NetSure RDB Series - Emerson Network Power

A technical manual from the experts
in Business-Critical Continuity™
NetSure™ RDB Series
Installation and User Manual — Plug-n-Play 48V Rack Distribution
Section 6041 (Issue AG, January 21, 2013)
Business-Critical Continuity™, Emerson Network Power, and the Emerson Network
Power logo are trademarks and service marks of Emerson Electric Co.
NetSure™, NetSpan™, NetReach™, NetXtend™, and NetPerform™
are trademarks of Emerson Network Power, Energy Systems, North America, Inc.
All other trademarks are the property of their respective owners.
The products covered by this instruction manual are manufactured and/or
sold by Emerson Network Power, Energy Systems, North America, Inc.
The information contained in this document is subject to change without notice and may not be
suitable for all applications. While every precaution has been taken to ensure the accuracy and
completeness of this document, Emerson Network Power, Energy Systems, North America, Inc.
assumes no responsibility and disclaims all liability for damages resulting from use of this information
or for any errors or omissions. Refer to other local practices or building codes as applicable for the correct
methods, tools, and materials to be used in performing procedures not specifically described in this document.
This document is the property of Emerson Network Power, Energy Systems, North America, Inc.
and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use or disclosure of it without the written permission
of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Copyright © 2013, Emerson Network Power, Energy Systems, North America, Inc.
All rights reserved throughout the world.
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.0
INSTALLATION
1.1
Shipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2
Installing the Rack PDU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2.1
1.2.2
Installing the Rack PDU Directly to a Rack Frame or Existing Mounting Bracket . . . . . . . . 2
Installing Rack PDUs to a Rack Frame using the Optional Mounting Bracket. . . . . . . . . . . . 2
2.0
ELECTRICAL CONNECTIONS
2.1
Connecting the Rack PDU DC Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2
Connecting the Rack PDU’s DC Output to Customer Equipment . . . . . . . . . . . . . . . . . . . . . 4
2.3
Connecting External Circuit Breaker Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.0
SPECIFICATIONS AND TECHNICAL DATA
3.1
Conformity and Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2
Environmental Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.4
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.4.1
3.4.2
3.4.3
3.4.4
3.4.5
3.4.6
NetSure™ RDB L6, P/Ns 547692, 547693, 547499 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
NetSure™ RDB L15, P/Ns 547694, 547695, 547615 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
NetSure™ RDB M6, P/Ns 547696, 547697, 547503 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
NetSure™ RDB H2, P/N 547500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
NetSure™ RDB H3, P/Ns 547698, 547699, 547501 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
NetSure™ RDB Mounting Bracket, P/N 547665. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.5
Input Quick Connect Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.6
Output Cable Assemblies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.6.1
3.6.2
P/N 547595, P/N 547613 and P/N 555654 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Output Connector Kits (P/N 554878 and P/N 554944). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.7
Replacement Circuit Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.0
OPERATION
4.1
Connecting Power to the Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.2
Removing Power from the Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.3
Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.3.1
4.3.2
Local Alarm Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
External Circuit Breaker Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
REVISION RECORD
i
This Page Intentionally Left Blank
ii
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
!
WARNING
Please read and follow all safety information!
Failure to observe the safety information listed below may result in electric shock, fire
hazards, or serious injury.
Please safeguard this Installation and User Manual.
Intended Use
The NetSure™ RDB Rack PDU (Power Distribution Unit) is designed to deliver power to
information technology and telecommunication equipment.
Operate the Rack PDU in an indoor environment only within an ambient temperature range and a
relative humidity range as listed in 3.2 - Environmental Characteristics. Install the Rack PDU in
a clean environment, free of conductive contaminants, moisture, flammable liquids, gases and corrosive substances.
• Do not use the Rack PDU in moist environments. If the Rack PDU is exposed to moisture, immediately disconnect the Rack PDU from DC input power by opening the circuit breaker or removing
the fuse or breaker supplying DC input to the Rack PDU. Send the Rack PDU to the manufacturer for inspection.
• Do not use the Rack PDU for household applications.
Installation and Operation
Improper installation and operation may cause overheating and lead to increased fire hazard. It may also destroy the device and damage other connected systems.
• Installation and start-up must be performed by a qualified service engineer.
