400 Series - Emerson Network Power

Power Switching & Controls
For Business-Critical Continuity™
400 Series
420 Surge Protective Device
Installation, Operation and Maintenance Manual
Installation, Operation and Maintenance Manual
IO-70104 Rev 1, 1/2014
EMERSON NETWORK POWER SURGE PROTECTIVE DEVICE
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
TABLE OF CONTENTS
INSTALLATION
Environment..................................................................................................................2
Mounting ......................................................................................................................2
Wire Sizing/Routing .......................................................................................................2
Conduit Connection ......................................................................................................2
Wiring Connections .......................................................................................................................... 2
Applying Power ................................................................................................................................. 3
PRODUCT RATINGS AND LIMITATIONS
Voltage Protection Ratings.............................................................................................3
Circuit Ampacity Limitations ..........................................................................................3
TROUBLESHOOTING/SERVICING/MAINTENANCE
Troubleshooting ............................................................................................................3
MODEL NUMBER CONFIGURATION
Model Number Configuration ........................................................................................3
Configuration & Voltage (Chart).....................................................................................4
SPD WIRING and MOUNTING
Circuit Breaker and Wire Size .........................................................................................5
Parallel Wiring Diagram .................................................................................................5
Screw Mounting ............................................................................................................5
DIN Rail Mounting Kit ....................................................................................................5
Dimensional Information ...............................................................................................6
Installation, Operation and Maintenance Manual
1
IO-70104 Rev 1, 1/2014
The Emerson Network Power 420 Surge Protective Devices are high quality, high energy surge
current diversion system designed to protect sensitive equipment from damaging transient
voltage surges resulting from load switching, lightning strikes and other sources.
The installer should perform the following steps to assure a quality installation. Please read all
instructions before starting the installation of this product. These instructions do not replace
national or local electrical codes — check applicable codes to ensure compliance.
INSTALLATION
DANGER! ONLY QUALIFIED PERSONNEL SHOULD INSTALL
OR SERVICE THIS SYSTEM. ELECTRICAL SAFETY PRECAUTIONS MUST BE FOLLOWED WHEN INSTALLING OR
SERVICING THIS EQUIPMENT. TO PREVENT RISK OF ELECTRICAL SHOCK, TURN OFF AND
LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE MAKING ELECTRICAL
CONNECTIONS OR SERVICING.
DANGER! SEULEMENT LE PERSONNEL QUALIFIÉ DOIT INSTALLER OU MAINTENIR CE
SYSTÈME. DES PRÉCAUTIONS DE SÉCURITÉ EN ÉLECTRICITÉ DOIVENT ÊTRE SUIVIS LORS
DE L'INSTALLATION OU DE LA MAINTENANCE DE CET EQUIPEMENT. POUR EVITER TOUT
RISQUE DE CHOC ÉLECTRIQUE, DÉBRANCHEZ ET VEROUILLER TOUTES LES SOURCES D’
ALIMENTATION DE CET EQUIPEMENT AVANT DE LE BRANCHER OU LE MAINTENIR.
Environment — The unit is designed for operation indoors in ambient temperatures of 40ºC (-40ºF) to +85ºC (+185ºF) with a relative humidity of 0% to 95% (non-condensing). The
unit is provided in an industrial enclosure, which should not be installed in areas with excessive
dust, corrosive vapors, flammable materials or explosive atmospheres.
Mounting — Mount unit as close as possible to the service panel in close proximity to the
breaker that will feed the SPD., Remove plastic cover on unit to gain access to the four
mounting holes in case. Use #6 x 3/4” self-threading screws (provided), to mount the SPD to
wall or metal back plane. Replace cover on unit and torque cover screws to 10 IN-LBS, (see
drawing). For best performance, unit should be positioned so that the length of the wiring to
the surge protective device (SPD) unit is minimized.
Wire Sizing/Routing — #12 AWG wiring is provided with unit. To reduce the wiring
impedance to surge currents, the phase, neutral (if required), and ground conductors are
recommended to be twisted together and routed in the same raceway (conduit). Avoid any
sharp bends in the conductors. All wiring must comply with the National Electrical Code (NEC)
and applicable local codes.
Conduit Connection — The SPD wires should feed through the plastic conduit piece supplied.
The conduit should be cut to match the distance from the unit to electrical panel. Use the
supplied conduit hub to connect to the electrical panel.
Wiring Connections — Before making connections to the unit, verify that the unit model
number and nameplate voltage rating are appropriate for connection to the intended power
source (See table).
1. It is recommended that a 20A circuit breaker be used for installation and connection to the
service panel.
2. Connect the white wire (if provided) of the SPD to the neutral of the supply, and connect
the green wire (if provided) of the SPD to source ground.
3. Connect each Black Phase Wire to corresponding phase on the service panel.
4.
If not using the relay contact wires for remote sensing, cut and dress the wires. If
using remote sensing, these wires are connected to COM (orange), NC (blue), and NO (yellow)
respectively. (Relay’s maximum switching capacity is 250VAC, 5A.)
(continued)
Installation, Operation and Maintenance Manual
2
IO-70104 Rev 1, 1/2014
CAUTION — For proper and safe operation, neutral and
ground MUST be reliably connected. Failure to operate this
unit from a solidly grounded power source of the proper
configuration will reduce or impede operation, and may result in unit failure.
ATTENTION - Pour un fonctionnement correct et sûr, le neutre et la mise à la terre doit
être connectés de manière fiable. Défaut de faire fonctionner cet appareil à partir d'une
source d'alimentation solidement mise à la terre va réduire ou même empêcher le
fonctionnement correct et peut entraîner une défaillance de l'unité.
