SAG582122500 System Application Guide Spec. No. 582122500 (Model 1231V2) Issue AH, July 31, 2008 Home SYSTEM OVERVIEW Description: This system provides a solution to replace traditional power with power derived from the Vortex® platform, or to expand existing Vortex Power Systems (VPS’s) to meet additional power needs. A VPS typically consists of ... • one front access VPS Intelligence Shelf, which houses Power Conversion Units (PCU’s). Also includes the Meter-Control-Alarm (MCA) assembly, which controls the operation of up to fifty-six (56) PCU’s, and provides system metering, control, and alarm functions. • one or more optional front access VPS Expansion Shelves, each of which houses PCU’s. • PCU’s which provide load power, battery float current, and battery recharge current during normal operating conditions. List 1 and 3 Shown List 2 and 4 Similar (no Intelligence Shelf) Family: Vortex Spec. No.: 582122500 Model: 1231V2 Output Voltage: -48 Volts DC Output Capacity System: PCU: 1200 amperes, maximum, per bay 50 amperes or 65 amperes, per PCU Framework Type: Relay Rack Mounting Width: 23 Inches per Bay Mounting Depth: 18 Inches Access: Front Supplemental Bay(s): Up to two (2) available Control: Microprocessor Color: Off-White (Lorain Spec. M500-117) Options: PCU Intelligence Shelf, PCU Expansion Shelf, V50B50 PCU, V65B50 PCU Accessories: PCU Shelf Class B Filter, PCU Shelf High AC Disconnect, PCU Shelf AC Input Line Cords, Vortex WinLink Hardware (Modem), Vortex WinLink Software Environment: 50°C List 5 Shown List 6 Similar Page 1 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582122500 Issue AH, July 31, 2008 System Application Guide Spec. No. 582122500 (Model 1231V2) Home 582122500 (Lists 1 through 4) Shunt POD Card (Inside) Common Equipment (Lists 1, 2, 3, and 4) Vortex WinLink Software (List 73) Vortex WinLink Hardware (Modem) (List 72) PCU Intelligence Shelf Interface (List 7) (used w/ Lists 1 and 3) AC Input Line Cords (List 32) Class B Filter or High AC Disconnect (List 24 or 27) V50B50 PCU or V65B50 PCU (List 21 or 22) Lists 1 and 3 Shown Lists 2 and 4 Similar (no Intelligence Shelf) PCU Expansion Shelf Interface (List 8) (used w/ Lists 1, 2, 3, and 4) SEE ALSO System Overview Table of Contents List Structure Table Lugs Relay Rack Options Replacement Cables List of Parts Dimensional Drawings Related Documentation Page 2 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582122500 (Model 1231V2) SAG582122500 Issue AH, July 31, 2008 Home 582122500 (Lists 5 and 6) Shunt POD Card (Inside) Common Equipment (Lists 5 and 6) Vortex WinLink Software (List 73) Vortex WinLink Hardware (Modem) (List 72) PCU Intelligence Shelf Interface (List 7) (used w/ Lists 5 and 6) Class B Filter or High AC Disconnect (List 24 or 27) V50B50 PCU (List 21) PCU Expansion Shelf Interface (List 8) (used w/ Lists 5 and 6) List 5 Shown List 6 Similar Mounting Frame (P/O List 5 only) SEE ALSO System Overview Table of Contents List Structure Table Lugs Relay Rack Options Replacement Cables List of Parts Dimensional Drawings Related Documentation Page 3 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582122500 Issue AH, July 31, 2008 System Application Guide Spec. No. 582122500 (Model 1231V2) TABLE OF CONTENTS System Overview Picture Lists 1-4 Lists 5-6 List Information Accessory Information List of Parts Physical Size Information Related Documentation SYSTEM OVERVIEW................................................................................................................................................ 1 TABLE OF CONTENTS ............................................................................................................................................ 4 LIST INFORMATION................................................................................................................................................. 5 List Structure........................................................................................................................................................ 5 List Descriptions .................................................................................................................................................. 6 List 1: Common Equipment for Main Power Bay (Ship Loose)......................................................................... 6 List 2: Common Equipment for Supplemental Power Bay (Ship Loose)........................................................... 6 List 3: Common Equipment for Main Power Bay (Factory Mounted in a Relay Rack) ..................................... 7 List 4: Common Equipment for Supplemental Power Bay (Factory Mounted in a Relay Rack) ....................... 