
Qty.
Note
Subject to technical changes • 03/12 - LIT1119E
78