Switch-mode power supplies connectPower PRO-M connectPower PRO-M A Technical data L (+) AC N (–) + DC PE – Two-Phase operation also possible L1 (+) AC L2 (–) L3 + DC PE – General technical data Current limiting > 120 % IN Ambient temp. operating / storage temperature Max. perm. air humidity (operation) Degree of protection Class of protection Overvoltage category Pollution degree Insulation voltage MTBF –25 °C … +70 °C / –40 °C … +85 °C 5 %…95 % RH IP20 I, with PE connection II 2 3 kV I/O / 2 kV I/earth / 0.5 kV O/earth > 500,000 h acc. to IEC 1709 (SN29500) Protection against reverse voltages from the load Parallel connection option Housing version Indication 30…35 V DC yes, without diode module metal, corrosion resistant operation, green LED Mounting position, installation notice horizontal on mounting rail TS35, 50 mm spacing top and bottom for free air circulation, can be mounted side by side with no space in between Permissible maximum continuous current [A] EMC / shock / vibration Noise emission acc. to EN55022 Max. limiting average on state current [A] Type\Temp. 1ph 24V / 3A Class B Noise immunity tests acc. to EN61000-4-2 (ESD), EN61000-4-3 und EN61000-4-8 (Fields), EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted), EN61000-4-11 (Dips) 45°C 3.6 50°C 3.4 55°C 3.2 60°C 3 65°C 2.6 70°C 2.3 1ph 24V / 5A 1ph 24V / 7.5A 1ph 24V / 10A 1ph 24V / 20A 1ph 24V / 40A 3ph 24V / 5A 3ph 24V / 10A 3ph 24V / 20A 6 9 12 24 48 6 12 24 5.7 8.5 11.3 22.7 45.3 5.7 11.3 22.7 5.3 8 10.7 21.3 42.7 5.3 10.7 21.3 5 7.5 10 20 40 5 10 20 4.4 6.6 8.8 17.5 35 4.4 8.8 17.5 3.8 5.6 7.5 15 30 3.8 7.5 15 Limiting of mains voltage harmonic currents Acc. to EN 61000-3-2 Resistance against vibration and shock Electrical safety (applied standards) Electrical equipment of machines Acc. to EN50178, shock: 5g in all directions Safety transformers for switched-mode power units Machinery with electronic equipment Safety extra-low voltage Protective separation / protection against electrical shock Acc. to EN61558-2-17 Acc. to EN50178 / VDE0160 SELV acc. to EN60950, PELV acc. to EN60204 VDE0100-410 / acc. to DIN57100-410 3ph 24V / 40A 48 45.3 42.7 40 35 30 Protection against dangerous shock currents Acc. to VDE0106-101 Acc. to EN60204 Project-planning data Type 24 V / 3 A Rated input voltage Mains voltage range Mains input current Rec. fuse [char..] Efficiency @ 230 V AC, @ 3x400 V AC Rated power loss [W] Installation width mm 24 V / 5 A 1.3...0.6 A 2 A / D I / II 6 A, [B] 2...4 A, [C] 90 % 8W 2.1...0.9 A 4 A / D I / II 6 A, [B] 3...5 A, [C] 90 % 13 W 33 40 24 V / 7.5 A 24 V / 10 A 1 - phase 100...240 V AC 85...264 V AC 2.1...0.9 A 2.8...1.2 A 6 A / D I / II 6 A / D I / II 10 A, [B] 10 A, [B] 5...10 A, [C] 5...10 A, [C] 91 % 90 % 18 W 27 W 50 Input terminals mm2 Conductor, flexible min/max mm2 Conductor, AWG/kcmil min/max 5.6...2.4 A 11.1...4.7 A 10 A / D I / II 16 A / D I / II 20 A, [B] 25 A, [B] 10...12 A, [C] 14...16 A, [C] 90 % 91 % 53 W 95 W 121 180 24 V / 5 A 0.3...0.28 A 2 A / D I / II 1...2 A, [C] 90 % 13 W 24 V / 10 A 24 V / 20 A 3 - phase 3 x 400...500 V AC 3 x 320...575 V AC 0.55...0.5 A 1.0...0.9 A 2 A / D I / II 2 A / D I / II 2...3 A, [C] 3...5 A, [C] 90 % 90 % 27 W 53 W 40 60 24 V / 40 A 2.5...2.0 