Uninterruptible Power Supply Unit
for Universal Use QUINT-DC-UPS/24DC/40
1. Short Description
Uninterruptible Power Supply Units for Buffering
Long-Term Power Interruptions
• Saves space thanks to the compact, uniform design
• Integrated diode saves money through isolation of
loads
• Maximum system availability through optimum
battery management and reliable signaling
• Minimum installation time due to ready-to-use
plug-in bridges and integrated timeout
QUINT-DC-UPS uninterruptible power supply units
with long-life lead-acid batteries provide long buffer
times at high currents. Even in the event of a longer
supply voltage failure, the units ensure that all
connected devices continue to operate without
interruption.
The devices have a narrow and uniform design,
which makes them ideal for use on the DIN rail where
space is limited. In addition, short wiring paths ensure
order and clarity in the control cabinet.
The high level of availability and the particularly long
service life of the battery modules are achieved
through professional battery management. An
automatic presence check (every minute), automatic
quality test (once a week), temperature-determined
charging, and electronic overcurrent protection ensure
the battery modules are ready to operate at all times.
Power is therefore available in the event of an error and
the service life of the battery module is maximized.
The actual state must be determined quickly so that
the right decision can be made in an emergency.
Optimum signaling is thus required for maximum
system availability. Three floating PDT contacts and
three LEDs are provided for function monitoring, which
indicate all the operating states clearly.
So that relay signaling is more reliable and more
durable than before, an additional positive supply
output has been provided. The contact, which is
current-limited and resistant to continued short circuits,
is located next to the relay connections and enables
easy bridging. In the event of wiring errors, the shortcircuit protection prevents any welding of the relay
contacts. This ensures that the user can rely on an OK
signal. Even in the event of connection errors, currents
remain below 100 mA, which prevents damage to the
relay contacts.
A system is switched off after a specific time that can
be set on the device or by an external signal. No
additional installation is required for shutdown. In
addition, ready-to-use plug-in bridges minimize the
installation time.
The connected devices can be divided into buffered
and unbuffered loads using the isolated input. This
extends the buffer time, which depends on the output
current. If only critical devices are protected using
fuses, smaller battery modules can be used that save
money and space in the control cabinet. In addition, the
isolated input protects the connected devices against
errors in the internal network.
Headquar ters: © Phoenix Contact GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany
Phone +49 - 52 35 - 30 0 • Fax +49 - 52 35 - 34 12 00 • www.phoenixcontact.com
Local Contact: www.phoenixcontact.com/salesnetwork
Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
2. Technical Data
125 mm (4.921 in.)
-
2 2
+ 2 4 V
2 0 0 m A
2 3
3 1
O u tp u t
0 -2 0 A D C
In p u t
D C 2 4 V
3 2
3 3
A la r m
1 3
2 1
130 mm
(5.118 in.)
B a tte ry
1 2
R 2
B a t. M o d e
2 x 1 2 V
1 1
R 1
C h a rg e
J
+
R e m o te
O n /O ff
t...[m in ]
B a t.-S e le c t [A h ]
66 mm
(2.598 in.)
QUINT-DC-UPS/24DC/40
DC UPS Module
Solid Stranded
[mm2]
Input
Output
Signal
0.5 - 16
0.5 - 16
0.2 - 2.5
0.5 - 10
0.5 - 10
0.2 - 2.5
AWG
Torque
[Nm]
20 - 6
20 - 6
25 - 14
1.2 - 1.5 10.6 - 13.3
1.2 - 1.5 10.6 - 13.3
0.5 - 0.6 4.5 - 5.3
[lb in]
UuF
L [mm]
10
mm (0.39 in.)
7 mm (0.28 in.)
Description
Type
Order No.
