TEMPERATURE HiTESTER 3441/3442/3446-01/3447-01

TEMPERATURE HiTESTER
3441/3442/3446-01/3447-01
Environmental Measuring Instruments
● 3447-01
-01 for HACCP Temperature
Recording/Management
- Compatible with Platinum temperature-measurement resistors (Pt 100) (-100˚C to 300˚C)
- Waterproof construction (IP67), 2-channel measurement
- Accommodates a temperature probe with hand switch
- Record temperature, time, and name of measurement object
- Record using either interval (28,800 data items) or manual (7,200 data items)
recording modes
● 3446-01
-01 For TemperatureRecording/Management
in Energy Conservation Applications
- 1-channel recording for use with Thermocouple (Type K) sensors (-100 C to 1000 C*)
3447
● 3442(-03)
(-03) With Water-resistant Construction
for Use in Damp Environments
3442
- Use with Thermocouple (Type K) sensor with water-resistant construction (-100˚C to 1300˚C*)
- Max/min temperature recording
● 3441(-02) Basic Temperature HiTESTER
- Thermocouple (Type K) sensor (-100˚C to 1300˚C*)
- A choice of temperature sensors for different applications
* Measurable temperature range varies
according to temperature sensor type.
2
Temperature Management of Food Preparation and
■ 3446-01, 3447-01 Record data and memos using either manual or interval recording mode
3447-01 has waterproof construction in both thermometer
and sensor.
2-channel Class A temperature measurement using a
platinum temperature-measurement resistor.
Single-channel recording with 3446 -01 using type K
thermocouple (-100˚C to 1000˚C).
Both provide two recording modes, manual and interval,
allowing recording at arbitrary times or at set intervals.
Records product name and inspector name or pass/fail result
along with temperature.
Send data to a computer by RS-232C connection.
Print recorded data (using the optional Printer 9670)
Screen Display
*1 Maximum recording time in interval recording mode
➀
➄
Note that the amount of continuous recording time available may be limited by remaining
battery charge.
➁
➅
Interval 1 sec
➂
When using only interval recording, the relationship between recording interval and maximum
recording time are as shown below:
Recording Time Interval Recording Time Interval
8 h
15 sec
5 days
1 min
2 sec
16 h
10 sec
3 days, 8 h 5 sec
20 sec
1 days, 6 h 30 sec
6 days 16 h 2 min
10 days
5 min
10 min
Recording Time Interval
20 days 15 min
Recording Time
300 days
100 days 30 min
600 days
40 days
20 min
200 days 60 min
400 days
➇
➈
➃
1200 days
■3447-01 Measurement Specifications
Sensor type
Measurement current
No. of inputs
Measurement range
Resolution
Measurement accuracy,
thermometer
Sampling rate
Water resistance
➆
➀REC: recording
➁INTVL: Interval recording mode, recording
interval
➂ Time display
➃ Channel number being recorded (3447-01)
➄APS:auto power save function ON and battery
charge remaining display
➅ITEM/ID: Product name/name of inspector
➆Memo, such as product name
➇Data number
➈ Temperature display
■3446-01 Measurement Specifications
: Platinum temperature-measurement resistor Pt 100 (3 line type)
: 0.5 mA
: 2 channel
: -100.0 to 300.0˚C
: 0.1˚C
: ±0.1% rdg. ±0.4˚C
Sensor type
Resolution
: 0.1˚C (-100.0 to 300.0˚C), 1˚C (-100 to 1000˚C)
: 1/second
: IP67 (EN60529:1991)
Sampling rate
: 1/second
No. of inputs
: Type K thermocouple
: 1 channel
Measurement range : -100 to 1000˚C
Measurement accuracy : ±0.1% rdg. ±0.5˚C (with 0.1˚C resolution)
±0.2% rdg. ±1˚C (with 1˚C resolution)
■ 3446-01 / 3447-01 Common Specifications
Measurement Modes
Manual recording : Temperature recording by key operation
(Recording also possible by the key on the 9479 Probe. 3447-01 only)
Data recorded : Time, temperature, item, ID, comparator test result
Data items recorded : Max 7,200 (for the 3447-01: 4,800 with 2-ch recording)
Interval recording : Measurement values recorded at a set interval
Data recorded : Time, temperature, item, ID, comparator test result
Data items recorded : Max 28,800 (with the 3447, 14,400 with 2-ch recording)
Recording interval : OFF, 1, 2, 5, 10, 15, 20, or 30 seconds,
1, 2, 5, 10, 15, 20, 30, or 60 minutes
Display
*Manual recording when set to OFF
LCD display : Measured temperature, date, time, item, ID, etc.
