PD-ADC - ASM GmbH

PRODIS®-ADC
Digital Process Meter
for analog position sensors
Instruction Manual
Please read carefully before installation and operation!
PRODIS®-ADC
Contents
Contents
Specifications
2
Specifications2
Safety instructions
3
Description4
Mechanical mounting
4
Operation9
Operation keys and display
9
Explanation and operation of the functions
10
RS-232-Interface14
Appendix15
Connection examples
15
Declaration of conformity
16
Display
6-digit, 7-segment LED, height 14 mm,
decimal point programmable
Counting rate
1 ... 25/s programmable
Measurement accuracy
±0.05 % f.s.
Excitation voltage/current
24 V DC ±10%/150 mA, residual ripple 1%PP;
85-250 V AC, 50-60 Hz/180 mA max.
Sensor excitation
24 V DC/300 mA; 5 V/10 mA
Input
Two channels, each for:
Voltage 10V; U1; U2; U3; max. 24V
Current I1, load 100 Ω, Imax<30 mA
Voltage divider Rmin=500 Ω, 0 ... 5 V
One input or the difference between both inputs
can be chosen by programming
Control input
2 control inputs 24 V, active low
Comparator Output (option)
Relay
NPN
250 V AC/5 A, 30 V DC/5 A
24 V max./50 mA to GND
Connection
Terminal strip 12 pole, excitation 3 pole
Temperature coefficient
±20 x 10-6 / °C
Operating temperature
-10...+40 °C
Storage temperature
-20...+85 °C
Weight
24 V DC: approx. 250 g; 230 V AC: approx. 400 g
Protection class
Front IP60, rear IP40
Humidity
Max. 80 % R. H., non condensing
Safety of equipment
EN 61010-1:2010
EMC
EN 61326-1:2006
MAN-PD-ADC-E-13
www.asm-sensor.com
ASM GmbH
PRODIS®-ADC
Instruction Manual
Safety
instructions
Do not use PRODIS®-ADC process meters in safety critical applications where malfunction or total failure of the sensor may
cause danger for man or machine.
For safety related applications additional mechanisms (de- vices) are necessary to maintain safety and to avoid damage.
Disregard of this advice releases the manufacturer from product liability.
The meter must be operated only within values specified in the
data sheet.
Connection to power supply must be performed in accordance
with safety instructions for electrical facilities and performed
only by trained staff.
Danger of
Destruction!
The inputs of the process meter must not be connected to current sources with more than 30 mA max.
It has to be guaranteed that the excitation voltage agrees with
the indicated value on the type label.
Do not open the process meter.
ASM GmbH
www.asm-sensor.com
MAN-PD-ADC-E-13
3
PRODIS®-ADC
Instruction Manual
Description
The process meter PRODIS®-ADC is designed for use with analog position sensors to display angles and displacements. A high-resolution analog/
digital converter can process two input signals of each 0 … 10 V, 0.5 … 10
V, 0/4 … 20 mA or voltage divider. Thus the difference of to measurement
signal can be measured.
To display mass units like inch, mm or degrees between given start and
end values the meter can be scaled by the user. Via two control inputs the
functions Tare and Display Hold can be activated.
The sensor excitation voltage is supplied from the meter. With four membrane keys the parameters for signal processing, scaling and comparator
function can be programmed. Optional comparator function with two relays
and four NPN open-collector outputs are available.
Mechanical
mounting
Mounting
clamps
Hook in the rear
notch and push
the end down
until the front
notch is locked
Turn the set screw
with a slotted
screwdriver until
stop at the front
plate.
4
MAN-PD-ADC-E-13
www.asm-sensor.com
ASM GmbH
PRODIS®-ADC
Instruction Manual
Wiring basic unit
Signals
Connector X1
pin no.