• Make sure that the total input current of the connected systems does not exceed the current rating specified on the rating plate of the Rack PDU.
Electrical Safety
Damaged Rack PDUs or connected cables increase the risk of electric shock or smoldering
fire.
• Check the unit for external signs of damage prior to start-up operation! Do not operate the device
if you detect any damage or other deficiencies.
• Only use the supplied DC input power cable.
Personal Safety
Careless handling increases the risk of electric shock.
• Never touch the outlets or the Rack PDU with wet or moist hands.
Service
Repairs should only be performed by qualified service technicians.
Unauthorized changes, modifications, or repairs of the device are performed at the owner’s risk and
will void all warranty claims.
• Do not open the Rack PDU.
• Please contact the nearest customer service center in case of malfunction! Damage and defects
must be repaired immediately.
• Always disconnect the unit from power before troubleshooting.
1
Installation
1.0
INSTALLATION
The NetSure™ RDB Rack PDUs (Power Distribution Units) are designed to be installed on the left
and/or right rear frames of IT racks. They can be mounted directly to the rack or use Rack PDU
Mounting Kit P/N 547665. See 3.4 - Dimensions for hole dimensions.
1.1
Shipment Inspection
Unpack the shipping container, inspect all items for damage and verify that the shipment is complete
and undamaged. Report any damage to your local Emerson representative and the carrier.
1.2
Installing the Rack PDU
!
WARNING
Ensure proper grounding.
The Rack PDU’s "Ground Lead Bracket" must be ground bonded to the mounting bracket (if
used) or rack frame. The mounting bracket (if used) must be ground bonded to the rack frame.
The rack frame must be ground bonded to your site ground. This is typically accomplished
through the use of paint free areas and/or grounding washers used when mounting the
components.
1.2.1
Installing the Rack PDU Directly to a Rack Frame or Existing Mounting Bracket
Install the Rack PDU directly to the rack frame or existing mounting bracket as shown in Figure 1.
Note that the supplied "Ground Lead Bracket" is to be placed between the PDU and the rack frame or
existing mounting bracket as shown in Figure 1. Use the supplied 1/4-20 screws and 1/4-20 KEPS
nuts.
1.2.2
Installing Rack PDUs to a Rack Frame using the Optional Mounting Bracket
If using the Rack PDU Mounting Kit, install the Rack PDU mounting bracket to the left and/or right
rear frame of the rack using the appropriate hardware that fits to the cabinet that will be used.
Install the Rack PDUs to the Rack PDU mounting bracket that was previously installed on the frame
as shown in Figure 2. Note that the supplied "Ground Lead Bracket" is to be placed between the
PDU and the mounting bracket as shown in Figure 2.
2
Installation
Figure 1
Mounting Rack PDUs Directly to Rack Frame
Keps
Nut
Ground
Lead
Bracket
PDU
Ground
Washer
Ground wires not shown
in illustration for clarity.
Screw
Rack PDUs can be mounted on either side.
Rack PDUs and Ground Lead Bracket can be
rotated 180 degrees (cables can exit at top or bottom).
Rear
Figure 2 Mounting Rack PDUs using Optional Mounting Bracket Kit
Keps
Nut
Mtg
Bracket
Ground Lead
Bracket
Rack PDUs and Ground Lead Bracket
can be rotated 180 degrees (cables can
exit at top or bottom).
PDU
Ground
Washer
Screw
Ground wires not shown
in illustration for clarity.
3
Electrical Connections
2.0
ELECTRICAL CONNECTIONS
2.1
Connecting the Rack PDU DC Input
The Rack PDU’s input is designed to be fed from a 200A (max) breaker or fuse using the factory supplied and connected DC input cable assembly and the customer connected input quick connect kits.
See Figure 3.
Figure 3
DC Input Connections
350A Red
Connector
OBSERVE CORRECT POLARITY
(+): Ground Return
(-): -48Vdc
350A Red
Connector
DC Source or
+ from
NetSure ITM DC UPS
- (field cut)
Typical
Rack PDU
Bottom View
2.2
DC Input Cable Assembly
(factory supplied and connected)
(6’ Cable)
Customer provided cables
Input Quick
to output circuit breaker or fuse
Connect Kit*
of a NetSure ITM DC UPS
(separately ordered)
or other DC source.
