Chloride 60-NET Brochure

Secure Power Always
60-NET from 10 to 20 kVA
Uninterruptible power supply
Secure Power Always
60-NET from 10 to 20 kVA
Chloride’s 60-NET offers an excellent integrated autonomy of up to 30
minutes, combined with a reduced footprint and optimum input
performances, making it the best solution in its power range.
Performances in real ratings 10-20 kVA
60-NET provides electrical continuity
upon failure or degradation of the
commercial AC source as a result of its
intelligent double conversion architecture
(Figure 1) with a DSP-based IGBT
inverter. This allows reliable filtering of
the mains network disturbances and
provides stable interference-free power
to the load, in turn ensuring a clean and
regulated output sine wave.
Equipped with an independent static
bypass switch, 60-NET guarantees power
system redundancy and continuity, while
its enhanced connectivity suite, safe
disconnection features and parallelability
ensure complete load protection.
BYPASS FOR MAINTENANCE
Bypass
STS
MAIN II
Line
MAIN I
Rectifier
Booster
Inverter
AC
DC
DC
DC
DC
=
OUPUT
AC
N
= Charger
N
Battery
60-NET provides reliable and secure
power
protection
to
electronic
equipment loads by stocking up on high
quality AC power and offering the
following features:
• IGBT intelligent double conversion
technology
• Excellent input performances:
• PF > 0.99
• THDi < 5%
• Inverter overload capability:
• 125% for 10 min
• 150% for 1 min
• High conversion efficiency (certified up
to 98%)
• Full compatibility with any installation
irrespective of the PF (leading or
lagging)
• Minimised footprint, easy installation
and maintenance
• Battery care
• Excellent backup time
Figure 1. Single block diagram.
Parallel ready
Automatic AC Bypass
60-NET is able to connect up to eight units in parallel without the
need for an additional parallel board (Figure 2), thus allowing
maximum power reliability and flexibility. A single unit can be
upgraded to parallel by using a simple cable.
AC
Normal
AC
Normal
AC
Normal
AC
Normal
AC
Normal
AC
Normal
AC
Normal
AC
Normal
The Loop Bus connection used in paralleling the system allows
for prompt communication and eliminates the possibility of a
single point of failure.
Parallel features:
• Modular parallel redundant configurations N+1
• Modular parallel scalable configurations, allowing on-site
power increase.
Load
Figure 2. Parallel configuration of power extension and redundancy.
Performance and Service
60-NET guarantees reliable and flexible secure power by adapting its
performances to meet individual infrastructure requirements, making it ideal
for a wide range of applications from IT and manufacturing to finance and retail.
Flexibility and compatibility for customised solutions
60-NET is flexible enough to meet any
power, redundancy, harmonic control and
battery backup time requirements as a
result of:
• Optimised trade-off between harmonic
rejection and efficiency
• Optimised load sharing between
parallel connected UPS systems and
enhanced performances for unbalanced
load conditions
• Output Power Factor diagram symmetrical
with respect to zero, up to 0.8 lagging
and leading
• Full compatibility with CROSS, Chloride’s
static transfer switch, which provides
additional protection against potential
interruptions in the power distribution
system by immediately switching to
an alternative source in the event of
a fault.
Quality standard and environmental sustainability
Efficiency (%)
60-NET is designed and manufactured
in accordance with the following
standards:
• IEC/EN62040-1-1 general and safety
requirements
• EN62040-2 EMC requirements
• IEC/EN62040-3 performance requirements
60-NET also respects the RoHS
environmental directives and carries the
TUV quality mark.
60-NET's battery care system is designed
to minimise environmental impact by
lengthening the battery life and increasing
battery efficiency.
With an overall efficiency of up to 98%,
60-NET allows for excellent energy savings
and reduced air conditioning in all types of
working conditions, even at partial loads, with
significant energy savings.
Serviceability
The modular architecture of 60-NET optimises service
intervention, as its internal modules can be easily accessed
by extracting the individual drawers from the front of the UPS.
All sub-assemblies have been designed to allow simplified
service and maintenance to be carried out, as well as
significantly reducing the Mean Time to Repair (MTTR)
of individual modules. 60-NET also comes complete with
casters to facilitate ease of movement and relocation.
60-NET complies with the IP 21 standard.
98
0
50
75
100
Load (%)
Figure 3. 60-NET efficiency curve.
Connectivity and Monitoring
Communication
60-NET features a back-lit multilingual
LCD display, allowing complete access
to all UPS functions and guaranteeing
easy interaction with the UPS through
the user-friendly navigation menu.