7 List 5: Common Equipment for Main Power Bay Mounted on Shipping Frame................................................ 8 List 6: Common Equipment for Main Power Bay (Factory Mounted in a Relay Rack) ..................................... 8 List 7: Interface Components for One (1) PCU Intelligence Shelf..................................................................... 9 List 8: Interface Components for One (1) PCU Expansion Shelf ...................................................................... 9 List 21: V50B50 PCU ...................................................................................................................................... 10 List 22: V65B50 PCU ...................................................................................................................................... 10 List 24: Optional PCU Shelf Class B Filter ...................................................................................................... 10 List 27: Optional PCU Shelf High AC Input Voltage Disconnect and Reconnect ........................................... 10 List 32: PCU Shelf AC Input Line Cords ......................................................................................................... 11 List 72: Vortex® WinLink Hardware (Modem Interface).................................................................................. 11 List 73: Vortex® WinLink Software.................................................................................................................. 11 ACCESSORY INFORMATION ............................................................................................................................... 12 Lugs..................................................................................................................................................................... 12 Output Lugs ...................................................................................................................................................... 12 Lug and Wire Selection Table .......................................................................................................................... 13 Standard Crimp Lug Part Numbers .................................................................................................................. 14 Relay Rack Options (for use with Lists 3, 4, and 6 only) ............................................................................... 15 Replacement Cables.......................................................................................................................................... 16 Optional Cables.................................................................................................................................................. 16 LIST OF PARTS...................................................................................................................................................... 17 PHYSICAL SIZE INFORMATION ........................................................................................................................... 19 Overall Dimensions - Lists 1-4.......................................................................................................................... 19 Overall Dimensions - Lists 5-6.......................................................................................................................... 20 Output Busbar Dimensions - Lists 1-4 ............................................................................................................ 21 Output Busbar Dimensions - Lists 5-6 ............................................................................................................ 22 RELATED DOCUMENTATION............................................................................................................................... 23 REVISION RECORD ............................................................................................................................................... 