VAL-SQ SI… SPD - Configurators

VAL-SQ SI…
36 to 120 kA Surge Protective Device for small
installation protection
TRABTECH
Data Sheet
2789_en_F
1
© PHOENIX CONTACT 2011-04-29
Description
The VAL-SQ SI… Surge Protective Device (SPD) provides
surge protection in a compact, affordable package.
A high-energy suppression circuit provides 36 to 120 kA
(depending upon the model) of surge current rating per
phase. Each surge suppression mode in the VAL-SQ SI… is
individually fused for safety.
The VAL-SQ SI… SPD uses a sealed, NEMA 4X housing,
allowing installation in harsh environments with limited
space. Operating status lights are easily observed and
provide verification of protection.
– The VAL-SQ SI 36-2C-120 provides compact protection
of 120 V applications with bonded neutral and ground.
– The VAL-SQ SI 40-3C-600 is for three-phase Wye
applications up to 600 V with bonded neutral and
ground.
– The VAL-SQ SI 40-3-600D is for three-phase Delta
applications up to 600 V.
– The VAL-SQ SI… 120/240S SPDs are for single- and
split-phase 120/240 applications with common or
separate neutral and ground.
2
–
–
–
–
–
–
Features
Compact design for flexible mounting locations
36 to 120 kA surge current capacity per phase (L-N and
N-G) protects against high-energy lightning strikes and
transient voltages
UL nominal surge discharge current (In) rating of 10 kA
NEMA 4X enclosure
LEDs provide continuous feedback on the status of
each phase
UL/cUL listed; meets UL 1449 3rd edition
DANGER: HAZARD OF ELECTRIC SHOCK OR ARC FLASH
Confirm the SPD voltage rating on the module or nameplate label is the same as the operating voltage.
Risk of electric shock. Disconnect power before installing or servicing. Service to be performed by qualified
personnel only.
The products described in this data sheet are exclusively for export outside of the European Economic area (EC).
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog.
This data sheet is valid for all products listed on the following page:
8251-0208F
VAL-SQ SI…
3
Ordering Data
Products
Description
Type
Part No.
Pcs./Pkt.
Surge protective device, 36 kA, 2-phase, 2-wire + ground for 120 V (L-N)
applications with common GND-N
VAL-SQ SI 36-2C-120
2800003
1
Surge protective device, 50 kA, 2-phase, 2-wire + ground + neutral for
120 V (L-N) applications with separate GND and N
VAL-SQ SI 50-120/240S
2800323
1
Surge protective device, 80 kA, 2-phase, 2-wire + ground + neutral for
120 V (L-N) applications with separate GND and N
VAL-SQ SI 80-120/240S
2800324
1
Surge protective device, 100 kA, 2-phase, 2-wire + ground + neutral for
120 V (L-N) applications with separate GND and N
VAL-SQ SI 100-120/240S
2800325
1
Surge protective device, 120 kA, 2-phase, 2-wire + ground + neutral for
120 V (L-N) applications with separate GND and N
VAL-SQ SI 120-120/240S
2800326
1
Surge protective device, 40 kA, 3-phase, 3-wire + ground
for up to 600 V (L-N) applications with common GND-N
VAL-SQ SI 40-3C-600
2800007
1
Surge protective device, 40 kA, 3-phase, 3-wire for up to 600 V (L-N)
applications without ground
VAL-SQ SI 40-3-600D
2800824
1
4
Technical Data
Surge Protection Data
Maximum surge current per phase
2800003
2800323
2800324
2800325
2800326
36 kA
50 kA
80 kA
100 kA
120 kA
2800007/
2800824
40 kA
Short circuit current rating (SCCR)
25 kA
200 kA
Nominal voltage
120 V
600 V1
Current rating (In)
10 kA
Circuit type
MOV technology
UL Class
1
Type 1
Up to 600 V
Voltage Protection Rating (VPR)
L-N
N-G
L-L
L-G
Part No.