(includes Red
housing and
*547668 (Red housing plus 1/0 contacts)
contacts)
*547669 (Red housing plus 2/0 contacts)
*547670 (Red housing plus 3/0 contacts)
*547671 (Red housing plus 4/0 contacts)
Connecting the Rack PDU’s DC Output to Customer Equipment
The Rack PDU’s output circuit breakers are connected to customer equipment via the separately
ordered output cable assemblies. A ground lead is also supplied with each output cable. Each ground
lead is terminated with a connector on one end (which mates with a connector on a ground wire factory connected to the "Ground Lead Bracket") and left unterminated on the other end. See Figure 4.
Figure 4
DC Output Connections
Red/Black
Connector
(P/O Cable Assy.)
Ground Lead
Bracket
Red/Black
Connector
(P/O PDU)
+
GND
+
GND
to
Customer
Equipment
+
GND
+
GND
+
GND
Factory
Connected to
Ground Wire Bracket
Ground
Output Leads
Leads
+
GND
DC Output Cable Assembly
(separately ordered)*
(ground wires shipped loose w/ PDU’s)
OBSERVE CORRECT POLARITY
Red Connector To Red Connector
Black Connector To Black Connector
Red (-): -48Vdc
Black (+): Ground Return
PDU Model
L6
M6
L15
H2
H3
L6
M6
L15
DC Output Cable P/N*
547595
547595
547595
547613
547613
555654
555654
555654
4
Wire Size/Length
10 AWG / 6’
10 AWG / 6’
10 AWG / 6’
6 AWG / 4’
6 AWG / 4’
10 AWG / 10’
10 AWG / 10’
10 AWG / 10’
Connector Rating
45A
45A
45A
75A
75A
45A
45A
45A
Typical PDU
Side View
Electrical Connections
2.3
Connecting External Circuit Breaker Alarms
Negative 48Vdc is provided to a set of alarm terminals if any circuit breaker is in the OFF position.
See Figure 5.
Figure 5
Alarm Connections
Circuit Breaker Alarm Connector
(mating screw-type connector supplied,
wire size range 16-24 AWG,
recommended torque 1.8 in-lbs)
Typical
Rack PDU
Bottom View
-48Vdc signal provided
to both terminals when
any circuit breaker is
in the OFF position.
Typical interconnections when
“daisy-chaining” multiple Rack PDUs.
-48Vdc alarm signal (out)
(to ACU+ Controller in a NetSure ITM DC UPS
or Customer Monitoring Equipment)
When used with a NetSure™ ITM DC UPS, refer to Section 6040
(NetSure ITM Installation Instructions) for circuit breaker alarm
connections to the ACU+ Controller.
When used with other monitoring equipment, refer to the
instructions supplied with this equipment.
5
Specifications and Technical Data
3.0
SPECIFICATIONS AND TECHNICAL DATA
3.1
Conformity and Standards
The NetSure RDB Rack PDU (Power Distribution Unit) has the following agency approval ratings:
• UL 60 950-1 + UL 1801 - Recognized (cURus)
3.2
Environmental Characteristics
The NetSure RDB Rack PDU (Power Distribution Unit) is designed to operate under the following
environmental conditions without damage or degradation in electrical operating characteristics:
3.3
Operating Temperature
-40°F to +104°F (-40°C to +40°C) (Models L6 and L15).
-40°F to +113°F (-40°C to +45°C) (Models H2, H3, and M6).
Storage Temperature
-40°F to +176°F (-40°C to +80°C).
Relative Humidity
0 to 95%, non-condensing.
Operating Elevation
6562 ft (2000m) at full power.
Specifications
Model
Part
Number
Number
of
Outlets
Max Amps1
Max kW
Max Amps1
420
10
2.5
60
630
15
3.8
90
547499
840
20
5.0
120
547694
420
10
6.3
150
630
15
8.42
2002
547615
840
20
8.42
2002
547696
1050
25
6.3
150
1260
30
7.6
180
1470
35
8.42
2002
3360
80
6.7
160
2100
50
6.3
150
2520
60
7.6
180
2940
70
8.42
2002
547692
L15
M6
547693
547695
547697
6
15
6
547503
H2
547500
2
547698
H3
Power Rating per PDU
Max Watts
RDB - Basic Rack PDUs
L6
Power Rating per Outlet
547699
547501
3
1
Max Amps rated at end of battery discharge (42V).