24 Page 4 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582122500 (Model 1231V2) SAG582122500 Issue AH, July 31, 2008 Home LIST INFORMATION List Structure List Number Description Part Number Mounting Positions (1U = 1-3/4”) 1 2 1 58212250001 Common Equipment, Main Bay (Ship Loose) 3U 1 2 58212250002 Common Equipment, Supplemental Bay (Ship Loose) 3U 1 3 58212250003 Common Equipment, Main Bay (Factory Installed in Specified Relay Rack) 3U 1 4 58212250004 Common Equipment, Supplemental Bay (Factory Installed in Specified Relay Rack) 3U 1 5 58212250005 Common Equipment, Main Bay, Mounted on Shipping Frame 19U 2 6 58212250006 Common Equipment, Main Bay (Factory Installed in Specified Relay Rack) 5U 1 7 58212250007 Interface Components for PCU Intelligence Shelf 6U 8 58212250008 Interface Components for PCU Expansion Shelf 6U 21 58212250021 V50B50 PCU for V200ICAB and V200ECAB Shelves -- 22 58212250022 V65B50 PCU for V260ICAB and V260ECAB Shelves -- 24 58212250024 Class B Filter for PCU Shelves -- 27 58212250027 High AC Disconnect for PCU Shelves -- 32 58212250032 AC Input Line Cords (Individual PCU Feeds) for PCU Shelves -- 72 58212250072 Vortex WinLink Hardware (Modem) for PCU Intelligence Shelf -- 73 58212250073 Vortex WinLink Software -- Lists 1-4, and 6: Mounting Positions Height does not include PCU Shelves. List 5: Mounting Positions Height includes two (2) PCU Shelves. Page 5 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582122500 Issue AH, July 31, 2008 System Application Guide Spec. No. 582122500 (Model 1231V2) Home List Descriptions List 1: Common Equipment for List of Parts Main Power Bay (Ship Loose) Features ♦ Provides output lead termination busbars for connection of customer DC power leads. ♦ Provides a shunt POD circuit card (433800164) to allow current monitoring of an external load shunt. The Shunt POD interfaces with the VPS's MCA for remote shunt monitoring. ♦ Provides a “Connector Assembly” circuit card for external alarm, reference, and control connections; and system interconnects. ♦ Includes 60’ long alarm extension cable, Part No. 421630900, for customer connections to VPS Intelligence Shelf external alarm and control circuits. Restrictions The system can consist of a main power bay, and up to two (2) supplemental power bays. Ordering Notes 1) Components shipped loose for mounting on a customer provided relay rack. 2) Order PCU Shelf(s) as required per Lists 7 and 8. 3) Order PCU Shelf options as required per Lists 24 or 27 and 32; and the appropriate PCU Shelf Power Data Sheet. 4) Order PCU's as required per List 21 or 22. 5) Order Vortex WinLink Hardware and Software as required per List 72 and 73. 6) Order output lugs as required per CRIMP LUGS table. List 2: Common Equipment for Supplemental Power Bay (Ship Loose) List of Parts Features ♦ Provides output lead termination busbars for connection of customer DC power leads. ♦ Includes 25’ long interbay cable, Part No. 100575. Restrictions The system can consist of a main power bay, and up to two (2) supplemental power bays. Ordering Notes 1) Components shipped loose for mounting on a customer provided relay rack. 2) Order PCU Shelf(s) as required per List 8. 3) Order PCU Shelf options as required per Lists 24 or 27 and 32; and the appropriate PCU Shelf Power Data Sheet. 4) Order PCU's as required per List 21 or 22. 5) Order output lugs as required per CRIMP LUGS table. Page 6 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582122500 (Model 1231V2) SAG582122500 Issue AH, July 31, 2008 Home List 3: Common Equipment for Main Power Bay (Factory Mounted in a Relay Rack) List of Parts Features ♦ Provides output lead termination busbars for connection of customer DC power leads. ♦ Provides a shunt POD circuit card (433800164) to allow current monitoring of an external load shunt. The Shunt POD interfaces with the VPS's MCA for remote shunt monitoring. ♦ Provides a “Connector Assembly” circuit card for external alarm, reference, and control connections; and system interconnects. ♦ Includes 60’ long alarm extension cable, Part No. 421630900, for customer connections to VPS Intelligence Shelf external alarm and control circuits. Restrictions The system can consist of a main power bay, and up to two (2) supplemental power bays. Ordering Notes 1) Factory mounted in relay rack ordered per RELAY RACK OPTIONS table. 2) Order PCU Shelf(s) as required per Lists 7 and 8. 3) Order PCU Shelf options as required per Lists 24 or 27 and 32; and the appropriate PCU Shelf Power Data Sheet. 4) Order PCU's as required per List 21 or 22. 5) Order Vortex WinLink Hardware and Software as required per List 72 and 73. 6) Order output lugs as required per CRIMP LUGS table. List 4: Common Equipment for Supplemental Power Bay (Factory Mounted in a Relay Rack) List of Parts Features ♦ Provides output lead termination busbars for connection of customer DC power leads. ♦ Includes 25’ long interbay cable, Part No. 100575. Restrictions The system can consist of a main power bay, and up to two (2) supplemental power bays. Ordering Notes 1) Factory mounted in relay rack ordered per RELAY RACK OPTIONS table. 2) Order PCU Shelf(s) as required per List 8. 3) Order PCU Shelf options as required per Lists 24 or 27 and 32; and the appropriate PCU Shelf Power Data Sheet. 