Description
The Liebert vNSA network switch is designed for
connecting multiple Ethernet-ready devices and
comes in various models. The unit may have:
• A Liebert iCOM® display mounted on the front,
as shown at right. Liebert iCOM models permit
interconnecting cooling units that are equipped
with Liebert iCOM controls, allowing the units to
communicate.
• One or two 8-port switches, providing a total
of 8 or 16 Ethernet ports. The example below
shows a model with two 8-port switches.
The number of ports available varies by model (see
Table 1 for details).
All models have a power supply that requires
connection, as shown below.
Key lock
Liebert iCOM display
INSIDE VIEW
16-port model
shown
UPPER SWITCH
(all models)
Power supply
(all models)
LOWER SWITCH
(16-port models
only)
Knockouts for cable access (top and bottom)
Liebert iCOM Display
Yes
No
Model
Firmware / Liebert Products Supported
vNSA8-iCOM
vNSA16-iCOM
PA
Liebert DS™
Liebert CW™
vNSA8-iCOM-CR
vNSA16-iCOM-CR
CR
Liebert CRV™
vNSA8-iCOM-XP
vNSA16-iCOM-XP
XP
Liebert XDP™
Liebert XDC™
vNSA8
vNSA16
—
Liebert Challenger™ 3000/
Liebert Challenger ITR™
with Liebert iCOM Control
—
1
Liebert HPM™
Liebert PeX™
Packing Contents
The Liebert vNSA comes standard with these components:
• Liebert iCOM display on front of enclosure (Liebert iCOM models only)
• One 8-port switch inside enclosure (8-port models)
or
Two 8-port switches inside enclosure (16-port models)
• Universal power supply and hardwire adapter
• Keys (2) to panel door lock
• User manual for Liebert vNSA
• User manual for industrial rail switch
• User manual for Liebert iCOM (Liebert iCOM models only)
Factory Connections
The Liebert vNSA has factory-wired connections to simplify installation, depending on the model (see
Figure 1):
Models with Liebert iCOM display
• The upper switch is factory-connected to the Liebert iCOM display.
16-port models
• The upper switch is factory-connected to the lower switch.
All models
• Proper power connections are factory-wired between the 3-pin terminal blocks on each switch.
Figure 1
Factory-wired connections
UPPER SWITCH
(all models)
Cable connecting
upper switch to lower switch
(16-port models only)
Cable connecting
upper switch to Liebert iCOM display
(Liebert iCOM models only)
LOWER SWITCH
(16-port models only)
2
Switches
Each switch has eight 10/100 Mbps twisted pair RJ45 ports, allowing connection of Ethernet-ready devices to
available ports.
The switch supports Ethernet 10 Mbps and Fast Ethernet 100 Mbps using twisted-pair RJ45 ports, allowing
connection of Ethernet-ready devices. The devices support switched Ethernet networks in accordance with
IEEE standard 802.3.
Three automatic features—autonegotiation, autopolarity and autocrossing—allow the use of standard
network cables (CAT5 or better) for connection to each port, rather than a special crossover cable. The switch
detects and makes adjustments for the network’s speed and transmission mode, polarity and transmit-andreceive pins. Refer to the Industrial Rail Switch user manual for more details.
Connecting Devices
Use CAT5 or better network patch cables with RJ45 connectors to connect devices to available ports.
Number of Ports Available
The number of ports available for Ethernet-ready devices varies by model, as shown in Table 1.
• Models with the Liebert iCOM display use one port for connection to the Liebert iCOM display.
• Models with two switches use two ports to interconnect the switches.