The UPS is suitable for use in any
building management system and offers
the following communication interfaces:
• Voltage-free interface for overseeing
functions offered by the AS400 system
• Serial interface
• Slot for LIFE.net or ManageUPSNET cards
• External battery temperature monitoring
connector
• EPO input for emergency UPS shutdown
• Backfeed contact which activates an
external isolating device if the UPS
detects a backfeed current over the bypass
in battery mode*. In compliance with
IEC/EN 62040-1-1.
* The external isolating device must be
provided by the customer.
Hardware Connectivity
ManageUPSNET ensures the monitoring
and control of the networked UPS
through the TCP/IP protocol allowing:
• UPS monitoring from NMS via SNMP
• UPS monitoring from PC via a web
browser
• Dispatch of e-mail notifications
• Monitoring of environmental installation
conditions
• Possibility of integrating Chloride UPS
systems with Building Monitoring and
Automation Systems via MODBUS RTU,
MODBUS/TCP or JBUS protocols.
system in the event of a load interruption.
MopUPS can also provide event logging
and automatic communication of events
through e-mail, SMS and other notification
tools.
ManageUPS CIO software provides a
central management system for critical
power infrastructures distributed within a
building, campus or wide area network
environment.
Software Connectivity
• MopUPS Professional
• ManageUPS CIO
The main function of MopUPS software is
the safe shutdown of the operating
LIFE.net 24x7 remote diagnostic system
Installation is only the beginning of your relationship with Chloride as it is essential that your critical
power protection system is maintained in an optimum state of readiness at all times. The innovative
range of maintenance and support services available from Chloride ensure reliability for life-long
protection. Chloride takes responsibility for the health of your UPS units 24 hours per day.
The LIFE cycle
LIFE.net is the maintenance program which includes the remote diagnosis, monitoring and
management of the operational status of UPS and power distribution systems. LIFE.net provides early
warning of any alarm condition or out of tolerance status, allowing effective proactive maintenance
and fast incident response, giving customers complete security and peace of mind.
Maximise
availability
Minimise
downtime
Reduce
operating costs
Pre-emptive maintenance
LIFE.net provides early warning of
the UPS parameters, allowing realtime diagnosis and prompt identification and resolution of operating
anomalies.
Immediate identification of problems
Should an emergency condition arise, a
Chloride engineer in the 24x7 manned
service centre carries out an immediate
fault analysis and instigates appropriate
corrective action.
Superior asset management
Through comprehensive data collection
and analysis, LIFE.net’s detailed reporting
system provides valuable information on
power and equipment trends, over any
selected period of time.
www.chloridepower.com
60-NET
TECHNICAL CHARACTERISTICS
Nominal primary mains input voltage
Input Phases
Input voltage tolerance @ full load
Nominal Frequency
Primary input Power Factor
Input current distortion (THDi)
Inrush current
BATTERY CHARGER
Battery nominal voltage
Output voltage
Battery ripple current
Output current
INVERTER
Nominal output power at 40° C
Nominal active power
Power Factor
Overload capacity
for 10 minutes
for 1 minute
Short circuit current
300% @ 50 Hz
200% @ 50 Hz
Nominal output voltage
Output frequency (nominal)
Output voltage stability by load
variation 0 - 100% (static-dynamic)
Output frequency variation with mains synchronization
with internal reference
Compatibility with loads
Output voltage distortion
Linear full load (%)
Non Linear full load
Load peak factor without derating
Neutral conductor sized up to
STATIC SWITCH
Voltage rating
Frequency (nominal)
Frequency tolerance
Voltage tolerance
Overload capacity
for 10 minutes
for 1 minute
In-phase switching mode bypass/inverter
inverter/bypass
UPS DATA
No load dissipated power
Maximum dissipated power