4) Order PCU's as required per List 21 or 22. 5) Order output lugs as required per CRIMP LUGS table. Page 7 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582122500 Issue AH, July 31, 2008 System Application Guide Spec. No. 582122500 (Model 1231V2) Home List 5: Common Equipment for Main Power Bay Mounted on Shipping Frame List of Parts Features ♦ All Equipment Cabinets Mounted to a Shipping Frame. ♦ Provides output lead termination busbars for connection of customer DC power leads. ♦ Provides 800A Internal Load Shunt. ♦ Provides a shunt POD circuit card (433800164) to allow current monitoring of the internal load shunt. The Shunt POD interfaces with the VPS's MCA for shunt monitoring. ♦ Provides a “Connector Assembly” circuit card for external alarm, reference, and control connections; and system interconnects. ♦ Includes 60’ long alarm extension cable, Part No. 421630900, for customer connections to VPS Intelligence Shelf external alarm and control circuits. Restrictions The system consists of a main power bay only. Ordering Notes 1) Components mounted on a shipping frame for mounting onto a customer provided relay rack. 2) Order PCU Shelf(s) as required per Lists 7 and 8. 3) Order PCU Shelf options as required per Lists 24 or 27; and the appropriate PCU Shelf Power Data Sheet. 4) Order PCU's as required per List 21. 5) Order Vortex WinLink Hardware and Software as required per List 72 and 73. 6) Order output lugs as required per CRIMP LUGS table. List 6: Common Equipment for Main Power Bay (Factory Mounted in a Relay Rack) List of Parts Features ♦ Provides output lead termination busbars for connection of customer DC power leads. ♦ Provides 800A Internal Load Shunt. ♦ Provides a shunt POD circuit card (433800164) to allow current monitoring of the internal load shunt. The Shunt POD interfaces with the VPS's MCA for shunt monitoring. ♦ Provides a “Connector Assembly” circuit card for external alarm, reference, and control connections; and system interconnects. ♦ Includes 60’ long alarm extension cable, Part No. 421630900, for customer connections to VPS Intelligence Shelf external alarm and control circuits. Restrictions The system consists of a main power bay only. Ordering Notes 1) Factory mounted in relay rack ordered per RELAY RACK OPTIONS table. 2) Order PCU Shelf(s) as required per Lists 7 and 8. Page 8 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582122500 (Model 1231V2) SAG582122500 Issue AH, July 31, 2008 3) Order PCU Shelf options as required per Lists 24 or 27; and the appropriate PCU Shelf Power Data Sheet. Home 4) Order PCU's as required per List 21. 5) Order Vortex WinLink Hardware and Software as required per List 72 and 73. 6) Order output lugs as required per CRIMP LUGS table. List 7: Interface Components for One (1) PCU Intelligence Shelf List of Parts Features ♦ Provides components to add one (1) PCU Intelligence Shelf to the power system. Spec. No. 588700701 or 588703600 for Lists 1, 3, 5 and 6. Spec. No. 588704200 for Lists 5 and 6. ♦ Includes two interconnect cables, Part Nos. 421868200 and 100573. Restrictions Includes PCU Shelf interconnect components only. Only one (1) PCU Intelligence Shelf required per system. Must be installed in main bay (List 1, 3, 5, or 6). Due to AC input connection routing, only one VPS Expansion Shelf (Spec No. 588704300) may be mounted directly below VPS Intelligence Shelf (Spec. No. 588704200). Ordering Notes 1) Order PCU Shelf as required per PD588700701/PD588700801 or PD588703600/PD588703700 (Lists 1, 3, 5 and 6), or PD588704200/PD588704300 (Lists 5 and 6). 2) Order PCU Shelf options as required per Lists 24 or 27, 32, and 72; and PD588700701/PD588700801, or PD588703600/PD588703700, or PD588704200/PD588704300. 3) Order PCU's as required per List 21 or 22. List 8: Interface Components for One (1) PCU Expansion Shelf List of Parts Features ♦ Provides components to add one (1) PCU Expansion Shelf to the power system. Spec. No. 588700801 or 588703700 for Lists 1 through 6. Spec. No. 588704300 for Lists 5 and 6. ♦ Includes two (2) 347177800 shelf interconnect busbars. Restrictions Includes PCU Shelf interconnect components only. Due to AC input connection routing, only one VPS Expansion Shelf (Spec No. 588704300) may be mounted directly below VPS Intelligence Shelf (Spec. No. 588704200). Ordering Notes 1) Order PCU Shelf as required per PD588700701/PD588700801 or PD588703600/PD588703700 (Lists 1 through 6), or PD588704200/PD588704300 (Lists 5 and 6). 2) Order PCU Shelf options as required per Lists 24 or 27, 32, and 72; and PD588700701/PD588700801, or PD588703600/PD588703700, or PD588704200/PD588704300. 