ASM-SENSOR 3258

SAFETY HiTESTER 3258
Field Measuring Instruments
Safely Measure Voltage Breaker Panels
■ New Technology
■ Safety
Measure voltage on insulated
electric cables
Measure safely around metal
busbars and terminals
■ Applicability
Optimized for 30-600 V AC
Measurable electrical cable: 38 mm2 or
larger insulated wires (100 mm2 or larger
recommended)
CAT IV 600V
2
HIOKI's new technology enhances voltage measurement safety
Development of the SAFETY HiTESTER 3258 opens the door to a new realm of safety by accurately
measuring non-destructively through wire insulation, a particular safety concern to those who maintain and
inspect electrical facilities
Safe Probe Heads
True RMS values on large, crystal-clear display
Data Hold Indicator
Shows when data is being held
(HOLD button pressed)
APS Indicator (Auto Power Shutoff)
The HiTESTER automatically shuts off when 10
minutes have elapsed from the last operation (can
be disabled)
AC Indicator
Low Battery Indicator
Reliably safe, non-metallic resin heads
Measured Value
Voltage Unit
Indicator
True RMS values retain accuracy despite waveform distortion
Voltage Detector
Power Button
Safety Barrier
Easy operation and informative display
1. Hot line check
Applicable electric cable types
Size: 38 mm2 or larger insulated electric line
(100 mm2 or larger recommended)
The HOLD lamp flashes when an energized line (at least 30 V AC) is detected.
Hot Line
Indicator
2. Measured value
Actual-size cross sections
When the display has stabilized, the HOLD lamp lights and the measured value is
displayed.
Measured
Value
38 mm2 (11.5 mm dia.) insulated cable
3. Hold measured value
Press the HOLD button to temporarily freeze the displayed value.
100 mm2 (17 mm dia.) insulated cable
Measurement
Hold
Lamp turns off
3
■ Ensures safe measurements in the cubicle
Point 1
Point 2
Easily measure right through cable insulation Safely measure around busbars
Also safe for metallic conductors
Actual size
Long grip for better safety
Safely measure 380-480 V AC lines
■ Get accurate measurements easily
The HiTESTER measures the voltage between two probes. To ensure accurate measurements, apply the
voltage detector probes perpendicular to the object to be measured.
To measure voltage to ground, apply one probe to a ground conductor.
Apply each voltage detector probe perpendicular to
the object to be measured.
Conductor
Conductor
Conductor
✕ Incorrect measurement
Conductor
Correct measurement method
✕
Conductor
4
❏ HiTESTER 3258 measurement principle
Measurements with traditional non-metallic-contact voltmeters and phase detectors
depend on the coupling capacitance (C1 and C2) between voltage detector electrodes in
the probe tips and the measurement objects. That voltage detection method can present
problems due to the dependence of the coupling capacitance on the material properties
of the measurement objects, making accurate voltage determination (Vm = Vm2 - Vm1)
problematic.
The SAFETY HiTESTER 3258 employs a new technological principle to detect
accurate measurement voltage (Vm) independent of coupling capacitance.
■ Model 3258 Specifications (accuracy guaranteed for one year at 23 ±5°C and 80% RH or less)
Measurement parameter
Measurement objects
Measurement values
Max. rated voltage to earth
Insulated electric lines (Indoor PVC or equivalent, 100 mm2 or larger),
metal conductors
Note: Not suitable for shielded cables
True RMS display
600 Vrms AC
Crest factor 1.8 (sine wave only at 600 V range)
Circuit dynamics
Temp. characteristics
Effect of conductor diameter
Effect of nearby conductors
Effect of external magnetic field
0.05% rdg./°C
0.5% rdg. (add to measurement accuracy for 38 to 100 mm2 insulated cables)
±5% rdg. or less
none
4200 counts, with less than 10 counts zero-suppressed
Display
Display refresh rate
Display response time
Approx. once every 0.6 seconds
2.4 s or less
Data Hold, Auto Power Shutoff, Low-Battery Warning
Functions
Operating temp. & humidity
Storage temp. & humidity
Operating environment
Applicable standards
0 to 40°C, 80% RH or less, non-condensating
-10 to 50°C, 80% RH or less, non-condensating
Indoors, up to 2000 m ASL
Safety: EN61010, EMC: EN61326
Six AA (LR6) alkaline batteries
Max. operating time: approx. 14 h (power on, no input),
or the equivalent of 1000 one-minute operations or 200 five-minute operations
Power source
Max. rated power
Size and weight
AC voltage (AC potential bridge)
2 VA
51W(2.01") × 275H(10.83") × 37.5D(1.48") mm (per probe),
Cable length: 900 mm (35.43"), 670 g (23.6 oz.) (including batteries)
AC Voltage Measurement Accuracy (on insulated PVC cables or equivalent, 100 mm2 or larger)
Ranges
(auto-ranging)
Displayable
range
Display
resolution
Range of guaranteed
accuracy
420.0 V
0.0 to 420.0 V
0.1 V
30.0 to 420.0 V
600 V
380 to 600 V
1V
380 to 480 V
481 to 600 V
Accuracy
40 to 66 Hz
66 to 400 Hz
±1.5% rdg. ±5 dgt. ±2.5% rdg. ±5 dgt.
±2.0% rdg. ±5 dgt.
±5.0% rdg. ±5 dgt.
SAFETY HiTESTER 3258
Supplied Accessories: One manual, one soft case and six AA (LR6) batteries
HIOKI (Shanghai) Sales & Trading Co., Ltd. :
1608-1610 Shanghai Times Square Office, 93 Huai Hai Zhong
Road, Shanghai, P.R.China POSTCODE: 200021
TEL +86-21-6391-0090/0092 FAX +86-21-6391-0360
E-mail: [email protected]
HEAD OFFICE :
81 Koizumi, Ueda, Nagano, 386-1192, Japan
TEL +81-268-28-0562 / FAX +81-268-28-0568
E-mail: [email protected]
HIOKI USA CORPORATION :
6 Corporate Drive, Cranbury, NJ 08512 USA
TEL +1-609-409-9109 / FAX +1-609-409-9108
E-mail: [email protected]
Supplied Accessory: soft case
DISTRIBUTED BY
Beijing Office :
A-2602 Freetown, 58 Dong San Huan Nan Road
Beijing, P.R.China POSTCODE: 100022
TEL +86-10-5867-4080/4081 FAX +86-10-5867-4090
E-mail: [email protected]
Guangzhou Office :
Room A-3206, Victory PlazaServices Center, No.103,
Tiyuxi Road, Guangzhou, P.R.China POSTCODE:510620
TEL +86-20-38392673/2676 FAX +86-20-38392679
E-mail: [email protected]
All information correct as of Jan. 16, 2009. All specifications are subject to change without notice.
3258E2-91M-05P
Printed in Japan