A 4 A / D I / II 10 A, [B] 6...8 A, [C] 91 % 95 W 121 180 0.5...6 0.5...2.5 0.5...6 0.5...2.5 0.08...4 0.5...2.5 0.5...6 0.5...2.5 0.5...6 0.5...2.5 26 / 12 26 / 10 28 / 12 26 / 12 26 / 12 Output terminals Screw connection 2/2 Number plus/minus Conductor, solid min/max mm2 Conductor, flexible min/max mm2 A.4 24 V / 40 A Screw connection Conductor, solid min/max Conductor, AWG/kcmil min/max 60 24 V / 20 A 2/3 0.5...6 0.5...2.5 0.5...6 0.5...2.5 0.5...16 2.5...10 0.5...6 0.5...2.5 0.5...6 0.5...2.5 0.5...16 2.5...10 26 / 12 26 / 10 22 / 6 26 / 12 26 / 10 22 / 6 connectPower PRO-M CP M SNT 70 W 24 V 3 A CP M SNT 120 W 24 V 5 A Switch-mode power supplies connectPower PRO-M A L L (+) N (–) H AC PE + N (–) DC – With DC connection, note polarity W L (+) AC PE + DC – With DC connection, note polarity Technical data Input rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / making current Recommended back-up fuse*) Output rated output voltage Output voltage residual ripple, breaking spikes Rated (nominal) output current @ UNom continous output current @ 24 V DC Powerboost @ 24 V DC, 60 °C General data Degree of efficiency Power factor (approx.) AC failure bridging time @ INom Parallel connection option Length x width x height Weight Approvals Connection data Conductor connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max mm² mm² Note 100...240 V AC (wide-range input) 85…264 V AC (Derating @ 100 V AC: 2.5 % / V) 47...63 Hz 80…370 V DC (Derating @ 120 V DC: 1 % / V) 0.6 A @ 230 V AC / 1.1 A @ 115 V AC 0.25 A @ 370 V DC / 0.7 A @ 120 V DC Yes / max. 40 A 2 A / DI, safety fuse 6 A, Char. B, circuit breaker 2...4 A, Char. C, circuit breaker 100...240 V AC (wide-range input) 85…264 V AC (Derating @ 100 V AC: 2.5 % / V*) 47...63 Hz 80…370 V DC (Derating @ 120 V DC: 1 % / V) 1.1 A @ 230 V AC / 2.0 A @ 115 V AC 0.4 A @ 370 V DC / 1.2 A @ 120 V DC Yes / max. 40 A 4 A / DI, safety fuse 6 A, Char. B, circuit breaker 3...5 A, Char. C, circuit breaker 24 V DC ± 1 % 22.5...29.5 V DC (adjustable via potentiometer on front) < 50 mVpp @ 24 V DC, IN 3 A @ 60 °C 3.6 A @ 45 °C, 3.2 A @ 55 °C, 2.3 A @ 70 °C 3.6 A for 1 min, ED = 5 % 24 V DC ± 1 % 22.5...29.5 V DC (adjustable via potentiometer on front) < 50 mVpp @ 24 V DC, IN 5 A @ 60 °C 6.0 A @ 45 °C, 5.3 A @ 55 °C, 3.8 A @ 70 °C 6 A for 1 min, ED = 5 % 90 % @ 230 V AC / 88 % @ 115 V AC > 0.6 @ 230 V AC / > 0,65 @ 115 V AC > 100 ms @ 230 V AC / > 20 ms @ 115 V AC yes, max. 5 125 / 33 / 130 mm 0.57 kg 90 % @ 230 V AC / 88 % @ 115 V AC > 0.5 @ 230 V AC / > 0.6 @ 115 V AC > 100 ms @ 230 V AC / > 20 ms @ 115 V AC yes, max. 5 125 / 40 / 130 mm 0.7 kg CE; cURus; cULus; C-Tick CE; cURus; cULus; C-Tick Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 12 Output Screw connection 4 (++ / --) 0.5 / 6 0.5 / 2.5 26 / 12 Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 12 Output Screw connection 5 (++ / ---) 0.5 / 6 0.5 / 2.5 26 / 12 *) Recommendation applies only for AC operation; the max. permissible operating voltage must be observed in all cases! *) Recommendation applies only for AC operation; the max. permissible operating voltage must be observed in all cases! Type Order No. Type 8951330000 CP M SNT 120W 24V 5A Ordering data Connection system Screw