3) Order PCU's as required per List 21 or 22. Page 9 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582122500 Issue AH, July 31, 2008 System Application Guide Spec. No. 582122500 (Model 1231V2) Home List 21: V50B50 PCU List of Parts Features ♦ Provides one (1) Model V50B50 (-48V/50A), Spec. No. 486529902, PCU. Restrictions For use in Spec. No. 588700701, 588700801, 588704200, and 588704300 PCU Shelves only. Ordering Notes 1) Each shelf holds up to four (4) PCU's. List 22: V65B50 PCU List of Parts Features ♦ Provides one (1) Model V65B50 (-48V/65A), Spec. No. 486531800, PCU. Restrictions For use in Spec. No. 588703600 and 588703700 PCU Shelves only. Ordering Notes 1) Each shelf holds up to four (4) PCU's. List 24: Optional PCU Shelf Class B Filter List of Parts Features ♦ Consists of four Part No. 433800199 Input Filter Assemblies (one for each PCU mounting position in a single shelf) and capacitor pigtail assemblies. Refer to PD588700701/PD588700801, PD588703600/PD588703700, or PD588704200/PD588704300 for further description. Restrictions Cannot be installed if 582122500 List 27 ordered. The PCU Shelf can only accommodate 582122500 List 24 or 582122500 List 27, not both. Ordering Notes 1) Specify one (1) List 24 per PCU Shelf. List 27: Optional PCU Shelf High AC Input Voltage Disconnect and Reconnect List of Parts Features ♦ Consists of four Part No. 486390500 High AC Input Voltage Disconnect and Reconnect circuit card assemblies (one for each PCU mounting position in a single shelf). Refer to PD588700701/PD588700801, PD588703600/PD588703700, or PD588704200/PD588704300 for further description. Restrictions Cannot be installed if 582122500 List 24 ordered. The PCU Shelf can only accommodate 582122500 List 24 or 582122500 List 27, not both. Ordering Notes 1) Specify one (1) List 27 per PCU Shelf. Page 10 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582122500 (Model 1231V2) SAG582122500 Issue AH, July 31, 2008 Home List 32: PCU Shelf AC Input Line Cords List of Parts Features ♦ Consists of four (4) 14’ long AC input line cords (one for each PCU mounting position in a single shelf). Refer to PD588700701/PD588700801 or PD588703600/PD588703700 for further description. Restrictions For use with PCU Shelves Spec. Nos. 588700701, 588700801, 588703600, and 588703700 only. CANNOT be used with PCU Shelves Spec. Nos. 588704200 and 588704300. Must be used with the standard PCU Shelf AC input housing assembly. Cannot be used with the optional PCU Shelf single or dual feed AC input housing assemblies. Ordering Notes 1) Specify one (1) List 32 per PCU Shelf. List 72: Vortex® WinLink Hardware (Modem Interface) List of Parts Features ♦ Provides Spec. No. 483215200 which consists of a 2400 bits/s Modem circuit card, Spec. No. 486781300, plus associated hardware. ♦ This option plugs into the side of the VPS Intelligence Shelf. Restrictions Only one interface option (Vortex WinLink Hardware or RS-485 can be installed on the VPS Intelligence Shelf. Do not order this option when the VPS is to be interfaced with a Vortex SMART or SMART DGU. Ordering Notes 1) Order this option for each VPS (MCA) to be accessed via Vortex WinLink Software. List 73: Vortex® WinLink Software List of Parts Features ♦ Provides Spec. No. 041182000 (Vortex WinLink Software). ♦ Vortex WinLink Software provides the user the ability to remotely communicate with multiple VPS's equipped with the Vortex WinLink Hardware option. Only one VPS can be remotely connected at a time. This allows a user to remotely monitor, control, and adjust the VPS via Vortex WinLink. Remote communication is done over dial-up phone lines when the VPS is equipped with the modem interface (List 72). ♦ With Vortex WinLink Software, the same tasks accomplished via the VPS's MCA local interface pad can be done remotely. This includes alarm monitoring, voltage/current monitoring, and adjustment of alarm and control circuits. ♦ The Vortex WinLink software, Spec. No. 041182000, runs under the Windows 95/NT platform. Ordering Notes 1) Only one List 73 required for each computer installation. Page 11 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582122500 Issue AH, July 31, 2008 System Application Guide Spec. No. 582122500 (Model 1231V2) Home ACCESSORY INFORMATION Lugs All lugs for customer connections must be ordered separately. For lug selection, refer to the CRIMP LUG TABLE. For additional lug information, refer to Drawings 031110100 through 031110300. Output Lugs Output lug requirements are determined by site requirements. Output conductors and lugs are connected to the main and supplemental bays’ output busbars. These busbars are provided with holes for installation