Table 1
Number of available ports by model
Maximum # Cooling Units
That May Be Connected
# Ports Needed to Connect:
Liebert
iCOM
Display
Model
vNSA8-iCOM
Yes
No
Total
#
Ports
To Liebert
iCOM
Display
Upper
& Lower
Switches
# Ports
Available
8
1
—
7
Cooling Units
With Small
Liebert iCOM
Display
Cooling Units
With Large
Liebert iCOM
Display
7 units
3 units
13 units
6 units
vNSA8-iCOM-CR
8
1
—
7
vNSA8-iCOM-XP
8
1
—
7
vNSA16-iCOM
16
1
2
13
vNSA16-iCOM-CR
16
1
2
13
vNSA16-iCOM-XP
16
1
2
13
vNSA8
8
—
—
8
8 units
4 units
vNSA16
16
—
2
14
14 units
7 units
Number of Cooling Units That May Be Connected
The maximum number of cooling units that may be connected depends on the Liebert vNSA model
and the size of the Liebert iCOM display in the cooling units, as shown in Table 1.
Refer to the Liebert iCOM user manual for additional details on connecting Liebert cooling products.
3
Connect Power to the Liebert vNSA
The Liebert vNSA requires AC power (100-240VAC single phase) for proper operation. A universal power
supply (12V, 1.5A) is installed inside the enclosure, with a hard-wired connection for 120V or 230V operation.
!
WARNING
Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric
power supplies before working within.
NOTICE
The Liebert vNSA is designed for use on properly grounded (earthed) 100-240VAC singlephase power, 50Hz or 60Hz. The ground wire for the power lead must be wired to the earth
ground terminal (stud located next to the universal power supply).
This equipment is intended to be installed by a qualified and certified electrician who must
review and approve customer supplied wiring and circuit breakers, verify correct input and
grounded (earthed) connections to ensure compliance with technical standards and national
and local electrical codes.
NOTE
The connector must be unplugged prior to installation.
A field-supplied power cord may be used in place of the hardwire adapter provided.
Power Supply Wiring Instructions
1. Loosen and remove the screw from the adapter cover.
Loosen
cover
screw
D
2. Remove the cover.
N
Fl
Remove
cover
N
E L
3. Loosen the two screws that secure the wire clamp. Remove the screws and the wire clamp.
N
Screws
E L
Wire
clamp
4
4. Connect the incoming electrical service ground wire to the earth ground terminal inside the enclosure,
shown below.
Earth ground
terminal
5. Feed wires—including a ground wire from the earth ground terminal in Step 4—through the rubber
strain relief into the adapter. Note: 16 AWG stranded maximum wire size.
N
Rubber
strain
relief
E L
6. Strip the insulation on each wire to expose 5/8" (16mm).
N
E L
Strip insulation
to expose 5/8" (16mm)
7. Loop each wire around the appropriate terminating screw and tighten. Each screw is labeled:
• N = Neutral for 120V; Line for 220V applications
• E = Earth ground
• L = Line
Neutral for 120V; Line for 220V applications
(white)
N
E L
Earth grounding conductor
(green)
Line
(black)
8. Replace the wire clamp and the two screws removed in Step 3 to secure wires.
9. Close the adapter cover and tighten the screw from Step 1.
5
Enclosure
The Liebert vNSA enclosure features a key lock for added
security. The enclosure is made of metal to accommodate
secure conduit fittings and protect components against
environmental debris.
14.25"
(361.95mm)
The enclosure is designed for easy wire routing and
terminations. Access slots for network cables and power
wiring are located on both the top and bottom of the
enclosure.
12"
(304.8mm)
The enclosure is 3.3" (84mm) deep, allowing for recess
mounting in a wall. The enclosure may also be surfacemounted.
The enclosure houses the power supply and one or two 8-port
rail switches. Some models have a Liebert iCOM display
mounted on the front of the enclosure.
FRONT VIEW
(all models)
Enclosure Mounting Considerations
The Liebert vNSA must be installed indoors. The enclosure
must be secured to a wall, either mounted on the surface of a
wall or recessed with the front flush against a wall. The
method of mounting depends on the application, the location
of equipment to be monitored and the type of wall the
enclosure will be mounted on.
• The Liebert vNSA should be mounted where it can be
easily accessed.
• The site must have electrical service and must permit
routing of network cables to the unit’s RJ45 ports.
• The wall material must be capable of supporting the
weight of the Liebert vNSA: see Specifications on
page 8.
