PRODIS® - PD-INC

PRODIS®-INC
Digital Process Meter
for incremental position sensors
Instruction Manual
Please read carefully before installation and operation!
PRODIS®-INC
Contents
Contents
Specifications
2
Specifications2
Safety instructions
3
Mechanical mounting
4
Description5
Comparator outputs
8
Outline Drawing
9
Operation10
Operation keys and display
10
Explanation and operation of the functions
11
Appendix
Examples for signal wiring
14
Determination of the scaling parameters
15
RS-232C interface
17
Declaration of Conformity
18
Display
6-digit, 7-segment LED, height 14 mm,
decimal point programmable
Counting frequency
250 kHz max., 1 MHz edge frequency
Excitation voltage/current
24 V DC ±10%/150 mA, residual ripple 1%ss;
85-250 V AC, 50-60 Hz/180 mA max.
Sensor excitation
24 V DC/300 mA or 5V DC/500 mA
Inputs
A, B, Z, T (reference signal)
Comparator outputs (option)
Relay
NPN
250 V AC/5 A, 30 V DC/5 A
24 V max./50 mA to GND
Connection
Terminal strip 12-pole, excitation 3-pole
Operating temperature
-10 ... +40 °C
Storage temperature
-20 ... +85 °C
Weight
24 V DC: approx. 250 g; 230 V AC: approx. 400 g
Protection class
Front IP60, rear IP40
Humidity
Max. 80 % R.H., non condensing
Safety of equipment
EN 61010-1:2010
EMC
EN 61326-1:2006
MAN-PD-INC-E-13
www.asm-sensor.com
ASM GmbH
PRODIS®-INC
Instruction Manual
Safety
instructions
Do not use PRODIS®-INC process meters in safety critical
applications where malfunction or total failure of the sensor
may cause danger for man or machine.
For safety related applications additional mechanisms (devices)
are necessary to maintain safety and to avoid damage.
Disregard of this advice releases the manufacturer from product
liability.
The meter must be operated only within values specified in the
data sheet.
Connection to power supply must be performed in accordance
with safety instructions for electrical facilities and performed
only by trained staff.
Danger of
Destruction!
It has to be guaranteed that the excitation voltage agrees with
the indicated value on the type label.
Do not open the process meter.
ASM GmbH
www.asm-sensor.com
MAN-PD-INC-E-13
3
PRODIS®-INC
Instruction Manual
Mechanical
mounting
Mounting
clamps
Hook in the rear
notch and push
the end down
until the front
notch is locked
Turn the set screw
with a slotted
screwdriver until
stop at the front
plate.
4
MAN-PD-INC-E-13
www.asm-sensor.com
ASM GmbH
PRODIS®-INC
Instruction Manual
Description
The process meter PRODIS®-INC is designed for use with incremental
­position sensors to display angles and displacements. The fast counter
processes 90° phase shifted A,B signals (quadrature signals) for direction
and counting information. When using ASM sensors resolutions up to 5
µm resp. 2 angular minutes are possible. The sensor excitation voltage is
supplied from the meter.
With four membrane keys all parameters can be programmed for the
­special application. An index pulse and a reference switch can be used for
calibration of the measurement system. Optional comparator function with
two relays and four NPN open-collector outputs are available. With the RS232 interface data can be transmitted easily to a PC, printer or PLC.
Quadrature signal A
Quadrature signal B
Zero- or index signal Z
Reference signal T
(multiple function, see page 12)
The reset of the display takes place for the
condition ( A & B & Z ) resp. ( A & B & Z & T )
The Zero signal is a pulse signal unique within the measurement range
and explicit to the phase of the quadrature signal to reset the PRODIS®INC meter.
The Index signal is a multiple periodical pulse signal within the measurement range and explicit to the phase of the quadrature signal, e.g. the zero
signal of an incremental encoder that appears at every single turn.
The Reference signal is a pulse signal unique within the measurement
range to enable the reset of the PRODIS®-INC meter, e.g. mechanical
­reference contact for end position recognition.
ASM GmbH
www.asm-sensor.com
MAN-PD-INC-E-13
5
PRODIS®-INC
Instruction Manual
Wiring basic unit
Signals
Connector X1
pin no.