Item display : 12 character (alphanumeric) item display, holds up to 300 entries
ID display : 12 character (alphanumeric), holds up to 100 entries
* Item and ID settings can be made from a computer using the 9674 PC software.
Functions
Comparator : Set for individual items (Hi, IN, Lo evaluation)
Result output : Result display, buzzer output
Clock : Real time control (year, month, day, hour, minute, second)
Data read-out : Measurement data, time, data number
Display hold : Holds measurement value.
Auto power save : Automatically switches the power off if no key is pressed for 10
minutes. Display automatically turned off during interval recording.
* Auto power save function can be disabled.
Data back-up : Measurement data, Setting data
Interface : RS-232C (using dedicated cable)
Applicable standards : Safety, EN61010-1:2001; Measurement category I,
Pollution degree 2/EMC, EN613260:1997+A1:1998+A2:2001
Ambient conditions
for use : 0 to 40˚C, 80% rh or less (non-condensating)
for storage : -10 to 50˚C, 80% rh or less (non-condensating)
Power supply : 4 LR03 (AAA) alkaline dry cell batteries
Maximum rated power : 60 mVA
Continuous use time : 15 days (at 20˚C, with auto power save disabled)
1 month (at 20˚C, using auto power save, with a recording interval of 1 min)
Dimensions/mass : Approx. 66 x 150 x 31.5 mm (2.6 x 5.9 x 1.25 in), approx. 240 g (8.47 ozs)
Accessories : Batteries, strap band
Storage, Support for Electronic Device Temperation Control
■ Settings can be made from and data transferred to a connected computer
When a PC is connected to the 3446-01/3447-01, it
can be used to make various settings (item, ID,
comparator), or to store recorded data transferred
from the Temperature HiTESTER. Computerization
of temperature management can greatly increase
work efficiency.
The optional RS-232C Package 9674 is used for PC
communications.
RS-232C Package 9674 (Optional)
(Package contents: RS-232C cable, PC software on CD-ROM)
RS-232C cable (cable length: 2 m; Connector on PC side: Dsub-9 pin;
Connector on thermometer side: Dedicated connector)
PC software (Windows 95/98/Me/NT 4.0/2000/XP compatible)
Functions: Item/ID setting, comparator setting, data list display, graph
display, printing, file storage (in proprietary format or text format)
Printer 9670
When outputting recorded data
to the optional Printer 9670, use
the RS-232C cable provided in
the RS-232C Package 9674 and
a commercially-available
connector adapter (male Dsub-9
pin <-> male Dsub-25 pin).
■3441/3442 Extended Operation, Max/Min Temperature Recording, Water-resistant Construction (3442 only)
Recording of maximum temperature and minimum
temperature
Current temperature display
▲
▲
The 3442 has a water-resistant
construction.
Measurement in damp
environments is possible by using
the thermometer in combination
with the 9472 or 9475
temperature probe.
Choose from 9 different
temperature sensors (optional),
according to your application.
MAX display
MIN display
The 3441 and 3442 support temperature management by recording maximum and
minimum temperatures in memory. By pressing the MAX/MIN key, you can switch
to display of the current maximum and minimum temperatures at any time.
■3441/3442 Specifications (accuracy at 23˚C ±5˚C, 80% rh or less)
Sensor
: Type K thermocouple
Measurement range : -100˚C to 1300˚C (-148˚F to 2372˚F)
Resolution
: 0.1˚C (100 to 199. 9˚C), 1˚C (200 to 1300˚C)/
0.1˚F (-148˚F to 392˚F), 1˚F (393˚F to 2372˚F)
Measurement accuracy : ±0.1% rdg. ±0.8˚C (from -100 to 199.9˚C)/
±0.1% rdg. ±1.5˚F (-148˚F to 392˚F)
±0.2% rdg. ±1˚C (from 200 to 1300˚C)/±0.2% rdg. ±1.8˚F
(393˚F to 2372˚F)
(Accuracy of temperature sensor is added.)