10
(V)
15
(%)
(A)
400
3 Ph + N
-25/+15
40 - 70
>0.99
<5
< I input max
(V)
(V)
(%)
(A)
± 180V
± 202.5V
<2
5
(%)
(Hz)
(kVA)
(kW)
10
8
(%)
(%)
(ms)
(s)
(V)
(Hz)
(%)
(%)
(%)
(Ipk/Irms)
15
12
0.8
125
150
5
4
400/380
50/60
20
16
±1 Complies with IEC/EN 62040-3, Class 1
± 2 (1, 3, 4 selectable)
± 0.1
Any power factor (leading or lagging) up to 0.8 without output derating
<2
Complies with IEC/EN 62040-3
3
1.6 I out nominal
(V)
(Hz)
(%)
(%)
(%)
(%)
400/380
50/60
±2
± 10
125
150
(ms)
Make before break (0ms)
(W)
Float (W)
Recharge (W)
AC/AC efficiency DIM* mode 100% of load
(%)
AC/AC efficiency double conversion mode 100% of load
(%)
Maximum noise level @ 1 metre
(dBA)
EMC class
62040-2
Degree of Protection
Classification according to IEC/EN 62040-3
Frame colour
Cooling
Equipment mobility
Parallel configuration
ENVIRONMENTAL
Operating temperature
(°C)
Recommended battery temperature
(°C)
Maximum relative humidity @ 20 °C (without condensation)
(%)
Elevation without derating
(-1.2 Pn every 100m above 1000m up to 3000m)
(m)
DIMENSIONS AND WEIGHT
Height
(mm)
Width
(mm)
Depth
(mm)
UPS weight without batteries
(kg)
*Conditions apply
20
800
1000
300
1200
1400
98
92
50 ± 2
Class C2
IP21
VFI - SS - 111
RAL 7016
Forced
On casters
up to 8 units
1500
1800
0 - 40
+15 - +25
95
1000
118
1240
420
635
122
122
This publication is issued to provide outline information only and is not deemed to form any part of any offer and/or contract. The company has a policy of continuous product development and improvement, and we therefore reserve the right to vary any information
without prior notice. MKA4L0UK60NET REV.2 - 02/2010
Technical Data
Chloride Systems
WORLD HEADQUARTERS
Via Fornace 30
40023 Castel Guelfo (BO)
Italy
T +39 0542 632 111
F +39 0542 632 120
E [email protected]
www.chloridepower.com
Chloride operates through a worldwide network of Chloride sales and service offices and
joint ventures, with operations across 80 countries including:
Almaty, Kazakhstan
Bangkok, Thailand
Beijing, China
Makati City, Philippines
Bologna, Italy
Buenos Aires, Argentina
Chicago, USA
Dubai, UAE
Erlangen, Germany
Ho Chi Minh City, Vietnam
Lisbon, Portugal
Istanbul, Turkey
Madrid, Spain
Moscow, Russia
Paris, France
Pune, India
Diadema, Brazil
Shanghai, China
Singapore
Southampton, UK
Sydney, Australia
Warsaw, Poland
• Principal sales & service offices
• Service network
Chloride Australia
Ground Floor, 16 Giffnock Avenue
North Ryde
NSW 2113
Australia
Chloride Middle East
Arenco Tower, Office 608
Dubai Internet City - Dubai
UAE
PO Box 72536
Chloride Secure Power Philippines, Inc.
7F Y-L Finance Building,
Corner of Rufino & Salcedo Streets
Legaspi Village, Makati City
Philippines
CHLD Singapore Pte Ltd
2 Corporation Road
#03-07 Corporation Place
Singapore
618494
T +61 2 9888 1266
F +61 2 9888 1966
E [email protected]
T +971 4 434 5201
F +971 4 430 8032
E [email protected]
T +63 2 810 0068
F +63 2 812 0433
E [email protected]
T +65 6481 4776
F +65 6481 0552
E [email protected]
www.chloridepower.com.au
www.chloridepower.com/middle-east
www.chloridepower.com
www.chloridepower.com.sg
Chloride UK
George Curl Way
Southampton
Hampshire, SO18 2RY
United Kingdom
Chloride North America
27944 North Bradley Road
Libertyville, IL 60048
USA
Chloride Power Protection Limited
1093/98-99 M. 12 Central City Tower 1
18th floor, Bangna-Trad Road (K.M.3)
Bangna, Bangkok 10260
Thailand
Eltek UPS AB
Hammarbacken 4A,
191 24 Sollentuna
Sweden
T +1 847 816 6000
+1 800 327 8801
F +1 847 680 5124
E [email protected]
www.chloridepower.co.uk
www.chloridepower.com/usa
T +66 2762 3600
F +66 2745 6618
E [email protected]
www.chloridepower.com/th
For a full list of contacts please visit our website at www.chloridepower.com
T +84 8 255 6737
F +84 8 255 6800
www.chloridepower.com/vn
T +46 8 626 64 20
F +46 8 626 64 30
E [email protected]
www.eltekups.se
MKA4L0UK60NET
T +44 (0) 23 8061 0311
F +44 (0) 23 8061 0852
E [email protected]
Chloride Vietnam
Unit 1708, 17th Floor, Gemadept Tower
06 Le Thanh Ton Street
Ben Nghe Ward, District 1
Ho Chi Minh City
Vietnam