Sensor +UB (* see footer)
Sensor 0 V (GND)
Signal A
Signal A
Signal B
Signal B
Signal Z (zero signal)
Signal Z (zero signal)
Signal T (reference signal)
Signal T (reference signal)
GND
PD-INC-24VDC (** see footer)
Excitation +24 V
Excitation 0 V (GND)
PD-INC-230VAC (** see footer)
Excitation
Protective ground
(*) Check the sensor excitation:
(**) Check the meter excitation:
Connector X2
pin no.
1
2
4
5
6
7
8
9
10
11
12
13
14
13, 15
14
PD-INC-X-G24V-X : PD-INC-X-G5V-X : PD-INC-24VDC-X-X: PD-INC-230VAC-X-X:
24 V sensor excitation
5 V sensor excitation
24 V DC meter excitation
230 V AC meter excitation
5 ........ 1
RS-232
Rear view without
comparator function
RS-232 interface
(w/o comparator
function)
(with comparator
function)
6
Level
Data format
Transmision rate
Signals
1.....................................12
13 14 15
X1
X2
RS-232: ±8 V, galvanically isolated
1 start bit, 8 data bits, 1 stop bit, no parity
9600 Baud
D-Sub, Pin No.
TxD
RxD
GND
2
3
5
Signals
TxD
RxD
GND
Connector X3, Pin No.
17
16
18
MAN-PD-INC-E-13
www.asm-sensor.com
ASM GmbH
PRODIS®-INC
Instruction Manual
30
29
28
Rear view with
comparator Output
Comparator
function
(option)
Desktop version
(option)
27
26
25
24 .................................18..17..16
X3
X4
Comparator
Comparator output
NPN
Connector X3
Collector
pin no.
Comparator 1
NPN1
20
Comparator 2
NPN2
21
Comparator 3
Comparator 4
NPN3
22
NPN4
23
NPN GND
NPN UB
(+24V)
24
19
RS-232
RS-232
Relay
Connector X4
pin no.
Relay 1
NO
NC
Common
Relay 2
NO
NC
Common
25
27
26
28
30
29
LED
LED1
LED2
Mains switch
8 ............................. 1
15 ....................... 9
X1
85 ... 250 V AC
Wiring of connector X1 see table at page 6.
ASM GmbH
www.asm-sensor.com
MAN-PD-INC-E-13
7
PRODIS®-INC
Instruction Manual
Comparator
outputs
(diagram)
Limit 1
Relay 1 COM
Relay 1 NC
Relay 1 NO
NPN +UB
NPN1 collector
NPN GND
Limit 2
Relay 2 COM
Relay 2 NC
Relay 2 NO
NPN2 collector
Limit 3
NPN3 collector
Limit 4
NPN4 collector
8
MAN-PD-INC-E-13
www.asm-sensor.com
ASM GmbH
PRODIS®-INC
Instruction Manual
Outline drawing
LED1
LED2
Dimensions in mm [inch]
PD-XXX-24VDC
Dimensions in mm [inch]
PD-XXX-230VAC
ASM GmbH
www.asm-sensor.com
MAN-PD-INC-E-13
9
PRODIS®-INC
Instruction Manual
Operation
Check all lines, connections and excitation voltages before switching on
the equipment!
When the meter is switched on a short self test sequence will start with
all LED segments on and then the version of the process meter will be
­displayed. After that procedure PRODIS®-INC is in the normal mode.
Operation keys
and display
Explanation of the operation keys and display elements:
LED 2
Sign
LED 1
: Key to control the programming menus
: Multifunction keys
for parameter settings
: Multifunction key to reset the display and to store
the parameters in a non-volatile memory
Note:
+
10
means:
hold key
and press
MAN-PD-INC-E-13
www.asm-sensor.com
.
ASM GmbH
PRODIS®-INC
Instruction Manual
Explanation and
operation of the
functions
Normal mode, displaying the position value
The displayed mesurement value will be calculated as
Measurement value • Multiplier
Reading = Divisor
+ Offset value
Multiplier, divisor, decimal divisor and offset are user definable parameters
(for calculation examples see appendix). When the display range is exceeded, the display shows oFrAnGE. PRODIS®-INC counts every pulse
edge of the quadrature signal (times 4 counting mode).
Relative measurement
In addition to the normal mode display PRODIS®-INC can display a second position value, a relative measurement mode with an independent
zero to be set by the reset key manually. The normal mode measurement
value remains in the background and will be displayed again after returning to the normal mode.
With the parameter CHnul (-> CHnul=1) the display will be set to zero
when relative measurement is activated.
Offset function
The offset function allows setting and changing of the offset value directly
in the normal mode.