Temperature coefficient : 0.03˚C/˚C (from -100 to 199.9˚C) / 0.054˚F/˚F (-148˚F to 392˚F)
0.05˚C/˚C (from 200 to 1300˚C) / 0.09˚F/˚F (393˚F to 2372˚F)
Sampling rate
: 2 / second
Display
: LCD display
Reference contact compensation : Automatic
Functions
: Max/Min temperature recording and display, display data hold, sensor
discontinuity display (- - - - ), over-range display (O.F, - O.F), auto power
save (operates after 30 min, can be disabled), low battery warning
Operating environment : Indoors, at altitude up to 2000 m
Ambient conditions
for use : 0 to 40˚C (32˚F to 104˚F), 80% rh or less (non-condensating)
for storage : -10 to 50˚C (14˚F to 122˚F), 80% rh or less (non-condensating)
Applicable standards : Safety, EN61010-1:2001; Measurement category I,
Pollution degree 2/EMC, EN613260:1997+A1:1998+A2:2001
Water-resistant construction: EN60529:1991 IP54
: 4 R6P manganese dry cell batteries or 4 LR6 alkaline
Power supply
batteries (AAA)
Maximum rated power : 35 mVA
Continuous operating : 200 hours or more (using manganese batteries)
Dimensions/mas : Approx. 74(W) x 155(H) x 24(D) mm (2.6 x 5.9 x 0.95 in),
approx. 160g (5.6 oz) (not including batteries or sensor)
: Batteries, strap band
Accessories
3
4
■ Choose from a wide range of temperature sensors for various applications (optional)
■ TEMPERATURE PROBE for 3441 / 3442
unit=mm (inch)
●:water--resistant structure
9472 / 9473 SHEATH TYPE
9474 / 9475 SHEATH TYPE
9180 / 9183 SHEATH TYPE
9182 SHEATH TYPE
9181 SURFACE TYPE
9476 SURFACE TYPE
Related Products
■ TEMPERATURE PROBE for 3446-01
9472-50 / 9473-50 SHEATH TYPE
9476-50 SURFACE TYPE
Management of temperature recordings
The 3412 -50 produces a
voltage output of 1 mV per
degree Centigrade.Using the
thermometer and recorder
together allows recording of
temperature variations.
■ TEMPERATURE PROBE for 3447-01
●:waterproof structure
9479 SHEATH TYPE with Hand Switch
9478 SHEATH TYPE
* The CE marking does not pertain to
the waterproof structure. Also, the
recorder, 9036 AC adapter, 9094
output cord, and temperature probes
are optional.
Range: –50˚C to 999˚C ( – 58 to 1830 ˚ F) , Sensor :
Thermocouple K (CA), Unit accuracy: ±0.2% f.s.±1dgt.