Uninterruptible power supply unit
3.4 Ah battery module
7.2 Ah battery module
12 Ah battery module
QUINT-DC-UPS/24DC/40
QUINT-BAT/24DC/3,4Ah
QUINT-BAT/24DC/7,2Ah
QUINT-BAT/24DC/12Ah
28 66 24 2
28 66 34 9
28 66 35 2
28 66 36 5
Technical Data
Input Data
Nominal input voltage
Input voltage range
Current consumption
Switching threshold
Buffer time
Input fuse
Maximum power dissipation
(No load/charging/maximum)
Can be configured
(Ready/buffer mode)
24 V DC
22.5 - 30 V DC
0.1 A/2.5 A/42.5 A
Ua < 22 V; dynamic Uin - 1 V/0.1 s
0.5; 1; 2; 3; 10; 15; 20; 30; continuous
Internal, 50 A
20 W/30 W
Output Data
Can be connected in parallel (battery module)
Yes, to increase the buffer time
Output Data in Normal Operation
Nominal output voltage
Output voltage
Output current
Current limit
Overload fuse
24 V DC
Uin
40 A
None
Internal, 50 A
Output Data in Buffer Mode
Nominal output voltage
Output voltage
Output current
Current limit
Overload fuse
Level of efficiency
Remote shutdown
Maximum
Typical
24 V DC
27.9 V DC
40 A (25 A for 3.4 Ah battery module)
45 A
Electronic
98%
Yes
Charging
Charge characteristic curve
End-of-charge voltage
Charge current
Battery/presence check/time interval
Battery/quality test/time interval
I/U characteristic curve
Temperature compensated
< 2.5 A
60 seconds
180 hours
Memory Medium
Nominal voltage
Nominal capacity
Charge current
External
24 V DC
3.4 Ah, 7.2 Ah, 12 Ah
< 2.5 A
PHOENIX CONTACT page 2 of 9
Pcs.
Pkt.
1
Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
Signaling
Power In OK
Alarm
Green LED
Red LED, floating PDT,
30 V AC/DC, maximum; 1 A, maximum
Yellow LED, floating PDT,
30 V AC/DC, maximum; 1 A, maximum
Yellow LED, flashing, floating PDT,
30 V AC/DC, maximum; 1 A, maximum
Battery Mode
Battery Charge
Approvals/Standards
Electrical equipment of machines
Electrical safety (of IT equipment)
EN 60 204 (Surge Voltage Category III)
EN 60950/VDE 0805,
UL/C-UL Recognized UL 60 950
UL/C-UL Listed UL 508
Germanischer Lloyd
EN 50 178/VDE 0160
Industrial control equipment
Shipbuilding
Electronic equipment for use in electrical power installations
General Data
Insulation voltage
Input/output to housing:
Degree of protection
Class of protection
MTBF
According to IEC 1709 (SN 29 500)
Housing version
Dimensions (W x H x D) default upon delivery
Dimensions (W x H x D) rotated 90°
Weight
Approximately
1 kV AC type test
1 kV AC routine test
On a horizontal 35 mm (1.378 in.) DIN rail
EN 60 715
1 kV/1 kV
IP20
II
> 500,000 h
AluNox (AlMg1), closed
(66 x 130 x 125 mm [2.598 x 5.118 x 4.921 in.])
(122 x 130 x 69 mm [4.803 x 5.118 x 2.717 in.])
0.9 kg
Climatic Data
Ambient temperature
Humidity
Vibration
Operation/storage
At +25°C (+77°F)
According to IEC 68-2-6
-25°C to +70°C (-13°F to +158°F)/-40°C to +85°C (-40°F to +185°F)
95%, no condensation
15 - 150 Hz, 2.3g, 90 minutes
Shock (in all space directions)
Pollution degree
Climatic category
According to IEC 68-2-6
According to EN 50 178
According to EN 60 721
30g
2
3K3
Mounting position
c
Conformance With EMC Directive 89/336/EEC
and Low Voltage Directive 73/23/EEC
EMC (Electromagnetic Compatibility)
Noise Immunity According to EN 61000-6-2:
Noise Immunity According to EN 61000-6-2
• EN 61000-4-23)
Electrostatic discharge
(ESD)
• EN 61000-4-32)
Electromagnetic HF field
Requirements
EN 61 000-6-2
Housing
Contact discharge:
Air discharge:
Housing
Frequency:
Field strength:
• EN 61000-4-43)
Fast transients (burst):
Input:
Output:
Signal:
Input:
• EN 61000-4-53)
Surge current loads (surge):
Output:
Signal:
• EN 61000-4-62)
Conducted interference
I/O/S:
Frequency:
U0:
• EN 61000-4-113)
Voltage dips
Input:
Noise Emission According to EN 50081-2
• Radio interference emission
EN 55011
• Radio interference voltage
EN 55011
EN 55011 corresponds to CISPR11/EN 55022 corresponds to
CISPR22/EN 61000 corresponds to IEC 1000
2) Criterion A:
Normal operating characteristics within the
specified limits.