Sensor excitation +UB 24 V
Sensor excitation 0 V (GND)
Control input terminal 1: tare function
Control input terminal 2: Freeze, Key lock,
Data send
Voltage input terminal 0 ... 10 V, channel 1
Voltage input terminal 0 ... 10 V, channel 2
Current input terminal 0/4 ... 20 mA, channel 1
Current input terminal 0/4 ... 20 mA, channel 2
Voltage divider input terminal, channel 1
Voltage divider input terminal, channel 2
Sensor excitation, R1K +UB = 5V
GND
PD-ADC-24VDC (* see footer)
Excitation +24 V
Excitation 0 V (GND)
PD-ADC-230VAC (* see footer)
Excitation
Protective ground
(*) Check the meter excitation:
PD-ADC-24VDC-X-X: PD-ADC-230VAC-X-X: Connector X2
pin no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
13, 15
14
24 V DC meter excitation
230 V AC meter excitation
5 ........ 1
RS-232
Rear view without
comparator function
RS-232 interface
(w/o comparator
function)
(with comparator
function)
1.....................................12
13 14 15
X1
X2
Level
Data format
Transmision rate
Signals
TxD
RxD
GND
RS-232: ±8 V, galvanically isolated
1 start bit, 8 data bits, 1 stop bit, no parity
9600 Baud
D-Sub, Pin No.
2
3
5
Signals
TxD
RxD
GND
Connector X3, Pin No.
17
16
18
ASM GmbH
www.asm-sensor.com
MAN-PD-ADC-E-13
5
PRODIS®-ADC
Instruction Manual
30
29
28
Rear view with
comparator Output
Comparator
function
(option)
Desktop version
(option)
27
26
25
24 .................................18..17..16
X3
X4
Comparator
Comparator output
NPN
Connector X3
Collector
pin no.
Comparator 1
NPN1
20
Comparator 2
NPN2
21
Comparator 3
Comparator 4
NPN3
22
NPN4
23
NPN GND
NPN UB
(+24V)
24
19
RS-232
RS-232
Relay
Connector X4
pin no.
Relay 1
NO
NC
Common
Relay 2
NO
NC
Common
25
27
26
28
30
29
LED
LED1
LED2
Mains switch
8 ............................. 1
15 ....................... 9
X1
85 ... 250 V AC
Wiring of connector X1 see table at page 5.
6
MAN-PD-ADC-E-13
www.asm-sensor.com
ASM GmbH
PRODIS®-ADC
Instruction Manual
Comparator
outputs
(diagram)
Limit 1
Relay 1 COM
Relay 1 NC
Relay 1 NO
NPN +UB
NPN1 collector
NPN GND
Limit 2
Relay 2 COM
Relay 2 NC
Relay 2 NO
NPN2 collector
Limit 3
NPN3 collector
Limit 4
NPN4 collector
ASM GmbH
www.asm-sensor.com
MAN-PD-ADC-E-13
7
PRODIS®-ADC
Instruction Manual
Outline drawing
LED1
LED2
Dimensions in mm [inch]
PD-XXX-24VDC
Dimensions in mm [inch]
PD-XXX-230VAC
8
MAN-PD-ADC-E-13
www.asm-sensor.com
ASM GmbH
PRODIS®-ADC
Instruction Manual
Operation
Check all lines, connections and excitation voltages before switching on
the equipment!
When the meter is switched on a short self test sequence will start with
all LED segments on and then the version of the process meter will be
­displayed. After that procedure PRODIS®-INC is in the normal mode.
Operation keys
and display
Explanation of the operation keys and display elements:
LED 2
Sign
LED 1
: Key to control the programming menus
: Multifunction keys
for parameter settings
: Multifunction key to reset the display and to store
the parameters in a non-volatile memory
Note:
+
means:
hold key
ASM GmbH
www.asm-sensor.com
and press
.
MAN-PD-ADC-E-13
9
PRODIS®-ADC
Instruction Manual
Explanation and
operation of the
functions
Scaling for maesurement input signals 0...10 V, 0/4...20 mA
The input of the start and end value for the displayed value range 0...10 V
resp. 0/4...20 mA will be made by the menu positions “start value” and “end
value”.