of customer provided two hole lugs with 1 inch centers and 3/8 inch bolt clearance holes. Customer must provide lug mounting bolts and additional hardware. For lug mounting hole size and spacing dimensions, refer to DIMENSIONS. The output busbars are designed to accommodate the lugs listed in Table 1. Use Table 1 to select recommended output lead sizes and lugs for various bay output current capacities. Wire sizes based on recommendations of the National Electrical Code Table 310-16 for copper wire at 90°C conductor temperature, operating in ambient of 50°C. For operation in other ambients, see Table 310-16 of the National Electrical Code. Recommended wire sizes are sufficient to restrict voltage drop to the values listed in Table 1 at stated bay output current for the loop lengths listed in Table 1. Loop length is the sum of the lengths of the positive and negative leads. Page 12 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582122500 (Model 1231V2) SAG582122500 Issue AH, July 31, 2008 Home Lug and Wire Selection Table LUG AND WIRE SIZE SELECTION (Two-Hole Lug, 3/8" Bolt Clearance Hole, 1" Centers) Bay’s Output Current Loop Length* Recommended Crimp Lug Recm Wire Size* 0.25 Volt Drop 1.0 Volt Drop Wire Stranding Class 1200A 18 ft. 75 ft. (Qty. 6) 4/0 Ga. B 245347400 (Burndy YA28L-2TC38) 1000A 18 ft. 75 ft. (Qty. 5) 4/0 Ga. B 245347400 (Burndy YA28L-2TC38) 800A 18 ft. 75 ft. (Qty. 4) 4/0 Ga. B 245347400 (Burndy YA28L-2TC38) 600A 18 ft. 75 ft. (Qty. 3) 4/0 Ga. B 245347400 (Burndy YA28L-2TC38) 400A 18 ft. 75 ft. (Qty. 2) 4/0 Ga. B 245347400 (Burndy YA28L-2TC38) 200A 18 ft. 75 ft. (Qty. 1) 4/0 Ga. B 245347400 (Burndy YA28L-2TC38) Part No. * Refer to OUTPUT LUGS for applicable information. Table 1 Recommended Output Lead Sizes and Crimp Lugs Page 13 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582122500 Issue AH, July 31, 2008 System Application Guide Spec. No. 582122500 (Model 1231V2) Home Standard Crimp Lug Part Numbers CRIMP LUGS (Two-Hole, 3/8” Bolt Clearance Hole, 1.000” Centers) LEAD SIZE (Ga.) PART NUMBER 8 245349800 6 245349900 4 245350000 2 245348200 1/0 2/0 3/0 4/0 250 MCM 300 MCM 350 MCM 400 MCM 500 MCM 600 MCM 750 MCM 245347100 245347200 245347300 245347400 245347500 245347600 245347700 245347800 245347900 245348000 245348100 Page 14 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582122500 (Model 1231V2) SAG582122500 Issue AH, July 31, 2008 Home Relay Rack Options (for use with Lists 3, 4, and 6 only) This system is factory mounted to the relay rack specified when ordered (List 3, 4, and 6 only). The following relay racks are available: AVAILABLE MOUNTING POSITIONS PART NUMBER SIZE 500091 25-1/8”H x 23”W 13U Allows for mounting of one (1) VPS PCU Shelf 377333500 27-1/2”H x 23”W 14U Allows for mounting of one (1) VPS PCU Shelf 377333600 35-7/16”H x 23”W 19U Allows for mounting of two (2) VPS PCU Shelves 377332900 39-1/8”H x 23”W 21U Allows for mounting of two (2) VPS PCU Shelves with List 6 or three (3) with Lists 3 and 4 NOTES 1U = 1-3/4” Seismic (complies with Bellcore Seismic Zone 4 requirements) 377334300 7’0”H x 23”W 45U 412404600 7’0”H x 23”W 45U Allows for mounting of up to six (6) VPS PCU Shelves 412404700 7’6”H x 23”W 48U Allows for mounting of up to six (6) VPS PCU Shelves Allows for mounting of up to six (6) VPS PCU Shelves Note 1: For additional relay rack options, see drawing 412202500. Page 15 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582122500 Issue AH, July 31, 2008 System Application Guide Spec. No. 582122500 (Model 1231V2) Home Replacement Cables Ordering Notes 1) Standard External Alarm Interconnect Cable: Provides mating connector and sixty (60) foot long cable as a convenient method of connecting the external alarm wiring of the VPS Intelligence Shelf to customer circuits. Connects to J8 on the VPS Intelligence Shelf and provides 28 gauge leads to be spliced to customer leads. For a replacement cable, order Part No. 421630900 (60'0" cable). Note: For a longer cable, see Optional Cables below. 2) VPS to VPS Interconnect Cable: Provides mating connectors and cable as a convenient method of connecting the alarm, reference, and control leads of a VPS to a subsequent VPS. Connects between J1 on "Connector Assembly" circuit card 500441 located within the VPS and J2 on "Connector Assembly" circuit card 500441 located within the subsequent VPS. For a replacement cable, order Part No. 100916 (25'0" cable). 