3)
Criterion B:
Temporary adverse effects on the operating
characteristics that the device corrects
automatically.
QUINT-DC-UPS/24DC/40
4 kV
8 kV
Level 4
8 kV
15 kV
80 -1000 MHz
10 V/m
Level 3
80 - 1000 MHz/1.4 - 2.0 GHz
10 V/m
2 kV
2 kV
1 kV
2 kV
2 kV
0.5 kV
0.5 kV
1 kV
asymmetrical5)
asymmetrical5)
asymmetrical5)
asymmetrical5)
symmetrical4)
asymmetrical5)
symmetrical4)
asymmetrical5)
0.15 - 80 MHz
10 V
asymmetrical5) Level 3
0.15 - 80 MHz
10 V
4 kV (Level 4)
2 kV (Level 3)
1 kV (Level 2)
4 kV (Inst. Class 4)
2 kV (Inst. Class 4)
0.5 kV/(Level 1)
0.5 kV/(Level 1)
1 kV/(Level 2)
30% reduction of the input voltage
for 0.5 periods
See Input Data:
Mains buffering
> 20 ms
Class A6)
Class A6)
EN 55011 (EN 55022) Class B7)
EN 55011 (EN 55022) Class B7)
4)
Symmetrical:
5) Asymmetrical:
6) Class A:
7) Class B:
PHOENIX CONTACT page 3 of 9
Cable to cable.
Cable to ground.
Industrial applications
Industrial and domestic applications
Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
3. Device View, Connections, and Control Elements
8
7
13
3 14 D
14O DC
C
OK
K ++
++
4V
0,2
13
3 14 D
11 14 O DC
C
21OK
K +
31 + +
R1 +
1
9
QUINT DC-UPS 40 A
A
4
5
2
13
11
Ala
R2
22
rm
32
33
21
Ba 3
Mo t.- 1
de Ba
Ch t.ar
ge
R1
Re
m R2
ot
e
OF
ONF
Ala
rm
B
Ba at.-M
t.-C o
ha de
rg
e
Po
we
r In
OK
t
m
[m ax 0,5 1
in] ∞
6
D
In C 24
pu
t V
+
–
40
O A
ut
pu
t
30
Ba
t.-S
2
ele 0
c
[A t
h]
L
IA
S
TR
AL
US OL T
OV INDNTRMEN
rm
Ala
de
Mo e
t.- arg
Ba -Ch
t.
Ba
OK
In
r
we
Po
2
PR
AP
U
F
COUIP
EQKA
43
D
TE
LIS
3
5
15 10
Ser
vice
≤3
,4
7,
≥1 2
2
Ba
tte
r
+
-2
0-6
00
61 81-1
EN 500
EN
5
–2
+
–
A
/40
/43 C
DC
/24 2 DC VD
PS 24 24V -30 0A
6
C-U8 6
2.5 C/4
:2 D
T-D
.: 2
ge 24V
o
IN
a
N
olt
QU er°C
lV
70 F
Ordut: ona
+ 58 °
Inperati
5…+1
Optput:
-2 …
3
Ou
-1
–
23
on
in
st
ru
ct
io
ns
ti
la g
al
s t tin
i n nec
a d con
R e ore
f
be
0
!
y
"
–
1
www.interface.phoenixcontact.com
+2
§
$
2
3
Figure 04
1 DC input, unbuffered
24 V DC input voltage
(0.5 mm2 to 16 mm2 solid)
(0.5 mm2 to 10 mm2 stranded)
(20 - 6 AWG)
Internal fuse 50 AT
2 DC output, buffered
24 V DC output voltage
(0.5 mm2 to 16 mm2 solid)
(0.5 mm2 to 10 mm2 stranded) (20 - 6 AWG)
The device is idling-proof and short-circuit-proof.
