SAG582122500 SYSTEM OVERVIEW

SAG582122500
System Application Guide
Spec. No. 582122500 (Model 1231V2)
Issue AH, July 31, 2008
Home
SYSTEM OVERVIEW
Description:
This system provides a solution to
replace traditional power with power
derived from the Vortex® platform, or to
expand existing Vortex Power Systems
(VPS’s) to meet additional power
needs. A VPS typically consists of ...
•
one front access VPS Intelligence
Shelf, which houses Power
Conversion Units (PCU’s). Also
includes the Meter-Control-Alarm
(MCA) assembly, which controls
the operation of up to fifty-six (56)
PCU’s, and provides system
metering, control, and alarm
functions.
•
one or more optional front access
VPS Expansion Shelves, each of
which houses PCU’s.
•
PCU’s which provide load power,
battery float current, and battery
recharge current during normal
operating conditions.
List 1 and 3 Shown
List 2 and 4 Similar (no
Intelligence Shelf)
Family:
Vortex
Spec. No.:
582122500
Model:
1231V2
Output Voltage:
-48 Volts DC
Output Capacity
System:
PCU:
1200 amperes, maximum, per bay
50 amperes or 65 amperes, per PCU
Framework Type:
Relay Rack
Mounting Width:
23 Inches per Bay
Mounting Depth:
18 Inches
Access:
Front
Supplemental Bay(s):
Up to two (2) available
Control:
Microprocessor
Color:
Off-White (Lorain Spec. M500-117)
Options:
PCU Intelligence Shelf, PCU Expansion
Shelf, V50B50 PCU, V65B50 PCU
Accessories:
PCU Shelf Class B Filter, PCU Shelf High AC
Disconnect, PCU Shelf AC Input Line Cords, Vortex
WinLink Hardware (Modem), Vortex WinLink Software
Environment:
50°C
List 5 Shown
List 6 Similar
Page 1 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582122500
Issue AH, July 31, 2008
System Application Guide
Spec. No. 582122500 (Model 1231V2)
Home
582122500 (Lists 1 through 4)
Shunt POD Card
(Inside)
Common Equipment
(Lists 1, 2, 3, and 4)
Vortex WinLink Software
(List 73)
Vortex WinLink
Hardware (Modem)
(List 72)
PCU Intelligence Shelf Interface
(List 7) (used w/ Lists 1 and 3)
AC Input Line Cords
(List 32)
Class B Filter or
High AC Disconnect
(List 24 or 27)
V50B50 PCU or
V65B50 PCU
(List 21 or 22)
Lists 1 and 3 Shown
Lists 2 and 4 Similar (no Intelligence Shelf)
PCU Expansion Shelf Interface
(List 8)
(used w/ Lists 1, 2, 3, and 4)
SEE ALSO
System Overview
Table of Contents
List Structure Table
Lugs
Relay Rack Options
Replacement Cables
List of Parts
Dimensional Drawings
Related Documentation
Page 2 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582122500 (Model 1231V2)
SAG582122500
Issue AH, July 31, 2008
Home
582122500 (Lists 5 and 6)
Shunt POD Card
(Inside)
Common Equipment
(Lists 5 and 6)
Vortex WinLink Software
(List 73)
Vortex WinLink
Hardware (Modem)
(List 72)
PCU Intelligence Shelf Interface
(List 7) (used w/ Lists 5 and 6)
Class B Filter or
High AC Disconnect
(List 24 or 27)
V50B50 PCU
(List 21)
PCU Expansion Shelf Interface
(List 8)
(used w/ Lists 5 and 6)
List 5 Shown
List 6 Similar
Mounting Frame
(P/O List 5 only)
SEE ALSO
System Overview
Table of Contents
List Structure Table
Lugs
Relay Rack Options
Replacement Cables
List of Parts
Dimensional Drawings
Related Documentation
Page 3 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582122500
Issue AH, July 31, 2008
System Application Guide
Spec. No. 582122500 (Model 1231V2)
TABLE OF CONTENTS
System
Overview
Picture
Lists 1-4
Lists 5-6
List
Information
Accessory
Information
List of
Parts
Physical Size
Information
Related
Documentation
SYSTEM OVERVIEW................................................................................................................................................ 1
TABLE OF CONTENTS ............................................................................................................................................ 4
LIST INFORMATION................................................................................................................................................. 5
List Structure........................................................................................................................................................ 5
List Descriptions .................................................................................................................................................. 6
List 1: Common Equipment for Main Power Bay (Ship Loose)......................................................................... 6
List 2: Common Equipment for Supplemental Power Bay (Ship Loose)........................................................... 6
List 3: Common Equipment for Main Power Bay (Factory Mounted in a Relay Rack) ..................................... 7
List 4: Common Equipment for Supplemental Power Bay (Factory Mounted in a Relay Rack) ....................... 7
List 5: Common Equipment for Main Power Bay Mounted on Shipping Frame................................................ 8
List 6: Common Equipment for Main Power Bay (Factory Mounted in a Relay Rack) ..................................... 8
List 7: Interface Components for One (1) PCU Intelligence Shelf..................................................................... 9
List 8: Interface Components for One (1) PCU Expansion Shelf ...................................................................... 9
List 21: V50B50 PCU ...................................................................................................................................... 10
List 22: V65B50 PCU ...................................................................................................................................... 10
List 24: Optional PCU Shelf Class B Filter ...................................................................................................... 10