Example: Sensor with a measurement range of 2000 mm and a output
signal of 4...20 mA, wanted display range 0 … 2000.0
Setting: SIG: I42, start value: 0, end value: 20 000, decimal point between
the first and second position from the right hand side.
Scaling for position sensors with potentiometric signal
An utilization factor nP considers measurement range limits and individual
sensitivity of the potentiometer. The display range is set by start and end
value. nP will be calculated as a product of (sensitivity) E x L (measurement range), both specifications can be taken from the type label. When
the sensor has been changed the re-calibration of the meter is very easy
by changing nP.
Example A: Linear sensor with a measurement range of 1250 mm and
output R1K, sensitivity: 0,756 mV/V/mm, wanted display: 0 … 1250.0 mm.
Setting: nP = 0.765 x 1.250 = 0.945, start value: 0, end value: 12500, decimal point between the first and second position from the right hand side.
Example B: as A, but wanted display range: 0 … 49.21 inch.
Setting: nP = 0.765 x 1.250 = 0.945, start value: 0, end value: 4921, decimal point between the second and third position from the right hand side.
Example C: angle sensor with a used range of 90 degrees and output R1K,
sensitivity: 2.846 mV/V/degree, wanted display range: 0 … 90 degrees.
Setting: nP = 0.002846 x 90 = 0.25614, start value: 0, end value: 90.
Tare function
Activated by the front button
or via the control input the display of the
meter will be set to the offset value, the decimal point is flashing while the
tare function is active. Pressing the button
again deactivates the tare
function.
Offset function
The offset function allows to set and change the offset value of the meter
directly in the normal mode.
10
MAN-PD-ADC-E-13
www.asm-sensor.com
ASM GmbH
PRODIS®-ADC
Instruction Manual
Explanation and
operation of the
functions
(continuation)
Teach-in scaling with start value and end value
A display value range is assigned to a measurement range by teach-in.
The display value range is defined by start and end value. The teach-in
procedure will be released via the programming menu with t-In = E. Set the
input signal to the first value and then press
. Then set the input signal
to the second value and press
. To avoid unintentional changes with­
t-In = A the teached scaling remains active, however, the teach-in procedure itself is disabled.
Explanation of the menu settings
Selection of the measurement signal:
SIG = r
SIG = U
SIG = U2
SIG = U3
SIG = I42
SIG = I02
potentiometric measurement signal
voltage signal 0…10 V
voltage signal 0.5 … 10 V
voltage signal 0 … 5 V
current signal 4 … 20 mA
current signal 0 … 20 mA
Teach-in scaling:
t-In = O
t-In = A
t-In = E
Teach-in scaling inactive
Teach-in scaling active, teach-in procedure inactive
Teach-in scaling active, teach-in procedure active
ASM GmbH
www.asm-sensor.com
MAN-PD-ADC-E-13
11
PRODIS®-ADC
Instruction Manual
Explanation and
operation of the
functions
(continuation)
Parameter settings
The Parameter settings are effected in a programming menu.
+
Activate programming mode
,
Change the parameter by decimal steps
+
Reset activated parameter
+
Change the sign of signed parameters
Store in non-volatile memory
Proceed and return to normal mode
New settings become effective immediately
Submenus
Parameter
Display
Value range
Factory
setting
+
Channel select
Ch
1, 2, 1-2 (difference)
1
Measurement signal
SIG
U, U2, U3, I42, I02, R
U
Decimal point
dp
1 aus 5, AUS (off)
AUS (off)
Activate tare function
tAr
OFF, ON
OFF
Activate teach-In function
t-In
O, A, E
O
Display start value
bEG
±999999
0
Display end value
End
±999999
10000
Utilization factor Rxk
nP
0 ... 0.99999
0.999
Measurement rate 1/s
rAtE
1 ... 25
16
Display brightness
db
1 ... 15
15
Baud rate
bA
4.8, 9.6, 19.2
9.6
Control input 2
Cntr
1 ... 4
1
Averaging filter
FIL
0 ... 128
0
Tare function on
flashing
decimal point
Offset
oFFSEt
-999999 ... +999999
0
Limit value
+/- 999.999
+999.999
Hysteresis
rELx
Hµ rELx
+/- 999.999
1
Operating direction
rx
oEF (nc), SCH
SCH (no)
Reset to factory default
settings
000000 for
2s
+
+
+ Power on*
0
* Disconnect device from excitation, wait 5 seconds, press
and
Connect excitation, the display shows “000000”, then release
+
12
MAN-PD-ADC-E-13
www.asm-sensor.com
together and hold.
