Chloride MP-NET - Emerson Network Power

Secure Power Always
MP-NET from 20 to 120 kVA
Uninterruptible power supply
Chloride Systems
WORLD HEADQUARTERS
Via Fornace 30
40023 Castel Guelfo (BO)
Italy
T +39 0542 632 111
F +39 0542 632 120
E [email protected]
www.chloridepower.com
Chloride operates through a worldwide network of Chloride sales and service offices and
joint ventures, with operations across 80 countries including:
Almaty, Kazakhstan
Bangkok, Thailand
Beijing, China
Makati City, Philippines
Bologna, Italy
Buenos Aires, Argentina
Chicago, USA
Dubai, UAE
Erlangen, Germany
Ho Chi Minh City, Vietnam
Lisbon, Portugal
Istanbul, Turkey
Madrid, Spain
Moscow, Russia
Paris, France
Pune, India
Diadema, Brazil
Shanghai, China
Singapore
Southampton, UK
Sydney, Australia
Warsaw, Poland
• Principal sales & service offices
• Service network
Chloride Australia
Ground Floor, 16 Giffnock Avenue
North Ryde
NSW 2113
Australia
Chloride Middle East
Arenco Tower, Office 608
Dubai Internet City - Dubai
UAE
PO Box 72536
Chloride Secure Power Philippines, Inc.
7F Y-L Finance Building,
Corner of Rufino & Salcedo Streets
Legaspi Village, Makati City
Philippines
CHLD Singapore Pte Ltd
200 Pandan Loop
#06-03 Pantech 21
Singapore
128388
T +61 2 9888 1266
F +61 2 9888 1966
E [email protected]
T +971 4 434 5201
F +971 4 430 8032
E [email protected]
T +63 2 810 0068
F +63 2 812 0433
E [email protected]
T +65 6481 4776
F +65 6481 0552
E [email protected]
www.chloridepower.com.au
www.chloridepower.com/middle-east
www.chloridepower.com
www.chloridepower.com.sg
Chloride UK
George Curl Way
Southampton
Hampshire, SO18 2RY
United Kingdom
Chloride North America
27944 North Bradley Road
Libertyville, IL 60048
USA
Chloride Power Protection Limited
1093/98-99 M. 12 Central City Tower 1
18th floor, Bangna-Trad Road (K.M.3)
Bangna, Bangkok 10260
Thailand
Eltek UPS AB
Hammarbacken 4A,
191 24 Sollentuna
Sweden
T +1 847 816 6000
+1 800 327 8801
F +1 847 680 5124
E [email protected]
www.chloridepower.co.uk
www.chloridepower.com/usa
T +66 2762 3600
F +66 2745 6618
E [email protected]
www.chloridepower.com/th
For a full list of contacts please visit our website at www.chloridepower.com
T +84 8 255 6737
F +84 8 255 6800
www.chloridepower.com/vn
T +46 8 626 64 20
F +46 8 626 64 30
E [email protected]
www.eltekups.se
MKA4L0UKMPN
T +44 (0) 23 8061 0311
F +44 (0) 23 8061 0852
E [email protected]
Chloride Vietnam
Unit 1708, 17th Floor, Gemadept Tower
06 Le Thanh Ton Street
Ben Nghe Ward, District 1
Ho Chi Minh City
Vietnam
Technical data
MP-NET
RATINGS
PRIMARY INPUT
Nominal voltage(1)
(V)
Voltage range
(V)
Minimum voltage without battery discharge
(V)
Nominal frequency
(Hz)
Frequency range
(Hz)
Maximum input current @ ambient temperature
within the range 0°C to 40°C
(A)
Power factor @ nominal load & nominal input conditions(2)
Input current distortion @ nominal input conditions
& nominal output power(3)
(%)
Walk in/Soft start
(seconds)
Rectifier Hold-Off
(seconds)
Inrush current / Imax input(4)
AC/DC Rectifier efficiency without charging current @ nominal
input conditions(2) with resistive load:
- Half load(6)
≥ (%)
- Full load(6)
≥ (%)
BATTERY
Permissible battery voltage range
(V)
Recommended no. of cells:
- VRLA(5)
- WET
- NiCd
Float voltage for VRLA @ 25°C