List 27: Optional PCU Shelf High AC Input Voltage Disconnect and Reconnect ........................................... 10
List 32: PCU Shelf AC Input Line Cords ......................................................................................................... 11
List 72: Vortex® WinLink Hardware (Modem Interface).................................................................................. 11
List 73: Vortex® WinLink Software.................................................................................................................. 11
ACCESSORY INFORMATION ............................................................................................................................... 12
Lugs..................................................................................................................................................................... 12
Output Lugs ...................................................................................................................................................... 12
Lug and Wire Selection Table .......................................................................................................................... 13
Standard Crimp Lug Part Numbers .................................................................................................................. 14
Relay Rack Options (for use with Lists 3, 4, and 6 only) ............................................................................... 15
Replacement Cables.......................................................................................................................................... 16
Optional Cables.................................................................................................................................................. 16
LIST OF PARTS...................................................................................................................................................... 17
PHYSICAL SIZE INFORMATION ........................................................................................................................... 19
Overall Dimensions - Lists 1-4.......................................................................................................................... 19
Overall Dimensions - Lists 5-6.......................................................................................................................... 20
Output Busbar Dimensions - Lists 1-4 ............................................................................................................ 21
Output Busbar Dimensions - Lists 5-6 ............................................................................................................ 22
RELATED DOCUMENTATION............................................................................................................................... 23
REVISION RECORD ............................................................................................................................................... 24
Page 4 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582122500 (Model 1231V2)
SAG582122500
Issue AH, July 31, 2008
Home
LIST INFORMATION
List Structure
List
Number
Description
Part Number
Mounting
Positions
(1U = 1-3/4”)
1
2
1
58212250001
Common Equipment, Main Bay (Ship Loose)
3U 1
2
58212250002
Common Equipment, Supplemental Bay (Ship Loose)
3U 1
3
58212250003
Common Equipment, Main Bay
(Factory Installed in Specified Relay Rack)
3U 1
4
58212250004
Common Equipment, Supplemental Bay
(Factory Installed in Specified Relay Rack)
3U 1
5
58212250005
Common Equipment, Main Bay,
Mounted on Shipping Frame
19U 2
6
58212250006
Common Equipment, Main Bay
(Factory Installed in Specified Relay Rack)
5U 1
7
58212250007
Interface Components for PCU Intelligence Shelf
6U
8
58212250008
Interface Components for PCU Expansion Shelf
6U
21
58212250021
V50B50 PCU for V200ICAB and V200ECAB Shelves
--
22
58212250022
V65B50 PCU for V260ICAB and V260ECAB Shelves
--
24
58212250024
Class B Filter for PCU Shelves
--
27
58212250027
High AC Disconnect for PCU Shelves
--
32
58212250032
AC Input Line Cords (Individual PCU Feeds) for PCU Shelves
--
72
58212250072
Vortex WinLink Hardware (Modem) for PCU Intelligence Shelf
--
73
58212250073
Vortex WinLink Software
--
Lists 1-4, and 6: Mounting Positions Height does not include PCU Shelves.
List 5: Mounting Positions Height includes two (2) PCU Shelves.
Page 5 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582122500
Issue AH, July 31, 2008
System Application Guide
Spec. No. 582122500 (Model 1231V2)
Home
List Descriptions
List 1: Common Equipment for List of Parts
Main Power Bay (Ship Loose)
Features
♦
Provides output lead termination busbars for connection of customer DC power leads.
♦
Provides a shunt POD circuit card (433800164) to allow current monitoring of an external load shunt. The
Shunt POD interfaces with the VPS's MCA for remote shunt monitoring.
♦
Provides a “Connector Assembly” circuit card for external alarm, reference, and control connections; and
system interconnects.
♦
Includes 60’ long alarm extension cable, Part No. 421630900, for customer connections to VPS
Intelligence Shelf external alarm and control circuits.
Restrictions
The system can consist of a main power bay, and up to two (2) supplemental power bays.
Ordering Notes
1) Components shipped loose for mounting on a customer provided relay rack.
2) Order PCU Shelf(s) as required per Lists 7 and 8.
3) Order PCU Shelf options as required per Lists 24 or 27 and 32; and the appropriate PCU Shelf Power
Data Sheet.
4) Order PCU's as required per List 21 or 22.
5) Order Vortex WinLink Hardware and Software as required per List 72 and 73.
6) Order output lugs as required per CRIMP LUGS table.