3) "Connector Assembly" Circuit Card to VPS Intelligence Shelf (MCA) Interconnect Cable: Provides mating connectors and cable as a convenient method of connecting the alarm, reference, and control terminals provided on the "Connector Assembly" circuit card for customer connections and system interface to the MCA in the VPS Intelligence Shelf. Connects between J2 on "Connector Assembly" circuit card 500441 located in the main VPS and J9 on the VPS Intelligence Shelf located within the same rack. For a replacement cable, order Part No. 421868200 (13.5" cable). 4) "Connector Assembly" Circuit Card to VPS Intelligence Shelf (MCA/PCU's) Interconnect Cable: Provides mating connectors and cable as a convenient method for MCA signal interconnection between the terminals provided on the "Connector Assembly" circuit card for customer connections and interface to PCU's located in other racks. Connects between J8, J9, or J10 on "Connector Assembly" circuit card 500441 located in the main VPS and J11 or J12 on the VPS Intelligence Shelf located within the same rack. For a replacement cable, order Part No. 100573 (11.5" cable). 5) VPS Intelligence and Expansion Shelves Interconnect Cable (when located in same rack): Provides mating connectors and cable as a convenient method for MCA signal interconnection between the VPS Intelligence Shelf and a VPS Expansion Shelf or between two VPS Expansion Shelves, located in the same rack. Connects between J11 and J12 of each shelf. A cable is provided with each VPS Expansion Shelf. For a replacement cable, order Part No. 100573 (11.5" cable). 6) VPS Intelligence and Expansion Shelves Interconnect Cable (when located in separate racks): Provides mating connectors and cable as a convenient method for MCA signal interconnection between VPS PCU Shelves located in separate racks. VPS PCU Shelves in the same rack are interconnected as described in 5). The VPS Intelligence Shelf is interconnected to the "Connector Assembly" circuit card as described in 4). Up to two additional racks of PCU Shelves are interconnected via the "Connector Assembly" circuit card. Each interconnect cable connects between J8, J9, or J10 on "Connector Assembly" circuit card 500441 located in the main VPS and J11 or J12 of the top most VPS PCU Shelf located in a separate rack. For a replacement cable, order Part No. 100575 (25'0" cable). A 12'0" cable is also available, Part No. 100574. Optional Cables External Alarm Interconnect Cable, Part no. 521216: Provides mating connector and 100-foot long cable as a convenient method of connecting the external alarm wiring of the VPS Intelligence Shelf to customer circuits. Connects to J8 on the VPS Intelligence Shelf and provides 28 gauge leads to be spliced to customer leads. Provides alarm relay connections only. Does not provide external control connections for Remote HVSD, Remote Emergency Shutdown, or Remote Test/Equalize functions. Can be used in place of the standard 60-ft.alarm cable, Part No. 421630900, when a longer cable is required and external control connections are not required. Page 16 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582122500 (Model 1231V2) SAG582122500 Issue AH, July 31, 2008 Home LIST OF PARTS (This Stocklist may not list every component contained in each List.) PART NUMBER LIST NUMBER QTY. 1 1 1 1 1 1 1 505287 505289 505290 505332 505505 421630900 Shield, E Shape, Rear Busbar Busbar, C Shaped, Neg Bat Busbar, Irregular U Shaped, Pos Bat Assy, Alm/Interface Hardware Kit Cable Assy 2 1 1 1 1 1 1 1 100575 505169 505286 505287 505289 505290 505505 Cable Assy Panel, Irreg, Busbar Support Panel, Hat Shape, Shunt/Alm Interface Shield, E Shape, Rear Busbar Busbar, C Shaped, Neg Bat Busbar, Irregular U Shaped, Pos Bat Hardware Kit 3 1 1 1 1 1 1 505287 505289 505290 505332 505505 421630900 Shield, E Shape, Rear Busbar Busbar, C Shaped, Neg Bat Busbar, Irregular U Shaped, Pos Bat Assy, Alm/Interface Hardware Kit Cable Assy 4 1 1 1 1 1 1 1 100575 505169 505286 505287 505289 505290 505505 Cable Assy Panel, Irreg, Busbar Support Panel, Hat Shape, Shunt/Alm Interface Shield, E Shape, Rear Busbar Busbar, C Shaped, Neg Bat Busbar, Irregular U Shaped, Pos Bat Hardware Kit 5 1 1 1 508573 508586 421630900 Panel, Mounting Frame Assy, Alm/Interface Cable Assy 6 1 1 508586 421630900 Assy, Alm/Interface Cable Assy 7 1 1 1 100573 505506 421868200 Cable Assy Hardware Kit Cable Assy 8 2 347177800 Busbar & Associated Hardware 21 1 486529902 Rect, Vortex PCU, 48V, 50A 22 1 486531800 Rect, Vortex PCU, 48V, 65A 24 6 2 2 4 425140100 425140400 425140600 433800199 Pigtail Assy Pigtail Assy Pigtail Assy Class B EMI Filter PW Assy 27 4 486390500 High AC Volt Shutdown PW Assy DESCRIPTION Page 17 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582122500 Issue AH, July 31, 2008 System Application Guide Spec. No. 582122500 (Model 1231V2) Home PART NUMBER LIST NUMBER QTY. 32 1 1 1 1 104821 104836 104837 104838 Cord, AC Input Cord, AC Input Cord, AC Input Cord, AC Input 72 1 483215200 Kit, MCA Modem Install 73 1 041182000 Vortex WinLink Software DESCRIPTION Page 18 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582122500 (Model 1231V2) SAG582122500 Issue AH, July 31, 2008 Home PHYSICAL SIZE INFORMATION Overall Dimensions - Lists 1-4 TOP VIEW 24.31 5.25 17.50 TOP PANEL LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW NOTES : 1. ALL DIMENSIONS ARE IN INCHES UNLESS OTHERWISE SPECIFIED. 