Type
MCOV
2800003
VAL-SQ SI 36-2C-120
150
700
NA
1200
NA
2800323
VAL-SQ SI 50-120/240S
150
700
NA
1200
800
2800324
VAL-SQ SI 80-120/240S
150
700
NA
1200
800
2800325
VAL-SQ SI 100-120/240S
150
700
NA
1200
800
2800326
VAL-SQ SI 120-120/240S
150
700
NA
1200
800
2800007
VAL-SQ SI 40-3C-600
750
2500
NA
4000
NA
2800824
VAL-SQ SI 40-3-600D
750
2500
NA
4000
NA
General Data
2800003
Dimensions (WxHxD)
2.25 x 2.25 x
1.94 in.
(57 x 57 x
49 mm)
Weight
0.53 lb.
(0.24 kg)
Phase connection
Parallel
#14 AWG
2800323
2800324
2800325
3.00 x 3.60 x 2.67 in.
(76 x 91 x 68 mm)
Parallel
#12 AWG
Parallel
#12 AWG
Parallel
#12 AWG
1/2-in. NPT
Enclosure material
Non-metallic
2800007/
2800824
3.60 x 3.00 x
2.64 in.
(92 x 76 x
64 mm)
1.6 lb. (0.73 kg)
Conduit connector
2789_en_F
2800326
1.0 lb. (0.45 kg)
Parallel
#12 AWG
Parallel
#12 AWG
PHOENIX CONTACT
2
VAL-SQ SI…
General Data
2800003
2800323
2800324
Housing rating
2800325
2800007/
2800824
NEMA 4X
Operating frequency
50/60 Hz
Operating temperature
-40 to 70°C (-40 to 160°F)
Operating altitude
0 to 12,000 ft. (3,658 m)
Approvals
U
1449 3rd edition
1283
CSA
C22.2 No. 8-M1986
IEEE
C62.41.1-2002
C62.41.2-2002
C62.45-2002
5
2800326
Dimensions
2.25 in.
57 mm
0.75 in.
19 mm
2.64 in.
67 mm
1.94 in.
49 mm
3.00 in.
76 mm
2.25 in.
57 mm
3.60 in.
91 mm
2800003 Dimensions
0.75 in.
19 mm
Figure 1
Figure 2
2789_en_F
2800007, 2800824 Dimensions
PHOENIX CONTACT
3
VAL-SQ SI…
0.75 in.
19 mm
3.60 in.
91.4 mm
3.00 in.
76.2 mm
0.87 in.
22 mm
2.67 in.
68 mm
Figure 3
6
2800323, 2800324, 2800325, 2800326 Dimensions
Installation
6.1
1.
DANGER:
Turn off all power supplying this equipment
before working on or inside equipment.
Always follow federal and local regulations during
installation. Apply appropriate personal
protective equipment (PPE) and follow electrical
work practices.
Only qualified electrical personnel may install and
service this equipment.
Mounting and connection
Position the VAL-SQ SI… so the LEDs are visible and
the wires are as short and straight as possible.
The SPD can be mounted in any orientation. It attaches
through any side of the enclosure being protected using
1/2-NPT threaded nipple.
NOTE:
Cover or remove components inside any
enclosure before drilling to prevent shavings from
causing short-circuits across terminals and races.
Never open SPD. No serviceable parts are inside.
WARNING:
This equipment depends upon an effective
ground. Failure to obtain a quality ground
connection may result in explosion or arc flash.
NOTE:
Megger® or hi-potential tests will damage this
surge protective device. Turn off all power
supplying the equipment and isolate the surge
protective device before testing.
NOTE:
Variant 2800007: Suitable for use on a circuit
capable of delivering not more than 200,000 rms
symmetrical Amperes.
All variants except the 2800007: Suitable for use
on a circuit capable of delivering not more than
25,000 rms symmetrical Amperes.
2789_en_F
PHOENIX CONTACT
4
VAL-SQ SI…
2.