List 2: Common Equipment for
Supplemental Power Bay (Ship Loose)
List of Parts
Features
♦
Provides output lead termination busbars for connection of customer DC power leads.
♦
Includes 25’ long interbay cable, Part No. 100575.
Restrictions
The system can consist of a main power bay, and up to two (2) supplemental power bays.
Ordering Notes
1) Components shipped loose for mounting on a customer provided relay rack.
2) Order PCU Shelf(s) as required per List 8.
3) Order PCU Shelf options as required per Lists 24 or 27 and 32; and the appropriate PCU Shelf Power
Data Sheet.
4) Order PCU's as required per List 21 or 22.
5) Order output lugs as required per CRIMP LUGS table.
Page 6 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582122500 (Model 1231V2)
SAG582122500
Issue AH, July 31, 2008
Home
List 3: Common Equipment for Main Power
Bay (Factory Mounted in a Relay Rack)
List of Parts
Features
♦
Provides output lead termination busbars for connection of customer DC power leads.
♦
Provides a shunt POD circuit card (433800164) to allow current monitoring of an external load shunt. The
Shunt POD interfaces with the VPS's MCA for remote shunt monitoring.
♦
Provides a “Connector Assembly” circuit card for external alarm, reference, and control connections; and
system interconnects.
♦
Includes 60’ long alarm extension cable, Part No. 421630900, for customer connections to VPS
Intelligence Shelf external alarm and control circuits.
Restrictions
The system can consist of a main power bay, and up to two (2) supplemental power bays.
Ordering Notes
1) Factory mounted in relay rack ordered per RELAY RACK OPTIONS table.
2) Order PCU Shelf(s) as required per Lists 7 and 8.
3) Order PCU Shelf options as required per Lists 24 or 27 and 32; and the appropriate PCU Shelf Power
Data Sheet.
4) Order PCU's as required per List 21 or 22.
5) Order Vortex WinLink Hardware and Software as required per List 72 and 73.
6) Order output lugs as required per CRIMP LUGS table.
List 4: Common Equipment for Supplemental
Power Bay (Factory Mounted in a Relay Rack)
List of Parts
Features
♦
Provides output lead termination busbars for connection of customer DC power leads.
♦
Includes 25’ long interbay cable, Part No. 100575.
Restrictions
The system can consist of a main power bay, and up to two (2) supplemental power bays.
Ordering Notes
1) Factory mounted in relay rack ordered per RELAY RACK OPTIONS table.
2) Order PCU Shelf(s) as required per List 8.
3) Order PCU Shelf options as required per Lists 24 or 27 and 32; and the appropriate PCU Shelf Power
Data Sheet.
4) Order PCU's as required per List 21 or 22.
5) Order output lugs as required per CRIMP LUGS table.
Page 7 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582122500
Issue AH, July 31, 2008
System Application Guide
Spec. No. 582122500 (Model 1231V2)
Home
List 5: Common Equipment for Main Power Bay
Mounted on Shipping Frame
List of Parts
Features
♦
All Equipment Cabinets Mounted to a Shipping Frame.
♦
Provides output lead termination busbars for connection of customer DC power leads.
♦
Provides 800A Internal Load Shunt.
♦
Provides a shunt POD circuit card (433800164) to allow current monitoring of the internal load shunt. The
Shunt POD interfaces with the VPS's MCA for shunt monitoring.
♦
Provides a “Connector Assembly” circuit card for external alarm, reference, and control connections; and
system interconnects.
♦
Includes 60’ long alarm extension cable, Part No. 421630900, for customer connections to VPS
Intelligence Shelf external alarm and control circuits.
Restrictions
The system consists of a main power bay only.
Ordering Notes
1) Components mounted on a shipping frame for mounting onto a customer provided relay rack.
2) Order PCU Shelf(s) as required per Lists 7 and 8.
3) Order PCU Shelf options as required per Lists 24 or 27; and the appropriate PCU Shelf Power Data
Sheet.
4) Order PCU's as required per List 21.
5) Order Vortex WinLink Hardware and Software as required per List 72 and 73.
6) Order output lugs as required per CRIMP LUGS table.
List 6: Common Equipment for Main Power
Bay (Factory Mounted in a Relay Rack)
List of Parts
Features
♦
Provides output lead termination busbars for connection of customer DC power leads.
♦
Provides 800A Internal Load Shunt.
♦
Provides a shunt POD circuit card (433800164) to allow current monitoring of the internal load shunt. The
Shunt POD interfaces with the VPS's MCA for shunt monitoring.
♦
Provides a “Connector Assembly” circuit card for external alarm, reference, and control connections; and
system interconnects.
♦
Includes 60’ long alarm extension cable, Part No. 421630900, for customer connections to VPS
Intelligence Shelf external alarm and control circuits.
Restrictions
The system consists of a main power bay only.
Ordering Notes
1) Factory mounted in relay rack ordered per RELAY RACK OPTIONS table.
2) Order PCU Shelf(s) as required per Lists 7 and 8.