3 24 V battery module connection
4 Floating PDT (11,12,13): Alarm
5 Floating PDT (21,22,23): Battery Mode
6 Floating PDT (31,32,33): Battery Charge
7 24 V supply voltage, maximum current limit 0.2 A
for grouped contacts 11, 21, 31
8 Remote shutdown (R1, R2)
9 Universal DIN rail adapter UTA 107
0 Red LED: Alarm
! Yellow LED: Battery Mode/Battery Charge
" Green LED: Power In OK
§ Buffer time setting 0.5 - 30 minutes
$ Battery module/Service setting selection
4. Safety Notes and Warning
Instructions
To ensure that the device can be operated safely
and all functions can be used, please read these
instructions carefully.
The QUINT-DC-UPS is a built-in device. Installation
and startup must only be carried out by qualified
personnel. The relevant country-specific regulations
(e.g., VDE, DIN) must also be observed.
Before startup it is particularly important to ensure
that:
• All supply lines have sufficient fuse protection and
are the correct size.
• All output cables are the correct size for the maximum
device output current or have separate fuse
protection.
• Sufficient convection is ensured.
• The fuse on the battery module is always removed
when carrying out any work.
PHOENIX CONTACT page 4 of 9
Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
5. Installation
5.1. Mounting
The uninterruptible power supply unit together with
the battery module can be snapped onto all DIN rails
according to EN 60715 and should be mounted
horizontally (input terminal blocks facing downwards).
4V
QUINT DC-UPS 40
20 A
Installation Dimensions
No minimum spacing to other modules is
required for proper operation of the
device.
13
A 3 14 D
11 14 O DC
C
21OK
K +
31 + +
R1 +
1
0,2
2
13
11
Ala
R1
23
Re
32
m R2
33
ote
21
OF
Ba 3
ONF
Mo t.- 1
de Ba
Ch t.arg
e
Ala
rm
B
Ba at.-M
t.-C o
ha de
rg
e
Po
we
r In
OK
t
–
V
20
4
O A
ut
pu
t
[m ax 0,5 1
in] ∞
30
Ba
t.-S
20
ele
c
[A t
h]
2
Ba
t
+
L
IA
S
TR
AL
US OL T
OV INDNTRMEN
PR
AP
U
F
COUIP
EQKA
43
ED
ST
LI
3
5
15 10
Se
rvice
≤3
,4
7,2
≥1
2
+
–
-2
0-6
00
61 81-1
EN 500
EN
–2
rm
larm
Ala
e
A
od
de e
-Moarg
rge
t.-M
at.
ha
B
-Ch
Bat.-C
K
at.
Ba
OK
B
In O
err In
we
o
w
Po
P
m
D
In C 24
pu
t
+
/20
/4
2A
/23
/4
DC
C
9 VDC VD
/243 2
0 0A
PS 24
24.5-3 /4
6
/2
C-U8 6
22 DC
T-D 2
e: V
IN No.:
ag 24
olt
QU erlV
rd
0 °C
a
7
O ut: on
+ 8 °F
Inperati
… 15
t:
p
5
+
u
O tp
-2 …
3
Ou
-1
5
–
R2
22
rm
www.interface.phoenixcontact.com
13
3 14 D
14O DC
C
OK
K ++
++
+2
ti o
ll a g
s ta tin
in nec
a d con
R e re
fo
be
n
in
s tr
uc
ti o
ns
te
ry
–
Figure 05
5.2. Narrow Mounting Position
The device is supplied ex works for a narrow
mounting position.
