For power line current value measurement (50/60 Hz) CLAMP ON PROBE 9132-50 CAT III 600V Max. circuit voltage 600V rms insulated wire 9704: Use when the receiving connectors are banana-type terminals Simply connect to a tester or recorder to easily measure large currents • CE mark compliant CAT III 600V • Choose from up to six general-purpose ranges • For more accurate waveform recordings and analysis of harmonic signals, etc. Basic specifications (Accuracy guaranteed for 1 year, or opening and closing of the clamp sensor 10,000 times) 9132-50 Rated current AC 20/50/100/200/500/1000 A Accuracy ±3% rdg. ±0.2% f.s. (45 to 66Hz) Frequency characteristics Add to amplitude accuracy for frequencies from 40 to 1kHz: ± 1% rdg. Output rate 0.2V AC f.s. (f.s.=setting rage) (Connect to a voltage input device providing a high input impedance of 1MΩ) Max. current input (For 40Hz to500 Hz: 100%, and for 500Hz to 1kHz: within 90% of derating) 1000Arms continuous (all ranges) Max. circuit voltage 600Vrms (Insulated conductor) Diameter Ø 55mm(2.17in), or 20mm(0.79in) × 80mm(3.15in) busbar Dimensions, mass 100mm(3.94in)W × 224mm(8.82in)H × 35mm(1.38in)D, 600g(21.2oz), cord length: 3m(9.84ft)