Page 8 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582122500 (Model 1231V2)
SAG582122500
Issue AH, July 31, 2008
3) Order PCU Shelf options as required per Lists 24 or 27; and the appropriate PCU Shelf Power
Data Sheet.
Home
4) Order PCU's as required per List 21.
5) Order Vortex WinLink Hardware and Software as required per List 72 and 73.
6) Order output lugs as required per CRIMP LUGS table.
List 7: Interface Components for One (1) PCU Intelligence Shelf
List of Parts
Features
♦
Provides components to add one (1) PCU Intelligence Shelf to the power system.
Spec. No. 588700701 or 588703600 for Lists 1, 3, 5 and 6.
Spec. No. 588704200 for Lists 5 and 6.
♦
Includes two interconnect cables, Part Nos. 421868200 and 100573.
Restrictions
Includes PCU Shelf interconnect components only.
Only one (1) PCU Intelligence Shelf required per system. Must be installed in main bay (List 1, 3, 5, or 6).
Due to AC input connection routing, only one VPS Expansion Shelf (Spec No. 588704300) may be mounted
directly below VPS Intelligence Shelf (Spec. No. 588704200).
Ordering Notes
1) Order PCU Shelf as required per PD588700701/PD588700801 or PD588703600/PD588703700 (Lists 1,
3, 5 and 6), or PD588704200/PD588704300 (Lists 5 and 6).
2) Order PCU Shelf options as required per Lists 24 or 27, 32, and 72; and PD588700701/PD588700801, or
PD588703600/PD588703700, or PD588704200/PD588704300.
3) Order PCU's as required per List 21 or 22.
List 8: Interface Components for One (1) PCU Expansion Shelf
List of Parts
Features
♦
Provides components to add one (1) PCU Expansion Shelf to the power system.
Spec. No. 588700801 or 588703700 for Lists 1 through 6.
Spec. No. 588704300 for Lists 5 and 6.
♦
Includes two (2) 347177800 shelf interconnect busbars.
Restrictions
Includes PCU Shelf interconnect components only.
Due to AC input connection routing, only one VPS Expansion Shelf (Spec No. 588704300) may be mounted
directly below VPS Intelligence Shelf (Spec. No. 588704200).
Ordering Notes
1) Order PCU Shelf as required per PD588700701/PD588700801 or PD588703600/PD588703700 (Lists 1
through 6), or PD588704200/PD588704300 (Lists 5 and 6).
2) Order PCU Shelf options as required per Lists 24 or 27, 32, and 72; and PD588700701/PD588700801, or
PD588703600/PD588703700, or PD588704200/PD588704300.
3) Order PCU's as required per List 21 or 22.
Page 9 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582122500
Issue AH, July 31, 2008
System Application Guide
Spec. No. 582122500 (Model 1231V2)
Home
List 21: V50B50 PCU
List of Parts
Features
♦
Provides one (1) Model V50B50 (-48V/50A), Spec. No. 486529902, PCU.
Restrictions
For use in Spec. No. 588700701, 588700801, 588704200, and 588704300 PCU Shelves only.
Ordering Notes
1) Each shelf holds up to four (4) PCU's.
List 22: V65B50 PCU
List of Parts
Features
♦
Provides one (1) Model V65B50 (-48V/65A), Spec. No. 486531800, PCU.
Restrictions
For use in Spec. No. 588703600 and 588703700 PCU Shelves only.
Ordering Notes
1) Each shelf holds up to four (4) PCU's.
List 24: Optional PCU Shelf Class B Filter
List of Parts
Features
♦
Consists of four Part No. 433800199 Input Filter Assemblies (one for each PCU mounting position in a
single shelf) and capacitor pigtail assemblies. Refer to PD588700701/PD588700801,
PD588703600/PD588703700, or PD588704200/PD588704300 for further description.
Restrictions
Cannot be installed if 582122500 List 27 ordered. The PCU Shelf can only accommodate 582122500 List 24
or 582122500 List 27, not both.
Ordering Notes
1) Specify one (1) List 24 per PCU Shelf.
List 27: Optional PCU Shelf High AC Input Voltage Disconnect and Reconnect
List of Parts
Features
♦
Consists of four Part No. 486390500 High AC Input Voltage Disconnect and Reconnect circuit card
assemblies (one for each PCU mounting position in a single shelf). Refer to
PD588700701/PD588700801, PD588703600/PD588703700, or PD588704200/PD588704300 for further
description.
Restrictions
Cannot be installed if 582122500 List 24 ordered. The PCU Shelf can only accommodate 582122500 List 24
or 582122500 List 27, not both.
Ordering Notes
1) Specify one (1) List 27 per PCU Shelf.
Page 10 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582122500 (Model 1231V2)
SAG582122500
Issue AH, July 31, 2008
Home
List 32: PCU Shelf AC Input Line Cords
List of Parts
Features
♦
Consists of four (4) 14’ long AC input line cords (one for each PCU mounting position in a single shelf).