Mounting:
Place the module with the DIN rail guideway on the
top edge of the DIN rail and then snap it downwards.
Removal:
Release the snap-on catch using a screwdriver and
then detach the module from the bottom edge of the
DIN rail.
5.3. Flat Mounting Position
A flat mounting position can be achieved by
mounting the module onto the DIN rail at a 90° angle.
To do this, mount the DIN rail adapter (UTA 107) 7 as
shown in Figure 07. No additional assembly material is
required. Mounting screws: Torx T10
(torque 0.8 - 0.9 Nm).
Mounting
Removal
Figure 06
Figure 07
PHOENIX CONTACT page 5 of 9
Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
QUINT-DC-UPS
Power
Supply
+ –
AC
Input Output Battery
+ – + –
+ –
QUINT-BAT/24DC
Unbuffered
Load
+ –
–
DC +
Buffered
Load
–
DC +
Figure 08
5.4. Connection
The following cable cross sections can be connected:
Stranded
[mm2]
0.5 - 10
0.5 - 10
0.5 - 10
0.2 - 2.5
AWG
20 - 6
20 - 6
20 - 6
25 - 14
Torque
[Nm]
1.2 - 1.5
1.2 - 1.5
1.2 - 1.5
0.5 - 0.6
13
3 14 D
14O DC
C
OK
K ++
++
+2
4V
0,2
13
3 14 D
11 14 O DC
C
21OK
K +
31 + +
R1 +
l
For reliable and safe-to-touch
connections: Strip 10 mm (0.39 in.)
from the input and output side
connector ends and 7 mm (0.28 in.)
from the signal connector ends.
To maintain UL approvals, use copper cables, which
are designed for operating temperatures > +75°C
(+167°F). To meet GL requirements, unused terminal
compartments should be closed.
QUINT DC-UPS 40 A
A
12
13
11
Ala
23
32
33
21
Ba 3
Mo t.- 1
de Ba
Ch t.ar
ge
Fuse
Further device protection is not required, as an
internal fuse is present.
If the internal fuse is blown, this is
most probably due to a device fault.
In this case, the device should be
checked in the factory.
PHOENIX CONTACT page 6 of 9
m R2
ote
OF
ONF
–2
+
–
40
O A
ut
pu
t
2
U
F
COUIP
EQKA
43
D
TE
LIS
3
5
15 10
Ser
vice
≤3
,4
7,
≥1 2
2
+
–
IA
S
TR
AL
US OL T
OV INDNTRMEN
PR
AP
-2
0-6
00
61 81-1
EN 500
EN
5
L
rm
de
Mo e
t.- arg
Ba -Ch
t.
Ba
OK
In
r
we
Po
Ala
m
[m ax 0,5 1
in] ∞
30
Ba
t.-S
20
ele
c
[A t
h]
Ba
tte
r
+
5.5. Input (1, Figure 04, Figure 08)
The QUINT-DC-UPS is connected to the 24 V DC
output of the power supply via the "Input +" and
"Input -" terminal blocks. The output is isolated from the
input by the internal diode. The stored power is only
supplied to the output. The device is protected against
overcurrent and short circuit by an internal input fuse.
R1
Re
Ala
rm
B
Ba at.-M
t.-C o
ha de
rg
e
Po
we
r In
OK
t
D
In C 24
pu
t V
A
/40
/43 C
DC
/24 2 DC VD
PS 24 24V -30 0A
6
.5 /4
C-U8 6
22 DC
T-D 2
e: V
IN No.:
ag 24
olt
QU er°C
V
l
70 F
Ordut: ona
+ 58 °
Inperati
5…+1
Optput:
-2 …
3
Ou
-1
–
R2
22
rm
www.interface.phoenixcontact.com
1 Input:
2 Output:
3 Battery:
4
--8 Signal:
Solid
[mm2]
0.5 - 16
0.5 - 16
0.5 - 16
0.2 - 4
io
at
a ll g
s t tin
in nec
a d con
R e re
fo
be
n
in
st
ru
ct
io
ns
y
–
Figure 09
Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
The QUINT-DC-UPS is optimized for use with
QUINT-BAT/24DC type battery modules.
