Chloride Exond Apodys inverter

Secure Power Always
Exond Apodys - DC/AC inverter from 2.5 kVA to 320 kVA
DC/AC inverter
Secure Power Always
Exond Apodys - DC/AC inverter from 2.5 kVA to 320 kVA
The Exond Apodys range of industrial inverters converts a DC input voltage into a
perfect sinusoidal output voltage to provide power supply to AC loads. This range
is available as standard from 2.5 to 250 kVA in single phase output configuration,
and up to 320 kVA in three-phase output configuration.
Flexibility for customised solutions
Reliability and accessibility
Applications
Exond Apodys is fully adaptable to changes in
Exond Apodys provides lasting secure power
The Exond Apodys range delivers a clean and
electrical load. A full range of additional options
architecture for your industrial applications
stable 1-phase or 3-phase power supply to
is available to provide tailored industrial solutions:
thanks to:
critical industrial applications such as:
• AC distribution board
• System lifetime of at least 20 years in
• Equipments in power generation plants
• Redundant ventilation
• Modular or centralised parallel configurations
• Up to IP54 external protection.
continuous operation conditions
• Continuous operation at full load in a
permanent 40°C ambient temperature
• Robust mechanical design (vertical and
• Monitoring and control systems as well as
automation systems
• Safety systems
• Electrical process in oil platforms and
For special configurations where a reserve
horizontal acceleration stress up to 0,5g)
supply is needed to secure the load on the
• High clearance capacity to eliminate short-
output of the inverter, the following solutions
circuits downstream the inverter (short-circuit
Secure Power Always
can be designed:
withstanding of 250% of nominal rating)
In order to reach the highest level of
• Integration of the static switch into the
• Front access to the main components,
business continuity, Chloride offers a range
inverter cabinet to ensure the automatic
reducing MTTR and easing maintenance
of maintenance plans, which will:
transfer on the reserve supply
operations.
• Help deliver reliability to your load
• Monitoring of the reserve supply voltage
• Additional reserve transformer to adapt the
refineries.
• Increase the lifetime of your power
Communication
protection equipment
reserve supply voltage to the inverter
Exond Apodys uses intuitive multilingual
• Optimise your capital expenditure
output voltage
digital graphic control, meaning system
• Provide risk management at a fixed cost
• Additional reserve stabiliser to control the
status, measurements and alarms are
• Provide a pro-active approach to disaster
reserve supply voltage within tolerance limits.
accessible from the front panel of the inverter.
recovery.
The embedded “Event Log” function allows
Exond Apodys inverters are also available
the user to trace the last 100 events.
For more information please contact your
with 400 VDC input. This configuration allows
Event memory is activated from the
local Chloride sales office
us to combine this inverters range with the
appearance of the very first event.
Excel Apodys battery chargers range in order
RS232, RS485 and voltage-free contacts
Delegate your power management to the
to design specific high ratings double
allow the monitoring of the inverter on
experts.
conversion AC UPS systems (up to 500 kVA).
SCADA systems.
Leading technology
Remote diagnosis
Chloride employs patented Vector Control
The Apodys family is fully compatible with
technology to increase the power components
LIFE.net, Chloride’s remote diagnostic service,
performances and to provide active conditioning
which provides:
of the load. The result is improved reliability for
• Continuous real time UPS monitoring
processes and enhanced safety for personnel,
• Regular transmission of an operating status
even in the harshest operating environments.
report
The innovative modular assembly of Exond
• UPS performance analysis
Apodys allows us to satisfy the most
• Power quality monitoring to analyse mains
demanding international project schedules.
disturbance trends.