Refer to PD588700701/PD588700801 or PD588703600/PD588703700 for further description.
Restrictions
For use with PCU Shelves Spec. Nos. 588700701, 588700801, 588703600, and 588703700 only. CANNOT
be used with PCU Shelves Spec. Nos. 588704200 and 588704300.
Must be used with the standard PCU Shelf AC input housing assembly. Cannot be used with the optional
PCU Shelf single or dual feed AC input housing assemblies.
Ordering Notes
1) Specify one (1) List 32 per PCU Shelf.
List 72: Vortex® WinLink Hardware (Modem Interface)
List of Parts
Features
♦
Provides Spec. No. 483215200 which consists of a 2400 bits/s Modem circuit card, Spec. No.
486781300, plus associated hardware.
♦
This option plugs into the side of the VPS Intelligence Shelf.
Restrictions
Only one interface option (Vortex WinLink Hardware or RS-485 can be installed on the VPS Intelligence
Shelf.
Do not order this option when the VPS is to be interfaced with a Vortex SMART or SMART DGU.
Ordering Notes
1) Order this option for each VPS (MCA) to be accessed via Vortex WinLink Software.
List 73: Vortex® WinLink Software
List of Parts
Features
♦
Provides Spec. No. 041182000 (Vortex WinLink Software).
♦
Vortex WinLink Software provides the user the ability to remotely communicate with multiple VPS's
equipped with the Vortex WinLink Hardware option. Only one VPS can be remotely connected at a time.
This allows a user to remotely monitor, control, and adjust the VPS via Vortex WinLink. Remote
communication is done over dial-up phone lines when the VPS is equipped with the modem interface (List
72).
♦
With Vortex WinLink Software, the same tasks accomplished via the VPS's MCA local interface pad can
be done remotely. This includes alarm monitoring, voltage/current monitoring, and adjustment of alarm
and control circuits.
♦
The Vortex WinLink software, Spec. No. 041182000, runs under the Windows 95/NT platform.
Ordering Notes
1) Only one List 73 required for each computer installation.
Page 11 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582122500
Issue AH, July 31, 2008
System Application Guide
Spec. No. 582122500 (Model 1231V2)
Home
ACCESSORY INFORMATION
Lugs
All lugs for customer connections must be ordered separately.
For lug selection, refer to the CRIMP LUG TABLE.
For additional lug information, refer to Drawings 031110100 through 031110300.
Output Lugs
Output lug requirements are determined by site requirements.
Output conductors and lugs are connected to the main and supplemental bays’ output busbars. These
busbars are provided with holes for installation of customer provided two hole lugs with 1 inch centers and
3/8 inch bolt clearance holes. Customer must provide lug mounting bolts and additional hardware. For lug
mounting hole size and spacing dimensions, refer to DIMENSIONS.
The output busbars are designed to accommodate the lugs listed in Table 1. Use Table 1 to select
recommended output lead sizes and lugs for various bay output current capacities. Wire sizes based on
recommendations of the National Electrical Code Table 310-16 for copper wire at 90°C conductor
temperature, operating in ambient of 50°C. For operation in other ambients, see Table 310-16 of the National
Electrical Code. Recommended wire sizes are sufficient to restrict voltage drop to the values listed in Table 1
at stated bay output current for the loop lengths listed in Table 1. Loop length is the sum of the lengths of the
positive and negative leads.
Page 12 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582122500 (Model 1231V2)
SAG582122500
Issue AH, July 31, 2008
Home
Lug and Wire Selection Table
LUG AND WIRE SIZE SELECTION
(Two-Hole Lug, 3/8" Bolt Clearance Hole, 1" Centers)
Bay’s
Output
Current
Loop
Length*
Recommended Crimp Lug
Recm
Wire
Size*
0.25
Volt
Drop
1.0
Volt
Drop
Wire
Stranding
Class
1200A
18 ft.
75 ft.
(Qty. 6)
4/0 Ga.
B
245347400
(Burndy YA28L-2TC38)
1000A
18 ft.
75 ft.
(Qty. 5)
4/0 Ga.
B
245347400
(Burndy YA28L-2TC38)
800A
18 ft.
75 ft.
(Qty. 4)
4/0 Ga.
B
245347400
(Burndy YA28L-2TC38)
600A
18 ft.
75 ft.
(Qty. 3)
4/0 Ga.
B
245347400
(Burndy YA28L-2TC38)
400A
18 ft.
75 ft.
(Qty. 2)
4/0 Ga.
B
245347400
(Burndy YA28L-2TC38)
200A
18 ft.
75 ft.
(Qty. 1)
4/0 Ga.
B
245347400
(Burndy YA28L-2TC38)
Part No.
* Refer to OUTPUT LUGS for applicable information.
Table 1
Recommended Output Lead Sizes and Crimp Lugs
Page 13 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582122500
Issue AH, July 31, 2008
System Application Guide
Spec. No. 582122500 (Model 1231V2)
Home
Standard Crimp Lug Part Numbers
CRIMP LUGS
(Two-Hole, 3/8” Bolt Clearance Hole, 1.000” Centers)
LEAD SIZE (Ga.)