connection CP M SNT 70W 24V 3A Qty. 1 Qty. 1 Order No. 8951340000 Note Accessories A.5 Switch-mode power supplies connectPower PRO-M connectPower PRO-M CP M SNT 180 W 24 V 7.5 A CP M SNT 250 W 24 V 10 A A L L (+) N (–) H AC PE + N (–) DC – With DC connection, note polarity W L (+) AC PE + DC – With DC connection, note polarity Technical data Input rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / making current Recommended back-up fuse Output rated output voltage Output voltage residual ripple, breaking spikes Rated (nominal) output current @ UNom continous output current @ 24 V DC Powerboost @ 24 V DC, 60 °C General data Degree of efficiency Power factor (approx.) AC failure bridging time @ INom Parallel connection option Length x width x height Weight Approvals Connection data Conductor connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max mm² mm² Note 100...240 V AC (wide-range input) 85…264 V AC (Derating @ 100 V AC: 2.5 % / V) 47...63 Hz 80…370 V DC (Derating @ 120 V DC: 1 % / V) 0.9 A @ 230 V AC / 1.8 A @ 115 V AC 0.6 A @ 370 V DC / 1.7 A @ 120 V DC Yes / max. 40 A 6 A / DI, safety fuse 10 A, Char. B, circuit breaker 6 A, Char. C, circuit breaker 100...240 V AC (wide-range input) 85…264 V AC (Derating @ 100 V AC: 2.5 % / V) 47...63 Hz 80…370 V DC (Derating @ 120 V DC: 1 % / V) 1.2 A @ 230 V AC / 2.4 A @ 115 V AC 0.8 A @ 370 V DC / 2.3 A @ 120 V DC Yes / max. 12 A 4 A / DI,safety fuse 10 A, Char. B, circuit breaker 3...4 A, Char. C, circuit breaker 24 V DC ± 1 % 22.5...29.5 V DC (adjustable via potentiometer on front) < 50 mVpp @ 24 V DC, IN 7,5 A @ 60 °C 9.0 A @ 45 °C, 8.0 A @ 55 °C, 5.6 A @ 70 °C 9 A for 1 min, ED = 5 % 24 V DC ± 1 % 22.5...29.5 V DC (adjustable via potentiometer on front) < 50 mVpp @ 24 V DC, IN 10 A @ 60 °C 12 A @ 45 °C, 10.7 A @ 55 °C, 7.5 A @ 70 °C 12 A for 1 min, ED = 5 % 91 % @ 230 V AC / 88 % @ 115 V AC > 0.94 @ 230 V AC / > 0.99 @ 115 V AC > 20 ms @ 230 V AC / > 20 ms @ 115 V AC yes, max. 5 150 / 50 / 130 mm 1.05 kg 90 % @ 230 V AC / 87 % @ 115 V AC > 0.99 @ 230 V AC / > 0.97 @ 115 V AC > 20 ms @ 230 V AC / > 20 ms @ 115 V AC yes, max. 5 150 / 60 / 130 mm 1.2 kg CE; cURus; cULus; C-Tick CE; cURus; cULus; C-Tick Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 12 Output Screw connection 5 (++ / ---) 0.5 / 6 0.5 / 2.5 26 / 12 Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 12 Output Screw connection 5 (++ / ---) 0.5 / 6 0.5 / 2.5 26 / 12 *) Recommendation applies only for AC operation; the max. permissible operating voltage must be observed in all cases! *) Recommendation applies only for AC operation; the max. permissible operating voltage must be observed in all cases! Type Order No. Type 8951350000 CP M SNT 250W 24V 10A Ordering data Connection system Screw connection Note Accessories A.6 CP M SNT 180W 24V 7,5A Qty. 1 Qty. 1 Order No. 8951360000 connectPower PRO-M CP M SNT 500 W 24 V 20 A CP M SNT 1000 W 24 V 40 A Switch-mode power supplies connectPower PRO-M A L L (+) N (–) H AC PE + N (–) DC – With DC connection, note polarity W L (+) AC PE + DC – With DC connection, note polarity Technical data Input rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / making current Recommended back-up fuse Output rated output voltage