The following battery modules are recommended:
QUINT-BAT/24DC/3,4AH (Order No. 2866349)
QUINT-BAT/24DC/7,2AH (Order No. 2866352)
QUINT-BAT/24DC/12AH (Order No. 2866365)
When using QUINT-BAT/24DC/3,4AH, the maximum
output current of 25 A must not be exceeded.
Following successful installation, the capacity of the
connected battery module must be selected using the
"Battery module selection" rotary switch $.
12 Ah
7.2 Ah
3.4 Ah
30
60
90
Time [min.]
5.7. Battery Module
The battery module is connected to the
QUINT-DC-UPS via the "Battery +" and "Battery -"
terminal blocks. To interrupt the charge/discharge
current of the battery module, the "Battery module
selection" selector switch $ must be set to "Service".
The fuse on the battery module
must be removed when installing or
replacing the battery module.
40
35
30
25
20
15
10
5
0
Current [A]
5.6. Output
All devices that must be supplied without interruption
in the event of a supply voltage failure
("Buffered Load"), are connected to the "Output +" and
"Output -" terminal blocks of the DC output (Fig. 08). It
is recommended that all other loads, which do not
require buffering ("Unbuffered Load"), are connected to
the 24 V DC output of the power supply.
This increases the buffer time, as this time depends
on the output current (see Fig. 10). The internal diode
ensures that the buffered loads are isolated from the
unbuffered loads.
at. M
-C od
ha e
rg
e
Po
we
r In
OK
t
m
[m ax
V
40
O A
u
+ tput
–
5.8. Signaling Outputs
The signal outputs are connected via terminal blocks
11/12/13 4, 21/22/23 5 or 31/32/33 6. The contacts
are floating contacts. The plug-in bridge provided can
be used to supply +24 V to grouped contacts 11,21,31.
This means that N/C contacts 12,22,32 and N/O
contacts 13,23,33 can be evaluated as switching
outputs with 0 V and +24 V voltage levels.
PHOENIX CONTACT page 7 of 9
0,5 1
in] ∞
30
Ba
t.-S
2
ele 0
c
[A t
h]
2
Figure 10
O
PR
AP
U
IN NT
COUIP
EQKA
43
ED
ST
LI
3
5
15 10
Se
rvic
e
≤3
,4
7,2
≥1
2
$
R
be
Ba
+
de
Mo e
t.- harg
a
B -C
t.
K
Ba
nO
rI
e
w
Po
120
tte
ry
–
Figure 11
Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
5.9. Remote Shutdown ("Remote", Fig. 12)
The device has a UPS remote shutdown function for
specific shutdown.
Remote shutdown must be deactivated for the device
to switch to buffer mode in the event of a supply voltage
failure.
Remote Shutdown Off
• The "Remote shutdown R1" and "Remote
shutdown R2" terminal points are short circuited
(e.g., with a plug-in bridge) OR
The "Remote shutdown R2" terminal point is
supplied with a 24 V DC voltage
• The QUINT-DC-UPS switches to buffer mode in the
event of a supply voltage failure
13
3 14 D
14O DC
C
OK
K ++
++
V
0,2
13
3 14 D
11 14 O DC
C
21OK
K +
31 + +
R1 +
1
A
2
13
11
Al
ar
m
Remote Shutdown On
• The "Remote shutdown R1" and "Remote
shutdown R2" terminal points are not connected
• All LEDs are off
• The QUINT-DC-UPS does not switch to buffer mode
in the event of a supply voltage failure, instead the
device is shut down. When the supply voltage is
reapplied, the battery module is charged and the
device remains off until remote shutdown is
deactivated.