Comparator function
(for versions with comparator function only)
Up to four comparator functions can defined by programming of limit
­value, hysteresis and operating direction. Outputs are two isolated relays
with C/O contacts and four ground related NPN open-collector outputs.
The operating condition of the comparators will be indicated by LED1 for
­relay1, NPN1, NPN3 and LED2 for relay2, NPN2, NPN4. With the parameter measurement mode (rx) the comparator function will be assigned to
the normal measurement or to relative measurement.
Last-value memory
When the last-value memory function is activated by ISt=1 (see table
page 13) the current measurement value wil be stored into memory when
­PRODIS®-INC is switched off. In the switched off condition, input pulses
are not recognized. When the display is switched on again, the stored
­measurement value will be displayed.
ASM GmbH
www.asm-sensor.com
MAN-PD-INC-E-13
11
PRODIS®-INC
Instruction Manual
Explanation and
operation of the
functions
(continuation)
12
T signal, functions
oFF: The T signal has no effect.
CS: The T signal activates the relative measurement mode.
CF: No function.
Hn: The T signal resets the display in normal and relative
measurement mode.
AF: The T signal holds the current measurement value.
The counting operation will not be interrupted.
tL:
The T signal locks the front key access (key lock)
brEF: The T signal activates the signal “Z” reset function
Ctr3: SEND The displayed value will be sent via the RS-232 interface
Ctr4: SEND-CYC The displayed value will be sent periodically every
10 ms via RS-232
MAN-PD-INC-E-13
www.asm-sensor.com
ASM GmbH
PRODIS®-INC
Instruction Manual
Explanation and
operation of the
functions
(continuation)
Parameter settings
The Parameter settings are effected in a programming menu.
+
Activate programming mode
,
Change the parameter by decimal steps
+
Reset activated parameter
+
Change the sign of signed parameters
Store in non-volatile memory
Proceed and return to normal mode
New settings become effective immediately
Submenus
Parameter
Display
Value range
Factory
setting
+
Decimal point
dp
1 of 5, AUS (off)
AUS (off)
Z signal active/inactive
rEF
1/0
0
Reset button
active/inactive
nuL
1/0
1
Automatic relative
measurement reset
CHnul
1/0
1
Multiplier
ZAEHL
0 ... +999999
1
Divisor
nEnnEr
0 ... +999999
1
Counting direction
drEh L/r
left / right
left
T signal
t
oFF/CS/Hn/AF/tl/
brEF/Ctr3/Ctr4
oFF
Last value memory
ISt
1/0
0
Display brightness
db
1 ... 15
15
Transmission rate
bA
4.8, 9.6 ... 115.2
9.6
Relative measurement
mode
Flashing
decimal point
+
0
Reset
+
+
+ Power on*
Offset
oFFSEt
-999999 ... +999999
0
Limit value
+/- 999.999
+999.999
Hysteresis
rELx
µ
H rELx
+/- 999.999
1
Operating direction
rx
oEF, SCH
SCH (no)
Measurement mode
rx
HAU / CHA
HAU (normal)
Reset to factory
default value
000000 for
2s
* Disconnect device from excitation, wait 5 seconds, press
and
Connect excitation, the display shows “000000”, then release
+
ASM GmbH
www.asm-sensor.com
together and hold.
.
MAN-PD-INC-E-13
13
PRODIS®-INC
Instruction Manual
Examples for
signal wiring
+24V: PD-INC-X-G24V-HTL
Wiring single ended
POSIMAG HTL
or
WS-X-PP530
WS-X-PP24V
Reference switch
PD-INC-24VDC-X-X
or
Protective ground
PD-INC-230V-X-X
+5V: PD-INC-X-G5V-TTL /
+24V: PD-INC-X-G24V-HTL
Wiring differential
POSIMAG TTL/HTL
Sensor with
Line driver
5V differential
or RS485,
reference switch
Reference switch
PD-INC-24VDC-X-X
or
Protective ground
14
MAN-PD-INC-E-13
www.asm-sensor.com
PD-INC-230V-X-X
ASM GmbH
PRODIS®-INC
Instruction Manual
Determination
of the scaling
parameters
• Determine the resolution of the position sensor ‘dX’ (displacement per
counting edge) and calculate it to the unit to be displayed
• Define the resolution of the meter ‘dA’ (same unit as dx)
• Multiplier’ = dX, Divisor’ = dA
• Insert and transform multiplier and divisor by extension or reduction
• Set decimal point
• With the decimal divisor an additional shift right can be made.