2
PDU power rating limited to 200A, 8.4kW each.
6
Input/Output
Voltage
(nominal)
-48Vdc
Specifications and Technical Data
3.4
Dimensions
3.4.1
NetSure™ RDB L6, P/Ns 547692, 547693, 547499
Notes:
1. Dimensions are in inches (millimeters),
unless otherwise specified.
2. Includes hardware to mount PDU
to IT rack or bracket P/N 547604.
3. Rack PDU and/or Ground Lead Bracket
can be mounted either as shown or
180 degree rotate.
4. Six outlets.
Factory Connected to
Ground Lead Bracket
Jumper Length: 3 (76)
10 AWG Cable
Tyco Electronics
Mate-N-Lok Connector, 350866-1
with 350922-3 male pin
Detail A, Ground Lead Jumper
3.10
(78.74)
Top View
0.40
(10.16)
3.00
(76.20)
0.28 (7.11) x 0.50 (12.70)
slot
15.06
(383.03)
DC Output
Cable Assembly
P/N 547595 or P/N 555654
(separately ordered,
see 3.6.1)
15.88
(403.35)
Ground wires
factory connected to
Ground Lead Bracket.
(ground wires not shown)
See Detail A.
Local Circuit Breaker
Open Alarm Indicator
0.28 (7.11) dia.
1.25
(31.75)
Front View
Left Side View
Circuit Breaker Alarm Connector
(mating screw-type connector supplied,
wire size range 16-24 AWG,
recommended torque 1.8 in-lbs)
Right Side View
DC Input Cable Assembly
(factory supplied and connected)
See Detail B.
Bottom View
1/0 AWG Cables
72
(1828.80)
Detail B, DC Input Cable Assembly
7
350A Anderson, PP350
Powerpole Connector,
Red
Specifications and Technical Data
3.4.2
NetSure™ RDB L15, P/Ns 547694, 547695, 547615
Factory Connected to
Ground Lead Bracket
Notes:
1. Dimensions are in inches (millimeters),
unless otherwise specified.
2. Includes hardware to mount PDU
to IT rack or bracket P/N 547604.
3. Rack PDU and/or Ground Lead Bracket
can be mounted either as shown or
180 degree rotate.
4. Fifteen outlets.
Jumper Length: 3 (76)
10 AWG Cable
Tyco Electronics
Mate-N-Lok Connector, 350866-1
with 350922-3 male pin
Top View
Detail A, Ground Lead Jumper
3.10
(78.74)
0.40
(10.16)
3.00
(76.20)
0.28 (7.11) x 0.50 (12.70)
slot
30.83
(783.08)
31.63
(803.40)
DC Output
Cable Assembly
P/N 547595 or P/N 555654
(separately ordered,
see 3.6.1)
Ground wires
factory connected to
Ground Lead Bracket.
(ground wires not shown)
See Detail A.
Local Circuit Breaker
Open Alarm Indicator
0.28 (7.11) dia.
1.25
Front View (31.75)
Left Side View
Circuit Breaker Alarm Connector
(mating screw-type connector supplied,
wire size range 16-24 AWG,
recommended torque 1.8 in-lbs)
Right Side View
DC Input Cable Assembly
(factory supplied and connected)
See Detail B.
Bottom View
1/0 AWG Cables
72
(1828.80)
Detail B, DC Input Cable Assembly
8
350A Anderson, PP350
Powerpole Connector,
Red
Specifications and Technical Data
3.4.3
NetSure™ RDB M6, P/Ns 547696, 547697, 547503
Notes:
1. Dimensions are in inches (millimeters),
unless otherwise specified.
2. Includes hardware to mount PDU
to IT rack or bracket P/N 547604.
3. Rack PDU and/or Ground Lead Bracket
can be mounted either as shown or
180 degree rotate.
4. Six outlets.
Factory Connected to
Ground Lead Bracket
Jumper Length: 3 (76)
10 AWG Cable
Tyco Electronics
Mate-N-Lok Connector, 350866-1
with 350922-3 male pin
Top View
Detail A, Ground Lead Jumper
3.10
(78.74)
0.40
(10.16)
3.83
(97.28)
0.28 (7.11) x 0.50 (12.70)
slot
Ground wires
factory connected to
Ground Lead Bracket.