2. WEIGHT IN LBS. (TOP PANEL AND BUSBARS ONLY) NET: 25 SHIPPING: 30 (refer to PCU Shelves Power Data Sheets for their weights) 3. FINISH: OFF-WHITE 4. INDICATES VENTILATING GRILLE 5. REFER TO THE PCU SHELVES POWER DATA SHEETS FOR THEIR DIMENSIONS Page 19 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582122500 Issue AH, July 31, 2008 System Application Guide Spec. No. 582122500 (Model 1231V2) Home Overall Dimensions - Lists 5-6 FRONT VIEW REAR VIEW Mounting Frame (P/O List 5 Only) LEFT SIDE VIEW 33.25 29.75 NOTES : RIGHT SIDE VIEW 17.25 1. ALL DIMENSIONS ARE IN INCHES UNLESS OTHERWISE SPECIFIED. 24.50 2. WEIGHT IN LBS. (TOP CABINET, TWO PCU SHELVES, EIGHT PCU's, AND SHIPPING FRAME) NET: 207 SHIPPING: 225 3. FINISH: OFF-WHITE 4. INDICATES VENTILATING GRILLE TOP VIEW Page 20 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582122500 (Model 1231V2) SAG582122500 Issue AH, July 31, 2008 Home Output Busbar Dimensions - Lists 1-4 3/8" CLEARANCE HOLES, 12 PLACES (CUSTOMER MUST SUPPLY LUG MOUNTING BOLTS AND ADDITIONAL HARDWARE) SUPPLY -48V GND RTN +48V 1.000 1.000 1.250 POS NEG POS NEG REAR VIEW Page 21 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582122500 Issue AH, July 31, 2008 System Application Guide Spec. No. 582122500 (Model 1231V2) Home Output Busbar Dimensions - Lists 5-6 TO +BATTERY (GND RTN +48V) TO GND BAR (GND RTN +48V) 1.000 TO DISTR. (SUPPLY -48V) TO -BATTERY (SUPPLY -48V) 1.000 1.000 1.250 +BAT DIST GRD -BAT FRONT VIEW 3/8" CLEARANCE HOLES, 24 PLACES (CUSTOMER MUST SUPPLY LUG MOUNTING BOLTS AND ADDITIONAL HARDWARE) Components removed in illustration for clarity. Page 22 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. System Application Guide Spec. No. 582122500 (Model 1231V2) SAG582122500 Issue AH, July 31, 2008 Home RELATED DOCUMENTATION VPS Intelligence and Expansion Shelf Power Data Sheets (includes PCU and MCA info): PD588700701/PD588700801 (V200ICAB/V200ECAB) PD588703600/PD588703700 (V260ICAB/V260ECAB) PD588704200/PD588704300 (V200ICAB/V200ECAB) Schematic Diagram: SD582122500 (VPS) SD505332 (Alarm/Interface Panel) SD508586 (Alarm/Interface Panel) SD588700701 (V200ICAB) SD588700801 (V200ECAB) SD588703600 (V260ICAB) SD588703700 (V260ECAB) SD588704200 (V200ICAB) SD588704300 (V200ECAB) Wiring Diagram: T505332 (Alarm/Interface Panel) T508586 (Alarm/Interface Panel) T588700701 (V200ICAB) T588700801 (V200ECAB) T588703600 (V260ICAB) T588703700 (V260ECAB) T588704200 (V200ICAB) T588704300 (V200ECAB) Color MCA Menu Tree: Section 5762 Instructions: Section 5806 (System User Instructions) Section 5878 (System Installation Instructions) Load and Battery Lug Detail Drawings: 031110100 through 031110300 Page 23 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. SAG582122500 Issue AH, July 31, 2008 System Application Guide Spec. No. 582122500 (Model 1231V2) Home REVISION RECORD Rev Change Number (ECO) AA LLP010235 AB LLP016262 AC LLP033070 AD LLP036276 AE Description of Change Date 3/7/00 LLP202677 New List 5 and 6 added. 588704200 added to List 7. 588704300 added to List 8. Loop length for 0.25 volt drop added to Table 1. Revised ENVIRONMENT statement on 1st page. Spec. No. 588703600 and 588703700 PCU Shelves added. List 22 PCU added. RELATED DOCUMENTATION section updated. Name/Logo Change. AF LLP201418 Added P/N 521216 cable to Accessories. AG LLP205204 AH LLP210437 Revised List 7 and 8 features and ordering notes. Part number 486529901 now 486529902. Approved J. Jasko, S. Lewis 1/23/01 Steve McWilliams 8/5/02 John Jasko 09/26/03 John Jasko 12/02/04 3/18/05 3/21/05 John Jasko P. Amato J. Kirkpatrick 1/20/06 J. Kirkpatrick 07/31/08 John Jasko E-Signed by John Jasko 8/1/2008 using ApproveIt E-Signed by Bruce Walsh 8/20/2008 using ApproveIt 8/1/2008 8/20/2008 Emerson Network Power, Energy Systems, North America, Inc. 1122 F Street / Lorain, Ohio 44052-2293 / (440) 288-1122 In Canada: Emerson Electric Canada Limited 122 Edward St. / St. Thomas, Ontario N5P 1Z2 / (519) 637-4900 In Mexico: Emerson Network Power de Mexico, S.A. de C.V. Apartado Postal 77001 / Mexico 10 D.F., MX 11200 / (525) 576-8277 Page 24 of 24 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.