2.5
5
7.5 10 15 20
Output type
25 30 40 50
60
80
One-phase output
100 120 160 200 250 320
Three-phase output
Input DC voltage (VDC)
110
110
220
220
110
110
220
220
Output AC voltage (VAC)
1 x 110
1 x 230
1 x 110
1 x 230
3 x 220
3 x 400
3 x 220
3 x 400
2.5 - 120
2.5 - 120
10 - 120
10 - 250
5 - 160
5 - 200
10 - 250
10 - 320
Available range of ratings (kVA)
TECHNICAL CHARACTERISTICS
INPUT
Nominal DC voltage (VDC) / tolerance (%)
110 ; 220 / + 18 / -20
OUTPUT
Nominal AC voltage (VAC) / frequency (Hz)
1 x 110 (120) ; 1 x 230 (220, 240) / 50 (60)
3 x 220 ; 3 x 400 (380, 415) / 50 (60)
Available ratings (kVA)
see above
Frequency response
1 Hz / sec
Frequency stability
with own oscillator
with mains synchronisation
± 0,05%
± 3% (adjustable from 0,2% to 6%)
Harmonic distorsion
with 100% linear load
3%
with 100% non-linear load - CF 3/1
5%
Synchronisation voltage limits
Dynamic voltage response
Static regulation (100% of load)
Overload capacity
Short-circuit capability
Load power factor
Output crest factor admissible
±15%
±3% (for 0-100%-0 of load variation)
±1% (in steady state)
125% for 10 min / 150% for 1 min
250% (100ms) - 175% (5s)
315% (100ms) - 240% (5s) - Ph/N
0,5 lagging to 0,9 leading
3:1
GENERAL DATA
Operating temperature (°C)
Storage temperature (°C)
Relative humidity (non condensing)
Operating altitude (m)
Cooling
External protection
Lock
0 - 40
-20 to +70
< 95%
1000 (without derating)
Fan-assisted
IP20*
Steel locked door with door handle
Frame colour
Grey RAL 7032 textured semi-gloss
Dimensions
According to ratings, please consult us
STANDARDS
Compliance
IEC 950, 439, 146, 529, 726 - EMC (62040-2) and security (62040-1-2)
CE directives
73 / 23 / EEC - LVD and 89 / 336 / EEC - EMC
US standards
Manufacturing following UL, ANSI, NEMA, IEEE standard is available upon request
OPTIONS
Inverter
Special input or output voltage, volt-free contacts, meters, serial link,
inrush current limitation, protection against sudden loss of DC input, AC earth fault alarm
Reserve supply
By-pass transformer, by-pass stabilizer, reserve voltage monitoring
System
parallel configurations, AC distribution, PPVis monitoring software
Mechanical
*Other type of protection available upon request.
Top cable entry, other frame colour, anti-seismic design
This product may differ slightly from the product photograph on the front cover.
www.chloridepower.com
This publication is issued to provide outline information only and is not deemed to form any part of any offer and/or contract. The company has a policy of continuous product development and improvement, and we therefore reserve the right to vary any information
without prior notice. MKA4L0UKEXDA Rev. 1-06/2008
RANGE OF RATINGS (kVA)
Chloride Industrial Systems
Chloride France S.A.
30 avenue Montgolfier - BP90
69684 Chassieu Cedex
France
T +33 (0) 4 78 40 13 56
F +33 (0) 4 78 90 58 90
E [email protected]
www.chloridepower.com
Closest Chloride Contact in Australia:
Chloride Australia
Ground Floor
16 Giffnock Avenue, North Ryde
NSW 2113
Australia
Closest Chloride Contact in UAE:
Chloride UPS Systems Middle East
Building 5, Office 104
Dubai Internet City - Dubai
UAE
PO Box 72536
Closest Chloride Contact in South East Asia:
CHLD Singapore Pte Ltd
2 Corporation Road
#03-07 Corporation Place
Singapore
618494
T +61 2 9888 1266
F +61 2 9888 1966
E [email protected]
T +971 4 391 3205
F +971 4 391 6803
E [email protected]
T +65 6481 4776
F +65 6481 0552
E [email protected]
www.chloridepower.com.au
www.chloridepower.com/middle-east
www.chloridepower.com.sg
Closest Chloride Contact in UK:
Chloride UK
George Curl Way
Southampton, Hampshire
SO18 2RY
United Kingdom
Closest Chloride Contact in USA:
Chloride
27944 North Bradley Road
Libertyville
IL 60048
USA
Closest Chloride Contact in Thailand:
Chloride Thailand
Panjathani Tower, 20th Floor
127/25 Nonsee Road , Chongnonsee,
Yannawa, Bangkok 10120
Thailand
T +44 (0) 23 8061 0311
F +44 (0) 23 8061 0852
E [email protected]
T +1 847 816 6000 / +1 800 327 8801
F +1 847 680 5124
E [email protected]
T +662 296 9800
F +662 681 0109
E [email protected]
www.chloridepower.co.uk
www.chloridepower.com/usa
www.chloridepower.com/th
Closest Chloride Contact in Vietnam
Chloride Vietnam
Unit 613, 6 floor, Melinh Point Tower
2 Ngo Duc Ke, District 1,
Ho Chi Minh City
Vietnam
T +84 8 5202971
F +84 8 5202800
For a full list of contacts please visit our website at www.chloridepower.com
ISO 9001
FM 12385
ISO 14001
EMS 86301
MKA4L0UKEXDA
www.chloridepower.com/en-gb/vietnam