PART NUMBER
8
245349800
6
245349900
4
245350000
2
245348200
1/0
2/0
3/0
4/0
250 MCM
300 MCM
350 MCM
400 MCM
500 MCM
600 MCM
750 MCM
245347100
245347200
245347300
245347400
245347500
245347600
245347700
245347800
245347900
245348000
245348100
Page 14 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582122500 (Model 1231V2)
SAG582122500
Issue AH, July 31, 2008
Home
Relay Rack Options (for use with Lists 3, 4, and 6 only)
This system is factory mounted to the relay rack specified when ordered (List 3, 4, and 6 only). The following
relay racks are available:
AVAILABLE
MOUNTING POSITIONS
PART
NUMBER
SIZE
500091
25-1/8”H x 23”W
13U
Allows for mounting of one (1) VPS PCU Shelf
377333500
27-1/2”H x 23”W
14U
Allows for mounting of one (1) VPS PCU Shelf
377333600
35-7/16”H x 23”W
19U
Allows for mounting of two (2) VPS PCU
Shelves
377332900
39-1/8”H x 23”W
21U
Allows for mounting of two (2) VPS PCU
Shelves with List 6 or three (3) with Lists 3
and 4
NOTES
1U = 1-3/4”
Seismic (complies with Bellcore Seismic Zone
4 requirements)
377334300
7’0”H x 23”W
45U
412404600
7’0”H x 23”W
45U
Allows for mounting of up to six (6) VPS PCU
Shelves
412404700
7’6”H x 23”W
48U
Allows for mounting of up to six (6) VPS PCU
Shelves
Allows for mounting of up to six (6) VPS PCU
Shelves
Note 1: For additional relay rack options, see drawing 412202500.
Page 15 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582122500
Issue AH, July 31, 2008
System Application Guide
Spec. No. 582122500 (Model 1231V2)
Home
Replacement Cables
Ordering Notes
1) Standard External Alarm Interconnect Cable: Provides mating connector and sixty (60) foot long cable
as a convenient method of connecting the external alarm wiring of the VPS Intelligence Shelf to customer
circuits. Connects to J8 on the VPS Intelligence Shelf and provides 28 gauge leads to be spliced to
customer leads. For a replacement cable, order Part No. 421630900 (60'0" cable). Note: For a longer
cable, see Optional Cables below.
2) VPS to VPS Interconnect Cable: Provides mating connectors and cable as a convenient method of
connecting the alarm, reference, and control leads of a VPS to a subsequent VPS. Connects between J1
on "Connector Assembly" circuit card 500441 located within the VPS and J2 on "Connector Assembly"
circuit card 500441 located within the subsequent VPS. For a replacement cable, order Part No. 100916
(25'0" cable).
3) "Connector Assembly" Circuit Card to VPS Intelligence Shelf (MCA) Interconnect Cable: Provides
mating connectors and cable as a convenient method of connecting the alarm, reference, and control
terminals provided on the "Connector Assembly" circuit card for customer connections and system
interface to the MCA in the VPS Intelligence Shelf. Connects between J2 on "Connector Assembly"
circuit card 500441 located in the main VPS and J9 on the VPS Intelligence Shelf located within the same
rack. For a replacement cable, order Part No. 421868200 (13.5" cable).
4) "Connector Assembly" Circuit Card to VPS Intelligence Shelf (MCA/PCU's) Interconnect Cable:
Provides mating connectors and cable as a convenient method for MCA signal interconnection between
the terminals provided on the "Connector Assembly" circuit card for customer connections and interface
to PCU's located in other racks. Connects between J8, J9, or J10 on "Connector Assembly" circuit card
500441 located in the main VPS and J11 or J12 on the VPS Intelligence Shelf located within the same
rack. For a replacement cable, order Part No. 100573 (11.5" cable).
5) VPS Intelligence and Expansion Shelves Interconnect Cable (when located in same rack):
Provides mating connectors and cable as a convenient method for MCA signal interconnection between
the VPS Intelligence Shelf and a VPS Expansion Shelf or between two VPS Expansion Shelves, located
in the same rack. Connects between J11 and J12 of each shelf. A cable is provided with each VPS
Expansion Shelf. For a replacement cable, order Part No. 100573 (11.5" cable).
6) VPS Intelligence and Expansion Shelves Interconnect Cable (when located in separate racks):
Provides mating connectors and cable as a convenient method for MCA signal interconnection between
VPS PCU Shelves located in separate racks. VPS PCU Shelves in the same rack are interconnected as
described in 5). The VPS Intelligence Shelf is interconnected to the "Connector Assembly" circuit card as
described in 4). Up to two additional racks of PCU Shelves are interconnected via the "Connector
Assembly" circuit card. Each interconnect cable connects between J8, J9, or J10 on "Connector
Assembly" circuit card 500441 located in the main VPS and J11 or J12 of the top most VPS PCU Shelf
located in a separate rack. For a replacement cable, order Part No. 100575 (25'0" cable). A 12'0" cable
is also available, Part No. 100574.