Create a hole in the enclosure, 2, for 1/2-in. conduit
attachment, approximately 7/8 in. (22 mm) diameter.
VAL-SQ SI Series
Surge Protective Device
TRABTECH
www.phoenixcontact.com
1
2
121
2
Black
White
C
1
3
N
A
Figure 5
1
2
SPD
Protected device
3
Single-phase, 3-wire, 120/240 V AC
connection
Strain relief nut
VAL-SQ SI Series
Figure 4
3.
4.
Route the wires and nipple through the hole and secure
the VAL-SQ SI… to the enclosure with the strain relief
nut, 3.
Connect the VAL-SQ SI… to the appropriate phases
and ground lines. Table provides a cross reference
between the figure number and order number. Wires
are color coded as shown. If equipped with a green
wire, it must be connected to ground.
Figure No.
5
6
7
8
Configuration
3-wire, 120/240 V AC single
phase
3-phase Wye, 208 V AC
3-wire + ground, 120 V AC
single phase
3-phase Wye, 208, 480 or
600 V AC
3-phase High-Leg Delta,
120/240 V AC
3-phase, Delta, 240, 480,
600 V AC
9
10
1
VAL-SQ SI Series
Surge Protective Device
Mounting the SPD
1
2
TRABTECH
Black
White
www.phoenixcontact.com
12 1
Surge Protective Device
TRABTECH
www.phoenixcontact.com
12 1
A
C
N
Order No.
2800003
28000031
2800323
2800324
2800325
2800326
2800007
B
Figure 6
3-phase Wye, 208 V AC connection
2800007
2800824
requires two SPDs
2789_en_F
PHOENIX CONTACT
5
VAL-SQ SI…
1
2
3
1 2 33
1
2
Green
White
Black
VAL-SQ SI Series
Black
White
Surge Protective Device
TRABTECH
www.phoenixcontact.com
2 1 11
N
A
A
N
C
C
Figure 7
1- or 2-phase, 120 V AC connection
B
Figure 9
3-phase High-Leg Delta, 120/240 V AC
connection
VAL-SQ SI Series
Surge Protective Device
1
2
Black
White
TRABTECH
www.phoenixcontact.com
2 111
VAL-SQ SI Series
Surge Protective Device
A
1
Black
TRABTECH
www.phoenixcontact.com
1 11
C
N
A
C
B
Figure 8
3-phase Wye, 208, 480 or 600 V AC
connection
B
Figure 10
2789_en_F
3-phase, Delta, 240, 480, 600 V AC,
connection, corner ground or floating ground
PHOENIX CONTACT
6
VAL-SQ SI…
Type 1 SPDs can be connected on either side of the
service entrance. Disconnects to the SPD are
recommended.
All wires must be connected to properly installed circuit
breakers sized according to the wire gauge. Use an
appropriate breaker, i.e., 2- or 3-pole, for the electrical
configuration.
7
Operation
LEDs indicate the operating status of the individual phases
of the VAL-SQ SI… The LEDs illuminate when the relevant
phase is operating correctly.
Device
Phase
Phase
LED
LEDs
LEDs
All wires must be connected for the SPD to
function correctly.
The wires between the SPD and protected device
should be twisted 1/2 turn every 12 in. (300 mm).
Do not loop or coil wire. Excess wire must be
removed without applying stress to wires.
VAL-SQ SI Series
VAL-SQ SI Series
VAL-SQ SI Series
Surge Protective Device
Surge Protective Device
Surge Protective Device
TRABTECH
www.phoenixcontact.com
TRABTECH
www.phoenixcontact.com
TRABTECH
Figure 11
www.phoenixcontact.com
LED location
If a phase is not operating correctly or a fault occurs, the
corresponding LED is not lit.
When a phase LED is not lit, verify the correct voltage is
present on each phase. If power is present, the VAL-SQ
SI… must be replaced. There are no serviceable parts.
2789_en_F
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
7