Output voltage residual ripple, breaking spikes Rated (nominal) output current @ UNom continous output current @ 24 V DC Powerboost @ 24 V DC, 60 °C General data Degree of efficiency Power factor (approx.) AC failure bridging time @ INom Parallel connection option Length x width x height Weight Approvals Connection data Conductor connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max mm² mm² Note 100...240 V AC (wide-range input) 85…264 V AC (Derating @ 100 V AC: 2.5 % / V) 47...63 Hz 80…370 V DC (Derating @ 120 V DC: 1 % / V) 2.4 A @ 230 V AC / 4.8 A @ 115 V AC 1.5 A @ 370 V DC / 4.6 A @ 120 V DC Yes / max. 5 A 6 A / DI, safety fuse 16 A, Char. B, circuit breaker 6…8 A, Char. C, circuit breaker 100...240 V AC (wide-range input) 85…264 V AC (Derating @ 100 V AC: 2.5 % / V) 47...63 Hz 80…370 V DC (Derating @ 120 V DC: 1 % / V) 4.7 A @ 230 V AC / 9.6 A @ 115 V AC 2.9 A @ 370 V DC / 9.1 A @ 120 V DC Yes / max. 5 A 16 A / DI, safety fuse 20 A, Char. B, circuit breaker 16 A, Char. C, circuit breaker 24 V DC ± 1 % 22.5...29.5 V DC (adjustable via potentiometer on front) < 50 mVpp @ 24 V DC, IN 20 A @ 60 °C 24 A @ 45 °C, 22.7 A @ 55 °C, 15 A @ 70 °C 24 A for 1 min, ED = 5 % 24 V DC ± 1 % 22.5...29.5 V DC (adjustable via potentiometer on front) < 50 mVpp @ 24 V DC, IN 40 A @ 60 °C 48 A @ 45 °C, 42.7 A @ 55 °C, 30 A @ 70 °C 48 A for 1 min, ED = 5 % 90 % at 230 V AC / > 85 % at 115 V AC > 0.98 @ 230 V AC / > 0.99 @ 115 V AC > 20 ms @ 230 V AC / > 20 ms @ 115 V AC yes, max. 3 150 / 121 / 130 mm 2.2 kg 91 % @ 230 V AC / 88 % @ 115 V AC > 0.99 @ 230 V AC / > 0.99 @ 115 V AC > 20 ms @ 230 V AC / > 20 ms @ 115 V AC yes, max. 3 150 / 180 / 130 mm 3.9 kg CE; cURus; cULus; C-Tick CE; cURus; cULus; C-Tick Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 10 Output Screw connection 5 (++ / ---) 0.5 / 6 0.5 / 2.5 26 / 10 Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 10 Output Screw connection 5 (++ / ---) 0.5 / 16 2.5 / 10 22 / 6 *) Recommendation applies only for AC operation; the max. permissible operating voltage must be observed in all cases! *) Recommendation applies only for AC operation; the max. permissible operating voltage must be observed in all cases! Type Order No. Type 8951370000 CP M SNT 1000W 24V 40A Ordering data Connection system Screw connection CP M SNT 500W 24V 20A Qty. 1 Qty. 1 Order No. 8951380000 Note Accessories A.7 Switch-mode power supplies connectPower PRO-M connectPower PRO-M CP M SNT3 120 W 24 V 5 A CP M SNT3 250 W 24 V 10 A A L L1 (+) L2 (–) L3 AC PE H W + L1 (+) L2 (–) L3 DC – AC PE With DC connection, note polarity With DC connection, note polarity Two-phase operation also possible Two-phase operation also possible + DC – Technical data Input rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / making current Recommended back-up fuse Output rated output voltage Output voltage residual ripple, breaking spikes Rated (nominal) output current @ UNom continous output current @ 24 V DC Powerboost @ 24 V DC, 60 °C General data Degree of efficiency Power factor (approx.) AC failure bridging time @ INom Parallel connection option Length x width x height Weight Approvals Connection data Conductor connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max mm² mm² Note 