As an alternative to the resolution parameters dX and dA the scaling parameters can be calculated by the measurement range parameters DX (display value for end of range) and DA (counting pulses for end of range).
Calculating examples for the scaling
1a. Meter for cable actuated position sensor model WS10 – 1000 – 25
– PP530
Least significant Digit (LSD) of the display has to be equivalent to 0.1 mm
The resolution with times 4 counting mode is 25 • 4 = 100 pulse edges
Resolution of the position sensor: 100 pulse edges per mm: dX = 0.01 mm
Resolution of the meter: dA = 0.1 mm
Multiplier’ = dX = 0.01
Divisor’ = dA = 0.1
Insert the values and extend / reduce:
Multiplier = 1
Divisor = 10
Set decimal point between the first and the second digit from the right hand
side
1b. Alternative calculation of example 1a
The display value for end of range has to be 10000
Display value for end of range DX=10000
Counting pulses for end of range
DA=1000 mm • (25 • 4) pulses/mm
Insert the values and extend / reduce:
Multiplier = 1
Divisor = 10
ASM GmbH
www.asm-sensor.com
MAN-PD-INC-E-13
15
PRODIS®-INC
Instruction Manual
Determination
of the scaling
parameters
2. Meter for POSIMAG position sensor PMIS2 – 10 – 5 – PP530
LSD of the display has to be equivalent to 0.01 in
Resolution of the position sensor: dX = 5 µm = 0.005 mm = 0.005/25.4 in
Resolution of the meter: dA = 0.01 inch
0.005
Multiplier’ = dX =
25.4
Divisor’ = dA = 0.01
Insert the values and extend / reduce:
Multiplier = 5
Divisor = 254
Set decimal point between the second and the third digit from the right
hand side
3. Meter for incremental encoder with 2500 pulses per revolution
LSD of the display has to be equivalent to 0.1 degrees
Resolution of the sensor with times 4 counting mode: dX = 4 • 2500 pulses
/ revolution corresponding to 360° / 4 • 2500 pulses
Resolution of the meter: dA = 0.025°
360
Multiplier’ = dX =
2500 • 4
Divisor = dA = 0.1
Insert the values and extend / reduce:
Multiplier = 9
Divisor = 25
Set decimal point between the first and the second digit from the right hand
side
16
MAN-PD-INC-E-13
www.asm-sensor.com
ASM GmbH
PRODIS®-INC
Instruction Manual
RS-232 interface
Transmission of a position value
Send to PRODIS®:
Response of PRODIS®:
“r”
CR, sign, n5, n4, n3, n2, n1, n0
with ni: ASCII characters, leading digits
filled with “0”
Sign: positive sign = Space “ “
Reset of the display value
Send to PRODIS®:
PRODIS® function:
“n”
Reset counter
Data format
1 start bit, 8 data bits, 1 stop bit, no parity
Baud rate: 9600 Bd, programmable via menu
Net transmission rate
Max. 50/s approx.
ASM GmbH
www.asm-sensor.com
MAN-PD-INC-E-13
17
PRODIS®-INC
Declaration of Conformity
Declaration of Conformity
The Process Meter
Manufacturer:
ASM GmbH
Am Bleichbach 18-22
85452 Moosinning / Germany
Model:
Options:
PRODIS®-INC
-24VDC, -230VAC, -REL2
complies with the following standards and directives:
Security:
Low voltage directive: 2006/95/EEC
Applicable standards: EN 61010-1:2010
EMC:
EMC directive: 2004/108/EEC
Applicable standards: EN 61326-1:2006
Note: When using the comparator option -REL2/NPN4 ensure that
the ­connected circuit complies also with the EMC directive.
Moosinning, 01.05.2013
i.A. Andreas Bolm
i.A. Peter Wirth
QualitätsbeauftragterLeiter Entwicklung
18
MAN-PD-INC-E-13
www.asm-sensor.com
ASM GmbH
PRODIS®-INC
Notes
ASM GmbH
www.asm-sensor.com
MAN-PD-INC-E-13
19
ASM GmbH Automation • Sensorik • Messtechnik
Am Bleichbach 18-22
Telephone: +49 8123 986-0
Internet: www.asm-sensor.de
E-Mail: [email protected]
85452 Moosinning / Germany
Telefax: +49 8123 986-500
www.asmsensors.com
[email protected]
© by ASM GmbH, Moosinning 05.2013 Subject to change without notice. See protection note DIN 34 !