(ground wires not shown)
See Detail A.
15.08
(383.03)
DC Output
Cable Assembly
P/N 547595 or P/N 555654
(separately ordered,
see 3.6.1)
15.88
(403.35)
Local Circuit Breaker
Open Alarm Indicator
0.28 (7.11) dia.
1.70
(43.18)
Front View
Left Side View
Circuit Breaker Alarm Connector
(mating screw-type connector supplied,
wire size range 16-24 AWG,
recommended torque 1.8 in-lbs)
Right Side View
DC Input Cable Assembly
(factory supplied and connected)
See Detail B.
Bottom View
1/0 AWG Cables
72
(1828.80)
Detail B, DC Input Cable Assembly
9
350A Anderson, PP350
Powerpole Connector,
Red
Specifications and Technical Data
3.4.4
NetSure™ RDB H2, P/N 547500
Notes:
1. Dimensions are in inches (millimeters),
unless otherwise specified.
2. Includes hardware to mount PDU
to IT rack or bracket P/N 547604.
3. Rack PDU and/or Ground Lead Bracket
can be mounted either as shown or
180 degree rotate.
4. Two outlets.
Factory Connected to
Ground Lead Bracket
Jumper Length: 3.25 (83)
8 AWG Cable
Anderson, PP75
Powerpole Connectors
Detail A, Ground Lead Jumper
3.31
(84.07)
3.39
(86.12)
Ground wires
factory connected to
Ground Lead Bracket.
(ground wires not shown)
See Detail A.
Top View
0.35
(8.89)
0.28 (7.11) x 0.38 (9.65)
slot
DC Output
Cable Assembly
P/N 547613
(separately ordered,
see 3.6.1)
9.83
(249.68)
10.56
(268.22)
Local Circuit Breaker
Open Alarm Indicator
0.28 (7.11) dia.
1.13
(28.70)
Front View
Left Side View
Right Side View
Circuit Breaker Alarm Connector
(mating screw-type connector supplied,
wire size range 16-24 AWG,
recommended torque 1.8 in-lbs)
DC Input Cable Assembly
(factory supplied and connected)
See Detail B.
Bottom View
1/0 AWG Cables
72
(1828.80)
Detail B, DC Input Cable Assembly
10
350A Anderson, PP350
Powerpole Connector,
Red
Specifications and Technical Data
3.4.5
NetSure™ RDB H3, P/Ns 547698, 547699, 547501
Notes:
1. Dimensions are in inches (millimeters),
unless otherwise specified.
2. Includes hardware to mount PDU
to IT rack or bracket P/N 547604.
3. Rack PDU and/or Ground Lead Bracket
can be mounted either as shown or
180 degree rotate.
4. Three outlets.
Factory Connected to
Ground Lead Bracket
Jumper Length: 3.25 (83)
8 AWG Cable
Anderson, PP75
Powerpole Connectors
Detail A, Ground Lead Jumper
3.39
(86.12)
Ground wires
factory connected to
Ground Lead Bracket.
(ground wires not shown)
See Detail A.
Top View
3.31
(84.07)
0.34
(8.64)
0.28 (7.11) x 0.38 (9.65)
slot
DC Output
Cable Assembly
P/N 547613
(separately ordered,
see 3.6.1)
9.87
(250.70)
10.56
(268.22)
Local Circuit Breaker
Open Alarm Indicator
0.28 (7.11) dia.
1.73
(43.94)
Front View
Left Side View
Right Side View
Circuit Breaker Alarm Connector
(mating screw-type connector supplied,
wire size range 16-24 AWG,
recommended torque 1.8 in-lbs)
DC Input Cable Assembly
(factory supplied and connected)
See Detail B.