(V/cell)
End cell voltage for VRLA
(V/cell)
Float voltage temperature compensation
DC ripple current in float mode for a 10 min autonomy as per VDE0510(5)
Float Voltage stability in steady state condition
(%)
DC ripple voltage without battery
(%)
Optimum battery temperature
(°C)
Maximum Battery recharge current for 240 cells @ 400V
input voltage & nominal load
(A)
Battery output power in discharge mode with nominal output load
(kW)
End battery voltage for 240 cells
(V)
End battery current for 240 cells with nominal output load
(A)
INVERTER OUTPUT
Nominal apparent power @ 40°C
(kVA)
Nominal active power
(kW)
Nominal output current
(A)
Overload at nominal output voltage for 10 minutes(8)
(%)
Overload at nominal output voltage for 1 minute(8)
(%)
Short circuit current for 300ms
(%)
Nominal output voltage
(V)
Nominal output frequency
(Hz)
Voltage stability in steady state condition for input (AC & DC)
variations and step load (0 to 100%)
(%)
Voltage stability in dynamic condition for input variation (AC & DC)
and step load (0 to 100% and vice versa)
(%)
Voltage stability in steady state for 100% load imbalance (0, 0, 100) (%)
Output frequency stability
- synchronised with bypass mains
(%)
- synchronised with internal clock
Frequency slew rate
(Hz/sec)
Output voltage distortion with 100% linear load
(%)
Output voltage distortion @ reference non linear load
as IEC/EN 62040-3
(%)
Load crest factor handled without derating the UPS
(Ipk/Irms)
20
40
60
80
100
120
400 (380, 415 selectable), three-phase + neutral
300 to 477
208Vac (at 70% output load)
50/60 [selectable]
45 to 65
33
66
98
131
164
197
96.5
97
96.5
97
96.5
97
>0.99
<5
30sec
N/A
≤1
96.5
97
96.5
97
96.5
97
± 240
240 cells
240 cells
375 cells
2.27
1.67
-3.96mV/cell, raise 1°C
<0.02C10
1
1
15 to 25
5
17
10
34
15
51.1
20
68.1
25
85.1
30
102.1
42.5
85.1
127.7
±200
170.2
212.8
255.3
20
16
29
40
32
58
60
48
87
100
80
145
120
96
174
80
64
116
<125
<150
300
400 (380, 415 selectable), three-phase + neutral
50 [60Hz selectable]
±1
±7
±1
±5 (±0.1~±5 selectable)
±0.05
<1
<3
<5
3
20
40
60
80
100
120
96.5
97
96.5
97
96.5
97
1.5°
2°
96.5
97
96.5
97
96.5
97
110
105
100
400 (380, 415 selectable), three-phase + neutral
50/60 [selectable]
±5 (±0.5 ~ ±5 selectable)
±15 (±8 ~ ±15 selectable)
<1
<1
<10
92.5
93.5
94
95
92.5
93.5
94
95
92.5
93.5
94
95
92.5
93.5
94
95
92.5
93.5
94
95
92.5
93.5
94
95
14.2
70
17.7
70
21.3
70
98
3.6
65
7.1
67
10.7
69
IP20
1165
520
910
1700
520
950
1
9005
169
199
229
259
Bottom
Front/Side/Rear
Forced Ventilation
349
379
0 to 40
<95
1500
(1) In case of a split input configuration, the primary input and the bypass input must have a common neutral. The neutral conductor may be
connected only to the bypass or primary mains but it must be present (bypass and primary neutrals are solidly connected inside the UPS).
(2) At nominal voltage and nominal frequency.
(3) With input voltage at nominal value and with voltage distortion THDv <1%.
(4) “Imax input” parameter can be calculated using the maximum input power @ 400V in battery recharge mode.
(5) Permitted number of cells = 240
(6) For tolerances see IEC/EN 60146-1-1 or DIN VDE 0558.
(7) Recommended average daily ambient temperature 35°C with a maximum of 40°C for 8 hours.
(8) Conditions Apply.