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 47...63 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 0.28 A @ 3 x 500 V AC / 0.3 A @ 3 x 400 V AC 0.18 A @ 800 V DC / 0.3 A @ 450 V DC No / max. 50 A 2 A / DI, safety fuse 2...3 A, Char. C, circuit breaker 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 47...63 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 0.5 A @ 3 x 500 V AC / 0.55 A @ 3 x 400 V AC 0.35 A @ 800 V DC / 0.6 A @ 450 V DC No / max. 50 A 2 A / DI, safety fuse 2...3 A, Char. C, circuit breaker 24 V DC ± 1 % 22.5...29.5 V DC (adjustable via potentiometer on front) < 50 mVpp @ 24 V DC, IN 5 A @ 60 °C 6.0 A @ 45 °C, 5.3 A @ 55 °C, 3.8 A @ 70 °C 6 A for 1 min, ED = 5 % 24 V DC ± 1 % 22.5...29.5 V DC (adjustable via potentiometer on front) < 50 mVpp @ 24 V DC, IN 10 A @ 60 °C 12 A @ 45 °C, 10.7 A @ 55 °C, 7.5 A @ 70 °C 12 A for 1 min, ED = 5 % 89 % @ 3 x 500 V AC / 90 % @ 3 x 400 V AC > 0.55 @ 3 x 500 V AC / > 0.65 @ 3 x 400 V AC > 50 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC yes, max. 5 125 / 40 / 130 mm 0.7 kg 89 % @ 3 x 500 V AC / 90 % @ 3 x 400 V AC > 0.65 @ 3 x 500 V AC / > 0.75 @ 3 x 400 V AC > 40 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC yes, max. 5 150 / 60 / 130 mm 1.25 kg CE; cURus; cULus; C-Tick CE; cURus; cULus; C-Tick Input Screw connection 4 for L1/L2/L3/PE 0.08 / 4 0.5 / 2.5 28 / 12 Output Screw connection 5 (++ / ---) 0.5 / 6 0.5 / 2.5 26 / 12 Input Screw connection 4 for L1/L2/L3/PE 0.5 / 6 0.5 / 2.5 26 / 12 Output Screw connection 5 (++ / ---) 0.5 / 6 0.5 / 2.5 26 / 12 *) Recommendation applies only for AC operation; the max. permissible operating voltage must be observed in all cases! *) Recommendation applies only for AC operation; the max. permissible operating voltage must be observed in all cases! Type Order No. Type 8951390000 CP M SNT3 250W 24V 10A Ordering data Connection system Screw connection Note Accessories A.8 CP M SNT3 120W 24V 5A Qty. 1 Qty. 1 Order No. 8951400000 connectPower PRO-M CP M SNT3 500 W 24 V 20 A CP M SNT3 1000 W 24 V 40 A Switch-mode power supplies connectPower PRO-M A L L1 (+) L2 (–) L3 AC PE H W + L1 (+) L2 (–) L3 DC – AC PE With DC connection, note polarity With DC connection, note polarity Two-phase operation also possible Two-phase operation also possible + DC – Technical data Input rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / making current Recommended back-up fuse Output rated output voltage Output voltage residual ripple, breaking spikes Rated (nominal) output current @ UNom continous output current @ 24 V DC Powerboost @ 24 V DC, 60 °C General data Degree of efficiency Power factor (approx.) AC failure bridging time @ INom Parallel connection option Length x width x height Weight Approvals Connection data Conductor connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max mm² mm² Note 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 47...63 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 0.9 A @ 3 x 500 V AC / 0.95 A @ 3 x 400 V AC 0.7 A @ 800 V DC / 1.2 A @ 450 V DC No / max. 50 A 4 A / DI, safety fuse 3...5 A, Char. C, circuit breaker 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 47...63 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 