MEMORY HiCORDER 8808-51 Recorders Instantaneous Analysis and Long-term Recording of Harmonic Waves for Maintenance of Commercial Power Systems Are the harmonics in your company's power lines in order? The 8808-51 is an economical tool that will clearly identify and analyze the current harmonic state of your power system. To the 8808- 01 MEMORY HiCORDER with their popular detachable printers, HIOKI has added the 8808-51 MEMORY HiCORDER with harmonic analysis function. Capable of both instantaneous analysis and time series recording of harmonics, this unit can measure and analyze harmonic current flowing into and out of a commercial power system, as well as harmonic components piggybacking on power line voltage. Instantaneous harmonic analysis • Can measure harmonics up to 40 orders from the fundamen-tal wave • Analysis display includes RMS value, content factor, phase angle, active power, and power phase angle for each order of harmonics (numeric and graphic display) • Analysis display of total RMS value, total distortion, active/ reactive/apparent power, and power factor (numeric display) • Bar graph and numeric data display • Power phase angle can be displayed as a vector Time series recording • Harmonic analysis of up to 20 items • Data recorded in time series • When analyzing four items simultaneously, data can be recorded for up to 150 days Flexible connection options • Supports independent channels, singlephase two-wire, single-phase three-wire, and three-phase three-wire • Full isolation of all analog channels Useful measurement functions • Connection check • Level check • Over-range function Waveform Direct read-out of current through general-purpose clamps Bar graph Numeric data Power vector • Compatible with HIOKI's 9018-50 and 9132- 50 CLAMP-ON PROBE This catalog is dedicated to featuring the harmonic wave analysis functions of Model 8808 -51, functions that are not included in the standard Model 8808 -01. As the waveform recording functions of Model 8808 -51 is identical to the Model 8808 -01, please refer to the catalog for the latter model for detailed descriptions. 2 Use the 8808-51 to determine the current - Harmonic Wave Functions Harmonic wave instantaneous analysis mode The 8808 -51 can analyze harmonic components (up to 40 orders from the fundamental wave) that are included in voltage and current in a power line with a base frequency of 45 to 65Hz. Based on the waveform that was captured, the 8808 51 can analyze the RMS value, content factor, phase angle, active power, and power phase angle for each order of harmonics. The measurement results can be displayed and recorded as a bar graph, numeric data, or power vector diagram. The 8808 -51 can also display numerically the total RMS value, the total distortion, the active/ reactive/apparent power, and power factor. ▲Captured waveform (waveform display screen) ▲RMS value of harmonic wave (bar graph) ▲Content factor of harmonic wave (numeric data) Time series analysis mode for continuous measurement of changes in harmonics This mode is used to continuously measure changes in the RMS value, content factor, phase angle, active power, and total distortion for each order of harmonics. Measurements are made at specific intervals and are displayed and recorded as a graph. Through long-term monitoring of the correlation between the timing of harmonic waves and their relationship to phenomena, the 8808 -51 become useful tools for finding the causes of harmonic interference and taking appropriate action. Time series graph display screen In time series recording mode, the 8808 -51 is capable of recordi ng up to 20 ha r mon ic wave a na lysis items simultaneously. The recording time can be set over a range of 30 minutes to 150 days and the data is stored in internal memory. If "continuous" is set as the recording time, the 8808 -51 is able to draw a continuous graph on recording paper. Only the measurements for the last 60 divisions are stored in internal memory. Harmonic analysis item settings ▲Time series analysis printout example This time series graph shows four of the analysis items that were recorded. 