Optional Cables
External Alarm Interconnect Cable, Part no. 521216: Provides mating connector and 100-foot long cable as a
convenient method of connecting the external alarm wiring of the VPS Intelligence Shelf to customer circuits.
Connects to J8 on the VPS Intelligence Shelf and provides 28 gauge leads to be spliced to customer leads.
Provides alarm relay connections only. Does not provide external control connections for Remote HVSD, Remote
Emergency Shutdown, or Remote Test/Equalize functions.
Can be used in place of the standard 60-ft.alarm cable, Part No. 421630900, when a longer cable is required and
external control connections are not required.
Page 16 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582122500 (Model 1231V2)
SAG582122500
Issue AH, July 31, 2008
Home
LIST OF PARTS
(This Stocklist may not list every component contained in each List.)
PART
NUMBER
LIST
NUMBER
QTY.
1
1
1
1
1
1
1
505287
505289
505290
505332
505505
421630900
Shield, E Shape, Rear Busbar
Busbar, C Shaped, Neg Bat
Busbar, Irregular U Shaped, Pos Bat
Assy, Alm/Interface
Hardware Kit
Cable Assy
2
1
1
1
1
1
1
1
100575
505169
505286
505287
505289
505290
505505
Cable Assy
Panel, Irreg, Busbar Support
Panel, Hat Shape, Shunt/Alm Interface
Shield, E Shape, Rear Busbar
Busbar, C Shaped, Neg Bat
Busbar, Irregular U Shaped, Pos Bat
Hardware Kit
3
1
1
1
1
1
1
505287
505289
505290
505332
505505
421630900
Shield, E Shape, Rear Busbar
Busbar, C Shaped, Neg Bat
Busbar, Irregular U Shaped, Pos Bat
Assy, Alm/Interface
Hardware Kit
Cable Assy
4
1
1
1
1
1
1
1
100575
505169
505286
505287
505289
505290
505505
Cable Assy
Panel, Irreg, Busbar Support
Panel, Hat Shape, Shunt/Alm Interface
Shield, E Shape, Rear Busbar
Busbar, C Shaped, Neg Bat
Busbar, Irregular U Shaped, Pos Bat
Hardware Kit
5
1
1
1
508573
508586
421630900
Panel, Mounting Frame
Assy, Alm/Interface
Cable Assy
6
1
1
508586
421630900
Assy, Alm/Interface
Cable Assy
7
1
1
1
100573
505506
421868200
Cable Assy
Hardware Kit
Cable Assy
8
2
347177800
Busbar & Associated Hardware
21
1
486529902
Rect, Vortex PCU, 48V, 50A
22
1
486531800
Rect, Vortex PCU, 48V, 65A
24
6
2
2
4
425140100
425140400
425140600
433800199
Pigtail Assy
Pigtail Assy
Pigtail Assy
Class B EMI Filter PW Assy
27
4
486390500
High AC Volt Shutdown PW Assy
DESCRIPTION
Page 17 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582122500
Issue AH, July 31, 2008
System Application Guide
Spec. No. 582122500 (Model 1231V2)
Home
PART
NUMBER
LIST
NUMBER
QTY.
32
1
1
1
1
104821
104836
104837
104838
Cord, AC Input
Cord, AC Input
Cord, AC Input
Cord, AC Input
72
1
483215200
Kit, MCA Modem Install
73
1
041182000
Vortex WinLink Software
DESCRIPTION
Page 18 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582122500 (Model 1231V2)
SAG582122500
Issue AH, July 31, 2008
Home
PHYSICAL SIZE INFORMATION
Overall Dimensions - Lists 1-4
TOP VIEW
24.31
5.25
17.50
TOP PANEL
LEFT SIDE VIEW
FRONT VIEW
RIGHT SIDE VIEW
NOTES :
1. ALL DIMENSIONS ARE IN INCHES
UNLESS OTHERWISE SPECIFIED.
2. WEIGHT IN LBS. (TOP PANEL AND BUSBARS ONLY)
NET: 25
SHIPPING: 30
(refer to PCU Shelves Power Data Sheets for their weights)
3. FINISH: OFF-WHITE
4.
INDICATES
VENTILATING
GRILLE
5. REFER TO THE PCU SHELVES POWER
DATA SHEETS FOR THEIR DIMENSIONS
Page 19 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582122500
Issue AH, July 31, 2008
System Application Guide
Spec. No. 582122500 (Model 1231V2)
Home
Overall Dimensions - Lists 5-6
FRONT VIEW
REAR VIEW
Mounting Frame
(P/O List 5 Only)
LEFT SIDE VIEW
33.25 29.75
NOTES :
RIGHT SIDE VIEW
17.25
1. ALL DIMENSIONS ARE IN INCHES
UNLESS OTHERWISE SPECIFIED.