2.0 A @ 3 x 500 V AC / 2.5 A @ 3 x 400 V AC 1.3 A @ 800 V DC / 2.4 A @ 450 V DC No / max. 60 A 6 A / DI, safety fuse 10 A, Char. B, circuit breaker 6...8 A, Char, C, circuit breaker 24 V DC ± 1 % 22.5...29.5 V DC (adjustable via potentiometer on front) < 50 mVpp @ 24 V DC, IN 20 A @ 60 °C 24 A @ 45 °C, 21.3 A @ 55 °C, 15 A @ 70 °C 24 A for 1 min, ED = 5 % 24 V DC ± 1 % 22.5...29.5 V DC (adjustable via potentiometer on front) < 50 mVpp @ 24 V DC, IN 40 A @ 60 °C 48 A @ 45 °C, 42.7 A @ 55 °C, 30 A @ 70 °C 48 A for 1 min, ED = 5 % 89 % @ 3 x 500 V AC / 90 % @ 3 x 400 V AC > 0.69 @ 3 x 500 V AC / > 0.82 @ 3 x 400 V AC > 25 ms at 3 x 500 V AC / > 20 ms at 3 x 400 V AC yes, max. 3 150 / 121 / 130 mm 2.2 kg 91 % @ 3 x 500 V AC / 91 % @ 3 x 400 V AC > 0.6 @ 3 x 500 V AC / > 0.6 @ 3 x 400 V AC > 25 ms at 3 x 500 V AC / > 20 ms at 3 x 400 V AC yes, max. 3 150 / 180 / 130 mm 4 kg CE; cURus; cULus; C-Tick CE; cURus; cULus; C-Tick Input Screw connection 4 for L1/L2/L3/PE 0.5 / 6 0.5 / 2 26 / 10 Output Screw connection 5 (++ / ---) 0.5 / 6 0.5 / 2.5 26 / 10 Input Screw connection 4 for L1/L2/L3/PE 0.5 / 6 0.5 / 2.5 26 / 10 Output Screw connection 5 (++ / ---) 0.5 / 16 0.5 / 10 22 / 6 *) Recommendation applies only for AC operation; the max. permissible operating voltage must be observed in all cases! *) Recommendation applies only for AC operation; the max. permissible operating voltage must be observed in all cases! Type Order No. Type 8951410000 CP M SNT3 1000W 24V 40A Ordering data Connection system Screw connection CP M SNT3 500W 24V 20A Qty. 1 Qty. 1 Order No. 8951420000 Note Accessories A.9 Switch-mode power supplies connectPower PRO-M PRO-M: Diode modules, capacity module and relay module A CP M DM20 L CP M DM40 1+ 3+ 4+ 1+ 11 12 14 12 14 12- H 34- 12- 21 3421 22 24 22 24 2+ W 3+ 4+ 11 2+ Technical data Input data Rated input voltage Input voltage range AC 24 V DC 24 V DC 18…30 V DC 18…30 V DC Input current Output data 2 x 10 A or 1 x 20 A 2 x 20 A or 1 x 40 A Rated output voltage Output voltage Rated (nominal) output current @ UN 24 V DC 24 V DC Input voltage - 0.7 V 20 A DC @ 60 °C Input voltage - 0.7 V 40 A @ 60 °C Continous output current @ 24 V DC 24 A @ 45 °C 22.5 A @ 55 °C 15 A @ 70 °C 48 A @ 45 °C 45 A @ 55 °C 30 A @ 70 °C Voltage monitoring Switching thresholds yes, in both inputs 21.6 V DC, relay is on for Power Good 20.4 V DC, relay is off for Power Fail yes, in both inputs 21.6 V DC, relay is on for Power Good 20.4 V DC, relay is off for Power Fail Potential free, floating contacts General data Max. 30 V DC / 1 A, CO contact Max. 30 V DC / 1 A, CO contact Degree of efficiency Length x width x height mm Weight Ambient temperature (operational) / Storage temperature Max. permitted humidity (operational) Degree of protection Class of protection Pollution degree Insulation voltage I/O to housing MTBF Mounting position, installation notice > 97 % @ 24 V input voltage > 97 % @ 24 V input voltage 150 x 34 x 130 0.3 kg -25…+70 °C / -40 °C…+85 °C 5 %…95 % RH IP20 III, without PE connection, for SELV 2 0.5 kV > 500.000 h according to IEC 1709 (SN29500) 150 x 60 x 130 0.6 kg -25…+70 °C / -40 °C…+85 °C 5 %…95 % RH IP20 III, without PE connection, for SELV 2 0.5 kV > 500.000 h