Applying Power — Apply power to the SPD and assure status indications are normal. Under
normal conditions, the green “OK” LED is illuminated and the red “REPLACE” LED is OFF. If
normal status indication does not exist, see “TROUBLESHOOTING”.
PRODUCT RATINGS AND LIMITATIONS
Voltage Protection Rating – To obtain the voltage protection ratings (VPRs), as obtained by
Underwriters Laboratories, Incorporated, in accordance with the Standard for Safety, Surge
Protective Devices (SPDs), Standard 1449 Third Edition, released 2009, marked on this product,
the #12 AWG wire supplied must be utilized to connect the 420 SPD to your facilities’ power
grid. Connections made with conductors other than #12 AWG may result in different VPRs.
Circuit Ampacity Limitations – This device has been investigated by Underwriters
Laboratories, Incorporated to withstand, without exposing live circuits or components on
power sources, a voltage of two times (2x) the device ratings, and fault currents of up to
200,000 AIC, as described in the Standard for Safety, Surge Protective Devices (SPDs), Standard
1449, Third Edition, released 2009.
TROUBLESHOOTING
If any of the diagnostic indicators indicates a problem (i.e. red LED ON, and/or green LED OUT), check
all connections and voltages to the unit. If all connections are reliable, and proper voltages are
supplied to the unit, call Emerson Network Power Surge Protection, Inc at 607-721-8840.
MODEL NUMBER CONFIGURATION
Model #: _
_
_
_
_
_
_
_
_
_
_
_
_
1
2
3
4
5
6
7
8
9
10
11
12
13
(1-3) Series
(8) Modes of Protection
420 = Non-Modular MOV - A = All Modes of
Medium Exposure
Protection .. (100kA Per Phase)
B = L-N & N-G .... (50kA Per Phase)
(4-5) Configuration &
E = L-L ............... (50kA Per Phase)
Voltage
F = L-N .............. (50kA Per Phase)
See Chart on Next Page
(9) Connection Type
(6-7) Surge Rating Per
Mode
05 = 50kA
W = Wire Leads
(10) Monitoring Options
R = LED/Relay
A = LED/Alarm/Relay
Installation, Operation and Maintenance Manual
3
(11) Enclosure
J = NEMA Type 4X
(plastic)
(12) UL 1449 Type
0 = No UL
1 = Type 1, 20kA
2 = Type 2, 20kA
(13) MOV Option
S = Standard
Q = High Rated
IO-70104 Rev 1, 1/2014
CONFIGURATION & VOLTAGE (CHART)
3
Installation, Operation and Maintenance Manual
4
IO-70104 Rev 1, 1/2014
SPD WIRING & MOUNTING
CIRCUIT BREAKER & WIRE SIZE
Overcurrent Protection:........... 20A Recommended
Connection Wire: ..................... Phase/Neutral/Ground; (24” of #12 AWG Included)
Summary Alarm Contacts ........ 24” of #18 AWG Included; (WIth AC Applied)
Normally Open .......... (NO) = Yellow
Normally Closed ......... (NC) = Blue
Common ................... (COM) = Orange
250VAC, 5A max
PARALLEL WIRING DIAGRAM
SCREW MOUNTING
Remove cover, and use #6 x 3/4”
self-threading screws (provided)
for mounting,
Replace cover, torque screws to
10 in/lbs.
DIN RAIL MOUNTING KIT
The optional DIN Rail mounting kit allows the 420 SPD to be installed on standard 35mm
industrial Din Rail. Individual clips mount to the bottom of the enclosure using 6-32 hardware
included.
Part Number: 420-DIN (Sold separately)
Installation, Operation and Maintenance Manual
5
IO-70104 Rev 1, 1/2014
DIMENSIONAL INFORMATION
Modes of Protection
A
B
Reduced Mode Units
(“B”, “E”, “F”)
3.24 [82.2]
5.00 [126.9]
6.30 [160]
8.04 [204.2] 5.83 [148.0] 1.9 lbs [0.86kg]
All Mode Units
(“A”)
C
Weight
2.76 [70.0] 1.2 lbs [0.54kg]
1/2 NPT flexible conduit and
connector assembly included,
Installation, Operation and Maintenance Manual
6
IO-70104 Rev 1, 1/2014
Emerson Network Power
Surge Protection
100 Emerson Parkway
Binghamton, NY 13905
800 288 6169 Phone (U.S. & Canada Only)
607 721 8840 (Outside U.S.)
607 722 8713 FAX
United States of America
Emerson Network Power
European Headquarters
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
Italy
39 049 9719 111 Phone
39 049 5841 257 FAX
Emerson Network Power Asia Pacific
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
+63 2 730 9572 FAX
Technical Support
800 288 6169 Toll-Free
607 721 8840 Phone
607 722 8713 FAX
Emerson Network Power.
The global leader in enabling Business-Critical
Continuity™.
 AC Power
 Connectivity
 DC Power
 Embedded Computing
 Embedded Power
 Industrial Power
 Infrastructure Management & Monitoring
 Outside Plant
 Power Switching & Controls
 Thermal Management
 Racks & Integrated Cabinets
 Service
EmersonNetworkPower.com/Surge
While every precaution has been taken to ensure accuracy and
completeness in this literature, Emerson Network Power assumes
no responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
© 2014 Emerson Network Power. All rights reserved throughout
the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
of their respective owners.