Bottom View
1/0 AWG Cables
72
(1828.80)
Detail B, DC Input Cable Assembly
11
350A Anderson, PP350
Powerpole Connector,
Red
72.782
12
53.761
58.971
0.218 X 0.562 SLOT (20)
38.012
40.909
44.357
0.281 X 1.000 SLOT (14)
14.656
19.867
22.847
29.277
32.718
35.617
50.780
68.842
70.595
71.937
6.81
3.032
6.000 (TYP)
3.25
2.250
0.75
0.000
1.75 (TYP)
2.68
1.687
1.375
0.218 X 0.562 SLOT (II)
0.218 X 0.375 SLOT (4)
4.785
0.25
o 0.147+0.002 (40 PLCS)
3.39
2.70
2.02
1.33
0.64
0.000
0.845
2.56
3.69
o
R 0.062 REF
0.25 X 45 (TYP)
3.4.6
73.63
Specifications and Technical Data
NetSure™ RDB Mounting Bracket, P/N 547665
Specifications and Technical Data
3.5
Input Quick Connect Kit
Provides the mating connector and contacts for the DC Input Cable Assembly factory supplied and
connected to the Rack PDU.
P/N
Contact Size
(AWG)
547668
1/0
547669
2/0
547670
3/0
547671
4/0
Mating
Anderson
Powerpole
Connector
350A, Red
(SB350)
SB350
3.6
Output Cable Assemblies
3.6.1
P/N 547595, P/N 547613 and P/N 555654
10 AWG Cables
Tyco Electronics
Mate-N-Lok Connector, 350865-1
with 350923-3 female socket
69
(1753)
GND
unterminated end
10 AWG Cables
45A Anderson, PP45
Powerpole Connector,
Red/Black
72
(1829)
+
unterminated ends
8 AWG Cables
DC Output Cable Assembly, P/N 547595
45
(1143)
Anderson, PP75
Powerpole Connectors
GND
unterminated end
6 AWG Cables
75A Anderson, PP75
Powerpole Connector,
Red/Black
48
(1219)
+
unterminated ends
DC Output Cable Assembly, P/N 547613
Tyco Electronics
Mate-N-Lok Connector, 350865-1
with 350923-3 Female Socket
117
(2972)
10 AWG Cables
GND
unterminated Ends
45A Anderson, PP45
PowerPole Connector,
Red/Black
120
(3048)
10 AWG Cables
+
unterminated Ends
DC Output Cable Assembly, P/N 555654
Notes:
1. Dimensions are in inches (millimeters),
unless otherwise specified.
13
Specifications and Technical Data
3.6.2
Output Connector Kits (P/N 554878 and P/N 554944)
P/N 101621 for
12 - 10 AWG
P/N 247109602
for 8 AWG
P/N 111691 for
6 AWG
P/N 142992 for
14 - 10 AWG
P/N 145369 for
16 - 12 AWG
554944
554878
For use with L6, L15 and M6 RDB
Includes red and black connector
housings and contacts for 10-14 AWG,
and 12-16 AWG wire sizes.
3.7
For use with H2 and H3 RDB
Includes red and black connector
housings and contacts for 6 AWG,
8 AWG and 10-12 AWG wire sizes.
Replacement Circuit Breakers
NetSure
Rack PDU
P/N
Replacement
Circuit Breakers
P/N
547692
547694
142907 (10A)
547693
547695
142908 (15A)
547499
547615
141801 (20A)
547696
143041 (25A)
547697
143042 (30A)
547503
141802 (35A)
547698
142951 (50A)
547699
142952 (60A)
547501
142953 (70A)
547500
142955 (80A)
14
Operation
4.0
OPERATION
!
WARNING
Improper operation may cause overheating and lead to increased fire hazard.
Improper operation may also destroy the device and damage other connected
systems.
Make sure that the total input current of the connected systems does not exceed the current
rating specified on the rating plate of the Rack PDU. Please refer to the operating instructions
or the rating plates of the connected systems or the circuit breaker for power specifications.
4.1
Connecting Power to the Loads
To connect DC power to the load(s), operate the respective circuit breaker on the Rack PDU to the ON
position.
4.2
Removing Power from the Loads
To disconnect DC power from the load(s), operate the respective circuit breaker on the Rack PDU to
the OFF position.
4.3
Alarms
4.3.1
Local Alarm Indicator
Each Rack PDU contains a circuit breaker alarm indicator. This indicator illuminates Red if any circuit breaker on the Rack PDU is in the OFF position.
4.3.2
External Circuit Breaker Alarm
Negative 48Vdc is supplied to a set of terminals when any circuit breaker on the Rack PDU is in the
OFF position. These terminals may be connected to customer external alarm circuits.