6
3.3"
(84mm)
TOP/BOTTOM VIEW
(vNSA8 & vNSA16 models)
7/8"
(22mm)
4.175"
(106mm)
TOP/BOTTOM VIEW
(Liebert iCOM models)
Surface Mounting
NOTE
Removing the conduit knockouts before mounting the Liebert vNSA on the wall will ease
installation and prevent strain on the mounting hardware and wall.
After determining where to place the enclosure, check to ensure that you have all the hardware required to
install the panel on the surface of a wall. Obtain the needed tools and material.
Required Tools
•
•
•
•
Electric drill (if surface is too hard to drive screws without pilot holes)
Screwdriver
Marker to denote layout of holes
Four screws, each #10
Mounting the Panel
NOTICE
Check building plans and other relevant documents to determine whether mounting the
Liebert vNSA at the selected location might cause cutting or otherwise damaging electrical or
communication wiring or pipes.
1. Mark the wall for mounting holes, using the back of the unit as a template (see Figure 2).
Figure 2
Mounting dimensions
12-1/2"
(318mm)
0.88"
(22mm)
0.213"
(5mm)
A
10"
(254mm)
0.694"
(18mm)
0.375"
(10mm)
1" (25mm)
Back Plate
(inside view)
Detail “A”
Mounting Slot
0.213" (5mm)
(two places)
2. Drill holes, if required, to install the four #10 screws that will secure the Liebert vNSA to the wall. Clean
up the debris.
3. If the wall material is not strong enough to hold the screws securely, use wall anchors.
4. Install the top two screws—the screw heads must be small enough to slip through the larger, bottom
portion of the pear-shaped mounting slot in the Liebert vNSA (see Figure 2). The screws must also be
large enough to extend over the edges of the top of the mounting slot.
5. Hang the Liebert vNSA on the screws, letting the panel slip down until the screws are in the smaller,
upper portion of the slot.
6. Tighten the screws until they are snug.
7. Insert the remaining two screws in the bottom holes on the back of the panel and tighten.
7
Specifications
vNSA16-iCOM
vNSA16-iCOM-CR
vNSA16-iCOM-XP
vNSA8-iCOM
vNSA8-iCOM-CR
vNSA8-iCOM-XP
MODEL
Power
vNSA8 / vNSA16
100-240VAC, single-phase, 47-63 Hz, 0.4A
Dimensions, W x D x H - in. (mm)
14.25 x 3.3 x 12 (362 x 84 x 305)
Weight - lb. (kg)
11 (5)
Enclosure Type
10 (4.5)
NEMA 1, painted steel IP20 - indoor use
Mounting Surface
Building wall or structural member
Ethernet 10/100 Mbps RJ45 ports,
autonegotiation, autopolarity and autocrossing
Communication
32°F to 140°F (0°C to 60°C);
0 to 95% relative humidity, non-condensing.
Ambient Operating Environment
Wiring Specifications
Connection
Supported Wire Types
Maximum Wire Length
Rating
Ethernet 10/100 Mbps
CAT 5 RJ45 Ethernet cable
328 ft. (100m)
N/A
Universal power supply
16 AWG Stranded
Contact local electrician
300V
Ordering Information
Quantity
Part #
Liebert vNSA with:
Firmware / Liebert Products Supported
vNSA8-iCOM
8 ports, Liebert iCOM display
vNSA16-iCOM
16 ports, Liebert iCOM display
vNSA8-iCOM-CR
8 ports, Liebert iCOM display
vNSA16-iCOM-CR
16 ports, Liebert iCOM display
vNSA8-iCOM-XP
8 ports, Liebert iCOM display
vNSA16-iCOM-XP
16 ports, Liebert iCOM display
vNSA8
8 ports
vNSA16
16 ports
PA
Liebert DS
Liebert CW
CR
Liebert CRV
XP
Liebert XDP
Liebert XDC
—
Liebert Challenger
series
Liebert HPM
Liebert PeX
—
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022
www.liebert.com
© 2006 Liebert Corporation
All rights reserved throughout the world. Specifications subject
to change without notice.
® Liebert is a registered trademark of Liebert Corporation. All
names referred to are trademarks or registered trademarks of
their respective owners.
SL-18840_REV1_05-10
8