Chloride Linear Plus

Secure Power Always
Linear Plus-T 6 kVA and 10 kVA
Uninterruptible Power Supply
Secure Power Always
Linear Plus-T 6 kVA and 10 kVA
Chloride's Linear Plus-T family is available in 6 kVA and 10 kVA single-phase output
tower units. Incorporating modern double conversion technology, an attractive
design and multiple system integration capabilities, the Linear Plus family offers
the most efficient all-round protection against all types of disturbances and
problems in the mains supply system.
Leading Technology
Linear Plus-T uses double conversion technology
to provide a secure power architecture for your
mission critical applications. This option ensures
the highest level of voltage and frequency
regulation and may be the only practical
alternative for environments where the
quality of the mains electricity is low.
• Real-time diagnosis of all UPS operating
parameters
• Remote fix capability
• Monthly UPS operational status reports
• Unique ETS function for trouble shooting the
most common operating anomalies
• Power quality monitoring to effectively
manage power disturbance trends.
Low-impedance isolation transformer at
output:
An output transformer installed inside the
cabinet makes it possible to:
• Set the nominal output voltage at
120/208/240 Volt
• Provide power conditioned protection
to the loads
• Protect equipment from surges and
noise
• Ensure clean ground reference.
Communication interface
The Linear Plus series shall be equipped with
a standard COM interface (RS232) and a
slot bay for optional connectivity cards.
Paralleling
Up to three Linear Plus-T UPS can be
paralleled for capacity and redundancy,
increasing the supported equipment’s overall
reliability and availability.
Users are advised to follow carefully the
installation guidelines enclosed with the
accessories.
Scalable autonomy
Easily replaceable batteries allow the simple
swap out of batteries without interruption to
the secured system. UPS runtimes can be
expanded by adding extra battery cabinets.
Available interface cards to be fitted in the
slot include:
• SNMP-Adapter (ManageUPSNET) for
connecting the device to a network
• LIFE.net adapter for remote monitoring
• Voltage-free contact adapter.
Applications
• Network & VoIP Protection/departmental
information systems in decentralised
environments
Control panel
Linear Plus-T shall be equipped with a control
panel comprising of a four language LCD
display for complete UPS monitoring and
control. The text shall be available in English,
German, Portuguese and Spanish.
Complete access to all LCD menus is
possible through navigation push buttons
located below the screen.
LIFE.net Monitoring
The Linear Plus family is fully compatible with
LIFE.net, Chloride's remote monitoring tool.
LIFE.net is the nearest thing to having a
Chloride engineer permanently onsite and
provides:
• Continuous real-time UPS monitoring
• Automatic transmission of daily status reports
Block Diagram (120/208/240 Volt output).
• Medical Equipment, IT Systems, diagnostic
equipment, clinical laboratories and monitoring
support systems
• Industrial environments such as process
control equipment
• LAN / WAN Servers & IT rooms
• Bank branches.
Secure Power Always
Supplying you with a UPS alone will never
deliver the level of business continuity you
require. Chloride offers a range of maintenance
plans which will:
• Help deliver reliability to your load
• Extend the life of your power protection
equipment
• Optimise your capital expenditure
• Provide risk management at a fixed cost
• Help to control your business environment
• Generate a proactive approach to
disaster recovery.
Contact your local Chloride sales office for
more information.
Delegate your power management to the
experts.
6/11
10/11
INPUT
Number of phases
1
Voltage (V)
1
200/208/220/230/240
Tolerance (V)
176-276
176-276
Frequency (Hz)
50/60
50/60
Power factor
>0.97
>0.97
Input current distorsion (%)
<5
<5
Number of phases
1
1
Nominal power rating @ 40°C (kVA)
6
10
Nominal active power rating (kW)
4.2
7
Voltage (V)
120/208/240
120/208/240
OUTPUT
Frequency (Hz)
50/60
50/60
Power factor
0.7
0.7
Output current @ 208V (Arms)
28.8
48.1
Output current @ 120V (Arms)
50.0
83.3
Overload 104%
Warning
105-125%
Transfer to bypass after 60 seconds
126-150%
Transfer to bypass after 10 seconds
150-300%
Transfer to bypass after 2 seconds
Output voltage dynamic variation due to load changes (%)
±2
Output waveform
sinusoidal
Output harmonic distortion
±2
sinusoidal
IEC/EN 62040 - 3 Compliant
BATTERIES
Optimum battery temperature (°C)
15-25
Charging current (A)
1.2
Number of Batteries
20
End of discharge voltage (Vdc)
200
UPS DATA
Operating temperature (°C)
0 - 40
0 - 40
Colour
RAL 7016
RAL 7016
Max. noise levels at 1 metre (dBA)
<50
<50
AC/AC efficiency (%)
>86
>86
Communication slot
1 for SNMP adapter, Voltage-free contact adapter, LIFE.net adapter
Standard communication interfaces
1 x RS 232
1 x RS 232
Height (mm)
800
800
Width (mm)
300
300
DIMENSIONS
Depth (mm)
675
675
UPS weight (kg) (without batt.)
71
101
UPS weight (kg) (with internal batt.)
148
Degree of protection
Safety standard
173
IP 20
UL-1778C/UL IEC/EN62040-1-1
www.chloridepower.com
This publication is issued to provide outline information only and is not deemed to form any part of any offer and/or contract. The company has a policy of continuous product development and improvement, and we therefore reserve the right to vary any information
without prior notice. MKA4L0UKLINPT Rev. 2-11/2007
Linear Plus-T
Chloride UPS Systems HQ
WORLD HEADQUARTERS
Via Fornace 30
40023 Castel Guelfo (BO)
Italy
T +39 0542 632 111
F +39 0542 632 120
E [email protected]
Closest Chloride Contact in Australia:
Chloride Power Protection
Ground Floor
16 Giffnock St, North Ryde
NSW 2113
Australia
Closest Chloride Contact in UAE:
Chloride UPS Systems Middle East
Building 5, Office 104
Dubai Internet City - Dubai
UAE
PO Box 72536
T +61 2 9888 1266
F +61 2 9888 1966
E [email protected]
T +971 4 391 3205
F +971 4 391 6803
E [email protected]
www.chloridepower.com/au
www.chloridepower.com/middle-east
Closest Chloride Contact in UK:
Chloride Power Protection
George Curl Way
Southampton, Hampshire
SO18 2RY
United Kingdom
Closest Chloride Contact in USA:
Chloride Power Protection
27944 North Bradley Road
Libertyville
IL 60048
USA
T +44 (0) 23 8061 0311
F +44 (0) 23 8061 0852
E [email protected]
T +1 800 239 2257
F +1 800 833 6829
E [email protected]
www.chloridepower.co.uk
www.chloridepower.com/us
For a full list of contacts please visit our website at www.chloridepower.com
Certificate No. EMS 76732 Certificate No. FM 11043
MKA4L0UKLINPT
www.chloridepower.com