This publication is issued to provide outline information only and is not deemed to form any part of any offer and/or contract. The company has a policy of continuous product development and improvement, and we
therefore reserve the right to vary any information without prior notice. MKA4L0UKMPN REV. 3 - 07/2010
MP-NET
RATINGS
INVERTER OUTPUT
Phase angle precision with balanced loads
(degrees)
Phase angle precision with 100% unbalanced loads
(degrees)
DC/AC Inverter efficiency @ nominal input conditions(2)
with resistive load:
≥ (%)
- Half load(6)
- Full load(6)
≥ (%)
Output power upgrading with ambient temperature:
- At 25°C
(%)
- At 30°C
(%)
- At 40°C
(%)
STATIC BYPASS
(V)
Nominal bypass voltage(1)
Nominal frequency
(Hz)
Frequency range
(Hz)
Voltage range
(%)
Transfer time with inverter synchronised to bypass:
- Inverter to Bypass
(ms)
- Bypass to Inverter
(ms)
Transfer time with inverter not synchronised to bypass
(ms)
SYSTEM DATA
AC/AC efficiency without charging current @ nominal
input conditions(2) with resistive load:
- 25% load(6)
(%)
- 50% load(6)
(%)
- 75% load(6)
(%)
(%)
- 100% load(6)
- VFD6)
(%)
Heat dissipation:
- Recharge mode
(kW)
Noise @ 1 metre as per ISO 3746(8)
(dBA ± 2dBA)
Protection degree with open doors
Mechanical dimensions:
- Height
(mm)
- Width
(mm)
- Depth
(mm)
No. of cabinets
Frame colour
(RAL scale)
Weight
(kg)
Cable entry
Access
Cooling
ENVIRONMENTAL
Temperature:
- Operating temperature(7)
(°C)
- Maximum relative humidity @ 20°C (non condensing)
(%)
Max altitude above sea level without derating
(m)
Secure Power Always
MP-NET from 20 to 120 kVA
Chloride's MP-NET is a modular solution designed to grow with evolving
load requirements, making it the perfect solution to power modular
distributed networks.
MP-NET has been developed to meet the highest standards of serviceability, flexibility and scalability, while also
having maximum energy and space saving features, guaranteeing maximum availability.
The smart solution that easily adapts
to run time requests
Key performances
MP-NET offers the most secure and flexible
system architecture able to grow with your
business. This modular solution is made up
of a bespoke cabinet that is able to house 20
kVA power modules. Bespoke cabinets are
available in two sizes to suit either up to 4 or
6 power modules. Power modules can easily be added to the cabinet at any time without dropping the load or making other
changes to the battery bank.
MP-NET offers the most secure and
flexible system architecture together with
intelligent double conversion.
Leading
10
0
60
Cos ϕ 0.9
40
100% KW
20
0
25
50
Cos ϕ 1
100
75
100% KW
20
40
Cos ϕ 0.9
60
Cos ϕ 0.8
80
100
KVA
100%
Cos ϕ 0.6
Lagging
MP-NET: adapts to business needs for maximum availability
MP-NET is easy to install and service
thanks to its modular design.
(that could potentially damage the
system or even cause the load to crash).
The Hot Swap feature makes it
possible to plug in a power module
while maintaining maximum load
security. This means that the power
module is replaceable without having
to transfer the load to the raw mains.
Furthermore making it easy for
the user to perform basic service
interventions.
Each power module provides a 5A
battery charging current, guaranteeing
full redundancy and long autonomy
battery configurations, making it
compatible with many different types
of installations.
The replacement or scaling is achieved
without any risk of handling errors
Cos ϕ 0.5
80
A
KV
The main features of the MP-NET are:
• IGBT double conversion technology
• Excellent input performances:
• PF > 0.99
• THDi < 5%
• High conversion efficiency (up to 98%)
• Output PF up to 0.9
• Capability to power leading and lagging
loads without derating
• 300% short circuit current
• Dual separated rectifier and bypass
input
• Cold start
100
%
MP-NET represents the best solution for
parallel redundant systems; maximising
system efficiency, and minimising the total
cost of ownership thanks to:
• Hot Swap plug-in modules
• High conversion efficiency
• Reduced footprint (optimising layout
space and transport costs)
• Optimised N+1 redundant configurations
up to 5N+1.
KVAr
Hot Swappable plug-in/out power
modules make MP-NET perfectly suitable for parallel redundant configurations, especially when minimum space
impact is required.
Kw
Geographical modularity - maximum flexibility for customised solutions
MP-NET is a dynamic modular UPS ideal for applications such as data centres, transport, communications, and
distributed networks.
MP-NET is designed to meet the
changing requirements of loads located
in different geographical areas, making it
the best solution to maximise system
efficiency, reduce running costs and
minimise the total cost of ownership.