.
ASM GmbH
PRODIS®-ADC
Instruction Manual
Control inputs
1 and 2
Functions TARE, FREEZE, KEY-LOCK, DATA-SEND
These functions can be activated by two control inputs. The activation of an
input is made by connecting the input with GND. An open input or a connection with 24 V sets the function of the control input to inactive.
Description of the functions
Control input 1, TARE function
The activation of the Tare function sets the display value to zero resp. to
the offset value from the offset menu input. The TARE compensation will be
held as long as the control input 1 is active. An active control input 1 avoids
any tare operation with the S key at the meter frontside.
Control input 2, functions FREEZE, KEY-LOCK, DATA-SEND
The used function of the control input 2 is set in the setting menu with the
“Cntr” menu:
Cntr: 1
FREEZE
Display “freeze”
Cntr: 2
KEY-LOCK
Programming blocked
Cntr: 3
SEND
The displayed value will be sent via
the RS-232 interface
Cntr: 4
SEND-CYC
The displayed value will be sent
periodically every 10 ms via RS-232
ASM GmbH
www.asm-sensor.com
MAN-PD-ADC-E-13
13
PRODIS®-ADC
Instruction Manual
RS-232 interface
Transmission of a position value
Send to PRODIS®:
Response of PRODIS®:
“r”
CR, sign, n5, n4, n3, n2, n1, n0
with ni: ASCII characters, leading digits
filled with “0”
Sign: positive sign = Space “ “
Tare function On/Off
Send to PRODIS®:
PRODIS® function:
“n”
Tare function on/off
Data format
1 start bit, 8 data bits, 1 stop bit, no parity
Baud rate: programmable
Net transmission rate
Max. 50/s approx.
14
MAN-PD-ADC-E-13
www.asm-sensor.com
ASM GmbH
PRODIS®-ADC
Instruction Manual
Examples for
signal wiring
+24 V
Excitation GND
UB = 24 V
0 ... 10 V
0,5
0.5 ... 10V
Excitation
+24 V
UB = 24 V
4 ... 20 mA
Load 100 Ω
Excitation
+24 V
Excitation GND
UB = 24 V 0/4 ... 20 mA
Load 100 Ω
Excitation
+5 V
UB = 5 V
0.5 ... 4,5
4.5 V
0,5
R1K
Signal 1+
+5 V
Signal 2+
Excitation
ASM GmbH
www.asm-sensor.com
MAN-PD-ADC-E-13
15
Declaration of Conformity
The Process Meter
Manufacturer:
ASM GmbH
Am Bleichbach 18-22
85452 Moosinning / Germany
Model:
Options:
PRODIS®-ADC
-24VDC, -230VAC, -REL2
complies with the following standards and directives:
Security:
Low voltage directive: 2006/95/EEC
Applicable standards: EN 61010-1:2010
EMC:
EMC directive: 2004/108/EEC
Applicable standards: EN 61326-1:2006
Note: When using the comparator option -REL2/NPN4 ensure that
the ­connected circuit complies also with the EMC directive.
Moosinning, 01.05.2013
i.A. Andreas Bolm
i.A. Peter Wirth
QualitätsbeauftragterLeiter Entwicklung
ASM GmbH Automation • Sensorik • Messtechnik
Am Bleichbach 18-22
Telephone: +49 8123 986-0
Internet: www.asm-sensor.de
E-Mail: [email protected]
85452 Moosinning / Germany
Telefax: +49 8123 986-500
www.asmsensors.com
[email protected]
© by ASM GmbH, Moosinning 05.2013 Subject to change without notice. See protection note DIN 34 !