• Connected loads are supplied as long as the supply
voltage is present
23
32
33
21
Ba 3
Mo t.- 1
de Ba
Ch t.ar
ge
R1
Re
I
QUde
Or u
Inpe
Optp
Ou
m R2
ot
e
OF
ONF
Al
ar
m
Ba
Ba t.t.-CMo
ha de
rg
e
m
ar
Al
de
Mo e
t.- arg
Ba Ch
P
AP
U
Figure 12
6. Setting Options on the Device
(Fig. 13)
6.1. Buffer Time Setting
Buffer mode can be exited after a predefined time
has elapsed or by external
shutdown (see 6.9).
If the device is to be shut down after a specific time
has elapsed, the time can be set via the
selector switch § on the front of the device.
When the supply voltage is reapplied, the device
can switch to buffer mode again.
8
–
R2
22
rm
B
Ba at.M
t.-C o
ha de
rg
e
Po
we
r In
OK
t
ar
Al
de
Mo e
t.- harg
a
B -C
t.
K
Ba
nO
rI
e
w
Po
m
V
40
O A
ut
pu
t
[m ax 0,5 1
in] ∞
30
Ba
t.-S
2
ele 0
c
[A t
h]
2
3
5
15 10
Se
rvic
e
≤3
,4
7,2
≥1
2
+
6.2. Battery Module Setting
Before startup, the capacity of the battery module
used must be set on the device via the selector switch
$. When replacing the battery, the selector switch
must be set to "Service" (see also 6.7).
PHOENIX CONTACT page 8 of 9
–
m
§
$
Ba
+
tte
ry
–
Figure 13
Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
7. Method of Operation
In the event of a power failure at the output, the QUINT-DC-UPS supplies all connected devices with a 24 V DC
voltage without interruption at a load current up to 40 A. When the 24 V supply voltage is applied, the connected
battery module is charged. In the event of a supply voltage failure, the battery module is connected to the output,
and the stored power ensures that all connected devices continue to operate without interruption. The professional
signaling via function LEDs and floating PDT contacts enables reliable evaluation of all the main operating states.
7.1. Output Voltage
In normal operation, the QUINT-DC-UPS output voltage corresponds to the usual supply voltage. If the supply
voltage drops more than 1 V in the space of 0.1 seconds or falls below the minimum threshold of 22 V, the device
switches to buffer mode.
If the output voltage drops below 20.4 V in buffer mode, this is indicated by the Alarm indicator.
If the output voltage drops to 19.2 V because the battery module is flat, the device is shut down completely. When
the supply voltage is reapplied, the device automatically switches on again. The device is electronically
short-circuit-proof and idling-proof.
7.2. Signaling
Three floating PDT contacts and three indicators are provided for function monitoring.
Buffer mode
Battery module flat
- Battery module quality test negative
- No battery module
- Service
- Buffer time elapsed
- Remote shutdown activated
xx - xx: Contact closed,
1x Alarm,
2x Battery Mode,
x1 group contact,
x2 N/C contact,
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
3x Battery Charge
x3 N/O contact
Bat. Charge
6
31 - 33
Bat. Mode
5
21 - 22
Supply voltage OK,
battery module charged (normal operation)
31 - 32
21 - 22
Buffer mode
31 - 32
21 - 23
Key/Output
Supply voltage OK,
battery module charging
Alarm
4
Battery module flat
31 - 32
21 - 22
11 - 13
- Battery module quality test negative
- No battery module
- Service
- Buffer time elapsed
- Remote shutdown activated
31 - 32
21 - 22
11 - 13
21 - 22
11 - 13
7.3. Temperature Response
The charging rate of the connected battery module depends on the temperature.
7.4. Testing the Battery Module
A quality test is carried out on the battery module once a week and its presence is verified every minute.
A negative test result is indicated by the Alarm indicator.
PHOENIX CONTACT page 9 of 9
http://www.phoenixcontact.com
ON
TNR:101997-00-gb
Supply voltage OK,
battery module charged (normal operation)
Red 0
Alarm
OFF
05/01/05
Supply voltage OK,
battery module charging
Green "“
Yellow !
Power IN OK Bat. Mode/Charge
ON
Flashing
 PHOENIX CONTACT
Key/Indicators