24.50
2. WEIGHT IN LBS.
(TOP CABINET, TWO PCU SHELVES,
EIGHT PCU's, AND SHIPPING FRAME)
NET: 207
SHIPPING: 225
3. FINISH: OFF-WHITE
4.
INDICATES
VENTILATING
GRILLE
TOP VIEW
Page 20 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582122500 (Model 1231V2)
SAG582122500
Issue AH, July 31, 2008
Home
Output Busbar Dimensions - Lists 1-4
3/8" CLEARANCE HOLES, 12 PLACES
(CUSTOMER MUST SUPPLY
LUG MOUNTING BOLTS AND
ADDITIONAL HARDWARE)
SUPPLY
-48V
GND RTN
+48V
1.000
1.000
1.250
POS
NEG
POS
NEG
REAR VIEW
Page 21 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582122500
Issue AH, July 31, 2008
System Application Guide
Spec. No. 582122500 (Model 1231V2)
Home
Output Busbar Dimensions - Lists 5-6
TO
+BATTERY
(GND RTN
+48V)
TO
GND BAR
(GND RTN
+48V)
1.000
TO
DISTR.
(SUPPLY
-48V)
TO
-BATTERY
(SUPPLY
-48V)
1.000
1.000
1.250
+BAT
DIST
GRD
-BAT
FRONT VIEW
3/8" CLEARANCE
HOLES, 24 PLACES
(CUSTOMER MUST SUPPLY
LUG MOUNTING BOLTS AND
ADDITIONAL HARDWARE)
Components
removed in
illustration
for clarity.
Page 22 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide
Spec. No. 582122500 (Model 1231V2)
SAG582122500
Issue AH, July 31, 2008
Home
RELATED DOCUMENTATION
VPS Intelligence and Expansion Shelf Power Data Sheets (includes PCU and MCA info):
PD588700701/PD588700801 (V200ICAB/V200ECAB)
PD588703600/PD588703700 (V260ICAB/V260ECAB)
PD588704200/PD588704300 (V200ICAB/V200ECAB)
Schematic Diagram:
SD582122500 (VPS)
SD505332 (Alarm/Interface Panel)
SD508586 (Alarm/Interface Panel)
SD588700701 (V200ICAB)
SD588700801 (V200ECAB)
SD588703600 (V260ICAB)
SD588703700 (V260ECAB)
SD588704200 (V200ICAB)
SD588704300 (V200ECAB)
Wiring Diagram:
T505332 (Alarm/Interface Panel)
T508586 (Alarm/Interface Panel)
T588700701 (V200ICAB)
T588700801 (V200ECAB)
T588703600 (V260ICAB)
T588703700 (V260ECAB)
T588704200 (V200ICAB)
T588704300 (V200ECAB)
Color MCA Menu Tree:
Section 5762
Instructions:
Section 5806 (System User Instructions)
Section 5878 (System Installation Instructions)
Load and Battery Lug Detail Drawings: 031110100 through 031110300
Page 23 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582122500
Issue AH, July 31, 2008
System Application Guide
Spec. No. 582122500 (Model 1231V2)
Home
REVISION RECORD
Rev
Change
Number
(ECO)
AA
LLP010235
AB
LLP016262
AC
LLP033070
AD
LLP036276
AE
Description of Change
Date
3/7/00
LLP202677
New
List 5 and 6 added. 588704200 added to List
7. 588704300 added to List 8. Loop length for
0.25 volt drop added to Table 1. Revised
ENVIRONMENT statement on 1st page.
Spec. No. 588703600 and 588703700 PCU
Shelves added. List 22 PCU added.
RELATED DOCUMENTATION section
updated.
Name/Logo Change.
AF
LLP201418
Added P/N 521216 cable to Accessories.
AG
LLP205204
AH
LLP210437
Revised List 7 and 8 features and ordering
notes.
Part number 486529901 now 486529902.
Approved
J. Jasko, S. Lewis
1/23/01
Steve McWilliams
8/5/02
John Jasko
09/26/03
John Jasko
12/02/04
3/18/05
3/21/05
John Jasko
P. Amato
J. Kirkpatrick
1/20/06
J. Kirkpatrick
07/31/08
John Jasko
E-Signed by John Jasko 8/1/2008 using ApproveIt
E-Signed by Bruce Walsh 8/20/2008 using ApproveIt
8/1/2008
8/20/2008
Emerson Network Power, Energy Systems, North America, Inc.
1122 F Street / Lorain, Ohio 44052-2293 / (440) 288-1122
In Canada:
Emerson Electric Canada Limited
122 Edward St. / St. Thomas, Ontario N5P 1Z2 / (519) 637-4900
In Mexico:
Emerson Network Power de Mexico, S.A. de C.V.
Apartado Postal 77001 / Mexico 10 D.F., MX 11200 / (525) 576-8277
Page 24 of 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.