The flexible design of the power modules
makes it possible to move them easily
from one bespoke cabinet to another.
The module is capable of powering any
kind of load, leading or lagging, with no
derating, and via the LIFE.net system it
is also possible to constantly monitor
the actual power offered. These elements
combined, allow for the optimisation
of energy consumption even in large
distributed networks.
Optimum space impact
It is possible to have a 100 kVA N+1 configuration
in a space of just:
W 520 x H 1700 x D 950
and a 60 kVA N+1 configuration in a space of just:
1700mm
W 520 x H 1165 x D 910
1165 mm
910 mm
950 mm
mm
520
mm
520
Interfaces
Communication
MP-NET features a centralised high
resolution LCD display with eight
languages, allowing for easy interaction
with all modules through the navigation
menu.
It also contains detailed information and
measures of:
• UPS system status
• Each single power module
• Battery
• Electrical parameters
The UPS is perfectly suitable for use in
any network or building management
system and offers the following standard
communication features:
• EPO
• I/P contact closure (two)
• I/P port for external battery temperature
sensor
• Battery cabinet status
• Two smart slots (for LIFE.net and
Connectivity cards).
Hardware Connectivity
MP-NET includes a complete suite of
connectivity solutions, ensuring the
monitoring and control of the networked
UPS, through the TCP/IP protocol.
A complete set of adaptors allow MP-NET to
be integrated with building and Automation
Systems via TCP/IP, MODBUS and JBUS. An
external sensor box is available for monitoring
the environmental conditions where the UPS
systems are installed. A relay I/O card with
programmable output can be inserted into the
slot to monitor UPS systems and modules.
components. The software works in
conjunction with the Connectivity Card to
provide easy, unattended shutdown of
multiple computer systems across the
network. It also enables the simultaneous
monitoring of UPS locally and remotely.
The hierarchical design makes it easy to
manage UPS intuitively.
Software Connectivity
A complete suite of software tools allows
for automatic and scheduled shutdowns
as well as a variety of other features that
help manage the system and its peripheral
Tailored sizing for maximum efficiency
Tailoring your power protection system to use only the
necessary power required makes for a smart investment which
is more economic to run.
Efficiency Curve of MP-NET 5N+1 configuration
95 %
The modular design of this UPS allows it to work at maximum
efficiency by offering the possibility of adding or removing
modules according to the load requirement. This in turn enables
it to obtain significant energy savings even at partial load.
A power upgrade can be made whenever necessary avoiding
system oversizing which could potentially lead to higher running
costs.
0
50
100
load (%)
Service and LIFE.net 24/7 remote diagnostic system
Installation is only the beginning of your relationship with Chloride as it is
essential that your critical power protection system is maintained in an
optimum state of readiness at all times. The innovative range of
maintenance and support services available from Chloride ensure
reliability for life-long protection. Chloride takes responsibility for
the health of your UPS units 24 hours per day.
The LIFE cycle
LIFE.net is the maintenance program which includes the remote
diagnosis, monitoring and managing of the operational status of
UPS and power distribution systems. LIFE.net provides early warning
of any alarm condition or out of tolerance status, allowing effective
proactive maintenance and fast incident response, giving customers
complete security and peace of mind.
Maximise
availability
Minimise
downtime
Reduce
operating costs
Pre-emptive maintenance
LIFE.net provides early warning of
more than 150 separate parameters
allowing real-time diagnosis and swift
identification and resolution of operating
anomalies.
Immediate identification of problems
Should an emergency condition arise, a
Chloride engineer in the 24x7 manned
service centre carries out an immediate
fault analysis and instigates appropriate
corrective action.
Superior asset management
Through comprehensive data collection and
analysis, LIFE.net’s detailed reporting system
provides valuable information on power and
equipment trends, over any selected period
of time.
Chloride Customers worldwide include:
Alcatel
American Telecom
Asia Multi Media
Bank of America
Barclays
BBC
Bennet
Berlin Airport
Beyond
Carlton TV
Citibank
Credit Suisse
Dubai international Airport
Ericsson
Fastweb
France Telecom
HSBC
Intel
Ikea
Kingston
Linante Airport, Milan
Lamborghini
MTV
Vodafone
Radio France Otre-Mer
RAI
Roche
Sky
Telecom Aisa
Tesco Kipa
Tiscali
Wind
www.chloridepower.com