15
Revision Record
5.0
REVISION RECORD
Issue
Change
Number
(ECO)
AA
LLP214446
New
AB
LLP214895
Table in 3.3 revised. Manufacturer P/Ns added to 3.5 and 3.6.
AC
LLP215438
Updated circuit breaker part number on the DC power strips and changed
hardware stack-up on the PDU.
AD
LLP215960
Updated orientation of Snap-Pak breakers and it’s connections to the following
assembly: 547499, 547692, 547693, 547615, 547694 and 547695. Added
insulator for wire connection for assembly: 547500 547501 547698 and 547699.
Updated reference about rack PDU mounting kit, rack PDU mounting bracket and
rack PDU mounting bracket dimensions. Updated RDB ground connections for
547499, 547503, 547615 and 547595.
AE
LLP217560
Update the size of ground lead jumper used for 547500,547698,547699, 547501
and update the length of ground lead jumper. Update the size of ground wire used
for 547613. Add connector kit information for 554878 and 554944.
AF
LLP217939
Add part number 555654 DC output cable assembly. Add labels to output
connector kits.
AG
LLP218160
UPdated DC output connector color.
Description of Change
16
NetPerform™ Optimization Services
At Emerson Network Power, we understand the importance of reliable equipment – it’s critical to both
your business and your bottom line. That is why we offer a wide array of services to meet all of your
network infrastructure needs.
Technical Support
Email
Phone
[email protected]
[email protected]
1.800.800.5260
Answers technical product and system
questions; determines status of warranties and
contractual agreements for repair.
Services - Design, Deployment & Optimization
Email
[email protected]
Phone
1.800.800.1280, option 7
FreedomCare Secure.EmersonNetworkPower.com
Provides quotes and bid responses, order
placement and scheduling for design, and
deployment and optimization services.
Download service & maintenance reports
online.
Spare Parts
Email
Phone
[email protected]
[email protected]
1.800.800.1280, option 5
Pricing and PO processing of spare parts,
including but not limited to breakers, cables,
fuses, rectifier fans, misc. breaker and fuse
panels, enclosure fans, doors & switches, etc.
DC Power Depot Repair
Email
[email protected]
Phone
1.800.800.1280, option 6
Creates and processes RMAs, determines lead
times and pricing, provides repair shipping
information and status.
DC Power Product Training
Email
Phone
[email protected] Requests for quotes, order placement and
scheduling.
1.800.800.1280, option 8
For More Information
To learn more about service offerings from Emerson Network Power, please contact your sales
representative, call 1-800-800-1280 option 7, email [email protected] or visit
www.EmersonNetworkPower.com/EnergySystems.
Emerson (NYSE: EMR), based in St. Louis, Missouri (USA), is a global leader in bringing technology and engineering
together to provide innovative solutions for customers in industrial, commercial, and consumer markets through its
network power, process management, industrial automation, climate technologies, and tools and storage businesses.
For more information, visit: Emerson.com.
Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™
from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network
Power provides innovative solutions and expertise in areas including AC and DC power, precision cooling, embedded
computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and
connectivity. All solutions are supported globally by local Emerson Network Power service technicians. For more
information on Emerson Network Power’s full suite of solutions specifically supporting the communications network
infrastructure, including NetSpan™, NetReach™ and NetXtend™ outside plant enclosures and equipment, NetSure™ DC
power systems, and NetPerform™ Optimization, Design & Deployment services, visit:
EmersonNetworkPower.com/EnergySystems.
.
Learn more about Emerson Network Power products and services at: EmersonNetworkPower.com.
Emerson Network Power
Energy Systems, North America
4350 Weaver Parkway, Warrenville, IL 60555
Toll Free: 800-800-1280 (USA and Canada)
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems
EnergyNet: Secure.EmersonNetworkPower.com
Emerson Network Power.
The global leader in enabling Business-Critical Continuity™ .
AC Power
Connectivity
DC Power
EmersonNetworkPower.com
Embedded Computing
Embedded Power
Outside Plant
Power Switching & Controls
Racks & Integrated Cabinets
Services
Infrastructure Management & Monitoring
Precision Cooling
Surge Protection