3 state of harmonic waves Harmonic wave power measurement on single-phase two-wire, single-phase three-wire*, and three-phase three-wire* lines Determine the direction of flow of harmonic waves Power vector diagram Power content factor (bar graph) The 8808-51 allow you to input voltage on channels 1 and 3 and current on channels 2 and 4 (through the clamp-on probe) and then display a power vector diagram for each harmonic wave. This diagram can then be used to determine whether the harmonic waves are flowing from the power supply system or from the load. The 8808 -51 is capable of measurement of single-phase threewire, dual single-phase two-wire, and three-phase three-wire lines. This unit can display numeric data or a graphs for the active power, active power content factor, and power phase angle for each order of harmonics. Because all analog input channels are isolated, no problems are encountered when measuring two different single-phase twowire systems simultaneously, or if connections are made incorrectly. - Product Specifications - Note: The waveform recording functions of the 8808-51 MEMORY HiCORDER is identical to the 8808-01 MEMORY HiCORDER. For details on specifications other than those concerning the harmonic wave analysis functions, refer to the catalog for the 8808-01 MEMORY HiCORDER. Instantaneous analysis mode General specifications for the harmonic wave analysis section Connection types Input settings Independent channels: Voltage, 9018, 9132, 3283, 3284, 3285, 9322 Other connections: Possible with even channels set to voltage and odd channels set to current. When measuring power, the following conditions must be met: (1) The input type on the channel used for measuring current must be set to 9018 or 9132. (2) The input type on the channel used for measuring current must be set to voltage with current scaling. (The clamp probe that is used must have good phase accuracy.) Fundamental frequency range 45Hz to 65Hz Automatic setting or manual setting (0.1Hz resolution) Number of orders for analysis Fundamental wave to 40th order Analysis frequency band 45Hz to 2.6kHz (on "×1" display) Fundamental wave to 20th order: ±3.5˚ 21st order to 40th order: ±7.5˚ (with content factor of 10%) Phase accuracy*3 Fundamental wave to 20th order: ±3.5˚ 21st order to 40th order: ±7.5˚ (with content factor of 10%) Amplitude accuracy*3 *3 When using a clamp-on probe, add the accuracy of the probe. Number of FFT operations 512 points (sampled during one cycle of the fundamental wave) Vertical axis enlargement/ compression For any harmonic wave order number: RMS value/content factor/ phase angle/active power*4/active power content factor*4/power phase angle*4 Total RMS value, total distortion-F*5, total distortion-R*6, active power*4, apparent power*4, reactive power*4, power factor*4 Supplemental functions When using a HIOKI Clamp-on probe, the current value can be read directly, and can be set as desired. Wiring and level check functions Measurement target auto range function, checking for reversed wiring, determination of phase sequence for threephase, three-wire connection Over-range function Automatically lowers the range sensitivity if the input range is exceeded while taking measurements. Tabulated results output Miscellaneous Trigger mode Sources Recording time (Time series analysis mode only) Cursor measurement, screen scrolling Single, repeat Permits selection of up to four types of harmonic wave triggers; trigger conditions can be set for each type of trigger. (Harmonic wave trigger sources are ORed together, while harmonic wave triggers are ANDed with external triggers and timer triggers.) Free-run operation when all triggers are OFF. Trigger types RMS value/content factor/active power value/power phase angle/total RMS value/total distortion-R/total distortion-F of any harmonic wave Miscellaneous Pre-trigger: 0, 5, 10 DIV. (time series analysis mode) Trigger timing: start only Harmonic wave analysis function recording time*1 Time axis * Only when single-phase two-wire, single-phase three-wire, or three-phase threewire is selected. *5 Ratio of all harmonic waves to fundamental wave *6 Ratio of all harmonic waves to total RMS value Time axis Can output a list of maximum and minimum values for the results of each analysis across all recording times. Harmonic wave trigger function 4 Number of simultaneous analyses Six levels of enlargement, from ×2 to ×100; one level of compression, to 1/2; logarithmic scale Scaling Scaling, cursor measurement, wiring and level check function Time series analysis mode Analysis types *4 Only when single-phase two-wire, single-phase three-wire, or three-phase three-wire is selected. *5 Ratio of all harmonic waves to fundamental wave *6 Ratio of all harmonic waves to total RMS value Analog 12 bits × 16 kwords/channel Harmonic waveform 32 bits × 96 kwords operation memory capacity Function Analysis types *3 When using a clamp-on probe, add the accuracy of the probe. Sampling frequency 400kS/s fixed Waveform memory capacity Numeric data + graph: harmonic wave RMS value, harmonic wave content factor, harmonic wave phase angle, harmonic wave active power*4, harmonic wave active power content factor*4, harmonic wave power phase angle*4 Numeric data only: Total RMS value, total distortion-F*5, total distortion-R*6, active power*4, apparent power*4, reactive power*4, power factor*4 Independent channels, single-phase two-wire*1, singlephase three-wire, and