according to IEC 1709 (SN29500) Horizontal on TS35 mounting rail, with 50 mm space at top and bottom. Direct side by side mounting allowed. Horizontal on TS35 mounting rail, with 50 mm space at top and bottom. Direct side by side mounting allowed. Class B CLass B EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields), EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted) EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields), EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted) Resistance against vibration and shock Electrical safety (applied standards) 1 g according to EN50178 / 15 g in all directions 1 g according to EN50178 / 15 g in all directions Electrical equipment of machines Safety transformers for switched-mode power units Safety extra low voltage Approvals according to EN60204 according to EN60204 according to EN50178 / VDE0160 according to EN50178 / VDE0160 SELV according to EN60950, PELV according to EN60204 SELV according to EN60950, PELV according to EN60204 Pending Connection data Conductor connection system Number of terminals CE, TUV, cULus, GL, GOST Input Screw connection Output Screw connection CE, TUV, cULus, GL, GOST Input Screw connection Output Screw connection 4 (1+, 2+, 1-, 2-) 0.5 / 6 0.5 / 2.5 4 (3+, 4+, 3-, 4-) 0.5 / 6 0.5 / 2.5 4 (1+, 2+, 1-, 2-) 0.5 / 16 2.5 / 10 4 (3+, 4+, 3-, 4-) 0.5 / 16 2.5 / 10 26 / 12 26 / 12 22 / 6 22 / 6 EMC / shock / vibration Noise emission acc. to EN55022 Noise immunity tests acc. to Conductor cross section, rigid min/max Conductor cross section, flexible min/max Conductor cross section, AWG/kcmil min/max Note mm² mm² Ordering data Type CP M DM20 A.10 Qty. 1 Order No. 1222210000 Type CP M DM40 Qty. 1 Order No. 1222220000 PRO-M: Diode modules, capacity module and relay module CP M RM24 Switch-mode power supplies connectPower PRO-M A red + black – 11 H 12 14 L W Technical data Input data Rated input voltage Input voltage range DC Output data 24 V DC 18…30 V DC Voltage monitoring Switching thresholds yes Potential free, floating contacts General data Max. 30 V DC / 1 A, CO contact Length x width x height mm Weight Ambient temperature (operational) / Storage temperature Max. permitted humidity (operational) Degree of protection Class of protection Pollution degree Insulation voltage I/O to housing MTBF Mounting position, installation notice 22 x 33 x 28 21.6 V DC, relay is on for Power Good 20.4 V DC, relay is off for Power Fail 75 g -25…+70 °C / -40 °C…+85 °C 5 %…95 % RH IP20 III, without PE connection, for SELV 2 0.5 kV > 500.000 h according to IEC 1709 (SN29500) Plugged in to the front of the PRO-M power supply EMC / shock / vibration Noise emission acc. to EN55022 Noise immunity tests acc. to Class B Resistance against vibration and shock Electrical safety (applied standards) 1 g according to EN50178 / 15 g in all directions Electrical equipment of machines Safety transformers for switch mode power units Safety extra low voltage Approvals according to EN60204 Pending Connection data Conductor connection system Number of terminals CE, TUV, cULus, GL, GOST Input Output 10 cm cable (red/black) with ferrules PUSH IN Conductor cross section, rigid min/max Conductor cross section, flexible min/max Conductor