Analog output: 1mV / ˚C, Power supply: 6F22 battery
TEMPERATURE HiTESTER 3412-50
waterproof structure
water-resistant structure
Item
Thermocouple material
Tolerance
Response (90%)*
Size of Sheath
Cable
Grip heat resistance
Max use temperature
9472 (-50)
9473 (-50)
9474
9475
9183
9180
K type (Chromel/Almel)
The greater of ±1.5˚C(2.7˚F) or ±0.4% of measured temperature
About 5 sec About 10 sec About 5 sec About 10 sec
About 5 sec
φ2.3×150mm φ4.8×300mm φ2.3×100mm φ4.8×100mm
φ3.2×150 mm
General use (–20˚C to 90˚C,– 4˚F to 194˚F) 1 m
150˚C
80˚C
–100~300˚C
0~800˚C
–100~300˚C –100~500˚C
–50~750˚C
–148~572˚F
32~1472˚F
–148~572˚F –148~932˚F
–58~1382˚F
* Sheath type: Responsiveness in ice water at 0˚C (32˚F) and in boiling water at 100˚C(212˚F)
Surface type: Responsiveness on a metal surface at 0˚C (32˚F) and at 100˚C(212˚F)
TEMPERATURE HiTESTER 3446-01
TEMPERATURE HiTESTER 3447-01
■ Options for 3446-01, 3447-01
RS-232C PACKAGE (with PC Software)
CARRYING CASE
SHEATH TYPE TEMPERATURE PROBE
SHEATH TYPE TEMPERATURE PROBE
SURFACE TYPE TEMPERATURE PROBE
SHEATH TYPE TEMPERATURE PROBE
SHEATH TYPE TEMPERATURE PROBE
PRINTER (with 1 roll of Recording Paper)
AC ADAPTER for 9670
RECORDING PAPER
(for 9670, 80mm × 25m, 4 rolls)
9674
9386-01
9472-50
9473-50
9476-50
9478
9479
9670
9671
9237
The greater of ±2.5˚C(4.5˚F) *2
About 3 sec
φ20 mm
φ15 mm
80˚C
–40~500˚C
–40~932˚F
150˚C
–50~400˚C
–58~752˚F
9182
About 5 sec
φ3.2×500mm
(0˚C~150˚C) 2m
90˚C
–50~750˚C
–58~1382˚F
9478
9479
Pt 100(3-wires)*1
± 0.15˚C ±0.002 T*3
About 5 sec
φ2.3×100 mm
(– 40˚C~120˚C) 1m
80˚C
–100~300˚C
–148~572˚F
TEMPERATURE HiTESTER 3441 ( ˚C only)
TEMPERATURE HiTESTER 3441-02 ( ˚C/ ˚F selectable)
TEMPERATURE HiTESTER 3442 ( ˚C only)
TEMPERATURE HiTESTER 3442-03 ( ˚C/ ˚F selectable)
■ Options for 3441(-02), 3442(-03)
SHEATH TYPE TEMPERATURE PROBE
SURFACE TYPE TEMPERATURE PROBE
SHEATH TYPE TEMPERATURE PROBE
SHEATH TYPE TEMPERATURE PROBE
SHEATH TYPE TEMPERATURE PROBE
SHEATH TYPE TEMPERATURE PROBE
SHEATH TYPE TEMPERATURE PROBE
SHEATH TYPE TEMPERATURE PROBE
SURFACE TYPE TEMPERATURE PROBE
CARRYING CASE
1608-1610 Shanghai Times Square Office, 93 Huai Hai Zhong
Road, Shanghai, P.R.China POSTCODE: 200021
TEL +86-21-6391-0090/0092 FAX +86-21-6391-0360
E-mail: [email protected]
HIOKI USA CORPORATION :
6 Corporate Drive, Cranbury, NJ 08512 USA
TEL +1-609-409-9109 / FAX +1-609-409-9108
E-mail: [email protected]
9181
*1 Platinum Temperature-measurement Resistor
*2 9180, 9182: The greater of ±2.5˚C(4.5˚F ) or ±0.75% of measured temperature
9476: (–0.03 ×T)˚C to + 2.5˚C at 100˚C<(T–Ts)
9181: (–0.035×T)˚C to + 2.5˚C at 100˚C<(T–Ts)
T: measured temperature, Ts: environmental temperature
*3 T: measured temperature
HIOKI (Shanghai) Sales & Trading Co., Ltd. :
HEAD OFFICE :
81 Koizumi, Ueda, Nagano, 386-1192, Japan
TEL +81-268-28-0562 / FAX +81-268-28-0568
E-mail: [email protected]
9476 (-50)
9180
9181
9182
9183
9472
9473
9474
9475
9476
9386
DISTRIBUTED BY
Beijing Office :
A-2602 Freetown, 58 Dong San Huan Nan Road
Beijing, P.R.China POSTCODE: 100022
TEL +86-10-5867-4080/4081 FAX +86-10-5867-4090
E-mail: [email protected]
Guangzhou Office :
Room 303, Profit Plaza, No.76, West Huangpu Road
Guangzhou, P.R.China POSTCODE: 510623
TEL +86-20-38392673/2676 FAX +86-20-38392679
E-mail: [email protected]
All information correct as of Sep. 25, 2008. All specifications are subject to change without notice.
3441-3447SE5-89E
Printed in Japan