three-phase three-wire *1 8808-51 permits simultaneous analysis of two systems 5 min./DIV Storage in internal memory (Number of analysis items is reduced depending on recording length) 5 hours (20 items) to 1 day (4 items) Up to 20 analyses (any combination); only four can be simultaneously displayed or printed 10 min./DIV 10 hours (20 items) to 2 days (4 items) Depends on time axis and number of simultaneous analyses 3 hour./DIV 7 days (20 items) to 37 days (4 items) 30 min./DIV 1 day (20 items) to 6 days (4 items) 5 minutes/12 hours/DIV, 7 ranges (80 samples/DIV) Printing types Dotted line graph or numerical data for each analysis value (time display) Enlargement/ compression Vertical axis: Six levels of enlargement, from ×2 to ×100; one level of compression, to 1/2; logarithmic scale Time axis: Two levels of enlargement, ×2 or ×4; six levels of compression, from 1/2 to 1/48 1 hour./DIV 2 days (20 items) to 12 days (4 items) 6 hour./DIV 14 days (20 items) to 75 days (4 items) 12 hour./DIV 30 days (20 items) to 150 days (4 items) *1 *2 *3 *4 Printing on paper without recording in memory *2 (Final 60 DIV are recorded in internal memory.) 6 days + 3.5 hours (4 items) 12 days + 7 hours (4 items) 36 days + 21 hours (4 items) 73 days + 18 hours (4 items) 221 days + 6 hours (4 items) 1 year + 77 days (4 items) *3, *4 2 years + 155 days (4 items) *3, *4 For the paper length, it is assumed that 1770 DIV will not use more than 30cm of paper. Only a maximum of four items can be printed on paper. One year is assumed to be 365 days. The recording times shown in the table are simply the calculated values. If measurements are taken over several years, wear on the equipment will begin to have an effect. Therefore, operation cannot be guaranteed. 4 RMS voltage n mine in operatio Power phase g a certa it possible to deter 8 -51 can n ri u d s e 0 Center is 0˚; within ±90˚ ns in valu one month makes Y HiCORDER 88 ent factor, nt fluctuatio r R indicates harmonic waves Analy zing e day, one week, o etc. The MEMO the RMS value, co Fluctuations flowing in; outside of n as o onics. tortion, cluding so ±90˚ indicates harmonic cycle, such total harmonic dis up to 20 items, in each order of harm Of course it is al . f r h o ce p fo n s waves flowing out. the cause y measure and gra nd total distortion n be seen at a gla cycle. a sl Third-order harmonic wave content continuou gle, active power, ch of the values ca during one waveform factor and total distortion of voltage phase an elations among ea antaneous values and corr le to analyze inst ■ Harmonic wave time series recording example Each order can be graphed. ib ss o p This graph shows that harmonic waves begin to decrease at 4:00 p.m., and then begin to increase at 6:30 a.m. the next morning. e ra ln e g s a d s, ■ Abnormal waveform n se io u ct e n b fu ls o le to 1 can a ful trigger recording example R 8 8 0 8 -5 uipped with power igger, they are ab dition E D R O This waveform was recorded in O RY H iC nit is eq e drop tr vels. In ad response to the voltage drop trigger. T h e M E M Because each u igger and a voltag ysis of waveform le of supply voltage the sters. input ion tr n anal Transient drops in voltage on a power purpose te eform discriminat d permit on-scree cept and measure combination with with line can be monitored through the wav , an d in ly ac ion such as a er line abnormalities nits can also direct current when use used in combinat ith a waveform. w en ow leak eu h p ed w es p re re th ip es su u tu , p lin ea es eq V m ca test 600 units are d 240V lin sfer 8 -51 can to 100V an 0V line. The 880 ER 3283, and can on, because both e unit and then tran from a 40 N LEAK HiTEST BE 9322. In additi rement data in th CL AMP-O FERENTIAL PRO ible to store measu the DIF rd slot, it is poss PC ca a PC. the data to ■ Example of data analysis on a personal computer Data stored in text format in a PC card can be loaded directly into spreadsheet software on a PC. If the data is in binary format, it must first be converted into text format. Configuration of options Note: Product names appearing herein are trademarks or registered trademarks of various companies. Removable storage (CF card) PC Software Supplied with PC Card adapter CARRYING CASE 9391 Soft case type, for storing options. Holds more options than the 9648 hard case. CARRYING CASE 9648 Hard case type, for storing options WAVE PROCESSOR 9335 4-channel type, for voltage/ contact signal ON/OFF detection (response time 0.5 μsec, miniature terminal type) ................ Cannot be used PC Card Precaution RS-232C CABLE 9612 CONVERSION CABLE 9323 LOGIC PROBE 9320-01 PC CARD 2G 9830 Convert data, print and display waveforms. Windows 2000/XP/Vista (32-bit), Windows 7 (32-bit/64-bit) LOGIC PROBE 9321-01 4 isolated channels, ON/ OFF detection of AC/ DC voltage (miniature terminal type) Used for connecting the 9320/9321 and 8808 series MEMORY HiCORDERs, because the terminal shapes are different. * This cable is not required for the small-terminal types 9327, 9320-01, and 9321-01. Mini DIN 9-pin - Dsub 9-pin, Cable length 1.5 m (4.92 ft) length. Voltage measurement Recommended Use only PC Cards sold by HIOKI. Compatibility and performance are not guaranteed for PC cards made by other manufacturers. You may be unable to read from or save data to such cards. Input cable for measurement use is not provided. Please purchase the optional cable. ALLIGATOR CLIP 9790-01 Red/black set attaches to the ends of test leads (9790) GRABBER CLIP 9790-02 Red/black set attaches to the ends of test leads (9790) CONNECTION CORD 9790 Voltage MEMROY HiCORDER 8808 -51 (4ch model) An The units can be operated using the supplied LR6/AA alkaline batteries but use of the optional AC ADAPTER 9418-15 or BATTERY PACK 9447 (the AC ADAPTER 9418-15 is necessary for recharging) is recommended. Manganese batteries cannot be used. Use of commercially available rechargeable batteries instead of the original battery pack may result in damage to the unit. (Thin Type) CAT II 300 V, ultraflexible 2.8 mm (0.11 in) diameter test lead cable, 1.5 m (4.92 ft) length Note: Attachment clips sold separately. CONNECTION CORD 9198 CONNECTION CORD 9197 For low voltage (up to 300 V), For high voltage (up to 500 V), 1.7 m (5.58 ft) length 1.8 m (5.91 ft) length High-Voltage measurement For up to 2 kV DC or 1 kV AC. Use with the AC Adapter 941815, for power supply. RECORDING PAPER 9234 112 mm (4.41 in) × 18 m (59.06 ft), 10 rolls set BATTERY PACK 9447 7.2 V, 2400 mAh Recommended CLAMP ON PROBE 9018 -50 Enables observation of AC current waveforms. Input: 40 Hz to 3 kHz, selectable 10 to 500 A ranges, Output: 0.2 V AC/ range CLAMP ON PROBE 9132-50 Enables observation of AC current waveforms. Input: 40 Hz to 1 kHz, selectable 20 to 1000 A ranges, Output: 0.2 V AC/ range CLAMP ON LEAK HiTESTER 3283 For leakage current measurement, includes 10 mA to 200 A ranges, with analog output of 1 V f.s. DC, and waveform monitor output of 1 V f.s. AC at 40 Hz to 2 kHz. Requires the AC adapter 9445-02/-03 For powering Differential probe 9322, 100 to 240 V AC. With the 3283, continuous use. For USA, Canada: 944502, For EU: 9445-03. OUTPUT CORD 9094 Required along with the 9199 adapter to connect the 3283 to the 8808 series. CONVERSION ADAPTER 9199 Insulation transformer, 400V or 200V AC input, 10V AC output, for AC power line measurement. Required along with the Conversion Adapter 9199. Banana-to-BNC, use to connect to BNC terminal on Input Module CONNECTION CORD 9217 Not CE marked CHARGE STAND 9643 Independent of the 8808 series main unit, use with the AC ADAPTER 9418-15 to charge one Model 9447. HIOKI (Shanghai) Sales & Trading Co., Ltd. : HIOKI USA CORPORATION : 6 Corporate Drive, Cranbury, NJ 08512 USA TEL +1-609-409-9109 / FAX +1-609-409-9108 http://www.hiokiusa.com / E-mail: [email protected] .......... (256 MB capacity) Current measurement *50/60 Hz line use PT 9303 1608-1610 Shanghai Times Square Office, 93 Huai Hai Zhong Road, Shanghai, P.R.China POSTCODE: 200021 TEL +86-21-6391-0090/0092 FAX +86-21-6391-0360 http://www.hioki.cn / E-mail: [email protected] HEAD OFFICE : 81 Koizumi, Ueda, Nagano, 386-1192, Japan TEL +81-268-28-0562 / FAX +81-268-28-0568 http://www.hioki.co.jp / E-mail: [email protected] .......... (512 MB capacity) PC CARD 256M 9727 Not CE marked Universal 100 to 240 V AC, 12 V DC/ 2.5 A output PAPER WINDER 220H Paper width: 70 to 220 mm (2.76 to 8.66 in), using special-purpose AC adapter ............... (1 GB capacity) PC CARD 512M 9728 AC ADAPTER 9445 -02/-03 AC ADAPTER 9418-15 Not CE marked for use with power supply AC ADAPTER 9418-15 DIFFERENTIAL PROBE 9322 PRINTER UNIT 8992 Printing width 100 mm (3.94 in), used together with the 8808-51 main body CONTACT PIN 9790-03 Red/black set attaches to the ends of test leads (9790) PC CARD 1G 9729 Cord has insulated BNC connectors at both ends, and connects to insulated BNC connectors on input terminal. 1.7 m (5.58 ft) length. LINE SPLITTER CT101A For 100 V/ 15 A, convenient for measuring 100 V AC line current with clamp-on probe DISTRIBUTED BY Beijing Office : TEL +86-10-5867-4080/4081 FAX +86-10-5867-4090 E-mail: [email protected] Guangzhou Office : TEL +86-20-38392673/2676 FAX +86-20-38392679 E-mail: [email protected] HIOKI INDIA PRIVATE LIMITED : Khandela House, 24 Gulmohar Colony Indore 452 018 (M.P.), India TEL +91-731-4223901, 4223902 FAX +91-731-4223903 http://www.hioki.in / E-mail: [email protected] All information correct as of Jun. 30, 2010. All specifications are subject to change without notice. 8808-51E8-06E-00KR Printed in Korea