cross section, AWG/kcmil min/max EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields), EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted), EN61000-4-11 (Dips) according to EN50178 / VDE0160 SELV according to EN60950, PELV according to EN60204 3 (Changeover contact) 0.2 / 1.5 0.2 / 1.5 24 / 16 mm² mm² Note Ordering data Type CP M RM24 Qty. 1 Order No. 1222230000 A.11 PRO-M: Diode modules, capacity module and relay module Pulse triggering for cable circuit breakers: with the Weidmüller capacitance module The following conditions apply to the table entries: • Ambient temperature of 20 °C • Inner resistance of the circuit breakers is taken into account •Half of the rated current flows to a neighbouring circuit before the short circuit is formed •DC-compatible circuit breakers: Siemens 5SY series L 1+ 2+ + 11 H 12 14 12- W Distance in m Technical data Fuse tripping Input data Rated input voltage Input voltage range DC Output data Conductor cross section B6 10 m 0.75 mm2 24 V DC Peak current output Recovery time for the capacitor Voltage monitoring Switching thresholds 18…30 V DC 1.0 mm2 Depending on load 1.5 mm2 2.5 mm2 4 mm2 approx. 1 s yes Max. 30 V DC / 1 A, CO contact Length x width x height mm Weight Ambient temperature (operational) / Storage temperature Max. permitted humidity (operational) Degree of protection Class of protection Pollution degree Insulation voltage I/O to housing MTBF Mounting position, installation notice 150 x 34 x 130 B16 0.4 kg -25…+70 °C / -40 °C…+85 °C 5 %…95 % RH IP20 III, without PE connection, for SELV 2 0.5 kV > 500.000 h according to IEC 1709 (SN29500) Horizontal on TS35 mounting rail, with 50 mm space at top and bottom. Direct side by side mounting allowed. 1.0 mm2 1.5 mm2 2.5 mm2 4 mm2 6 mm2 0.75 mm 2 1.0 mm2 1.5 mm2 2.5 mm2 4 mm2 Noise emission acc. to EN55022 Noise immunity tests acc. to Class B 1.0 mm2 EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields), EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted), EN61000-4-11 (Dips) Resistance against vibration and shock Electrical safety (applied standards) 1 g according to EN50178 / 15 g in all directions 1.5 mm2 2.5 mm2 4 mm2 6 mm2 Electrical equipment of machines Safety transformers for switched-mode power units Safety extra low voltage Approvals according to EN60204 according to EN50178 / VDE0160 SELV according to EN60950, PELV according to EN60204 CE, TUV, GL cULus, GOST Input Screw connection Output Screw connection 4 (++--) 0.5 / 6 0.5 / 4 26 / 12 3 (Changeover contact) 0.5 / 6 0.5 / 2.5 26 / 12 Note Ordering data Type CP M CAP A.12 Qty. 1 Order No. 1222240000 4m 6m 10 m 16 m C2 11 m C4 6m 14 m 21 m 34 m 8m 12 m 19 m 32 m C6 3m C10 3,5 m 5,5 m 9m 14 m 2m 3m 5m 8m 12 m 6 mm2 0.75 mm2 mm² mm² 6m 9m 15 m 24 m 0.75 mm2 EMC / shock / vibration Pending Connection data Conductor connection system Number of terminals 14 m 20 m 30 m 50 m B10 6 mm2 21.6 V DC, relay is on for Power Good 20.4 V DC, relay is off for Power Fail Potential free, floating contacts General data Conductor cross section, rigid min/max Conductor cross section, flexible min/max Conductor cross section, AWG/kcmil min/max Load A CP M CAP Power supply + CAP module Switch-mode power supplies connectPower PRO-M